Compact & Powerful InverterStarvert iG5A 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts Drive Solution Inverter STARVERT iG5A LS Starvert iG5A is very competitive in its price and shows an upgraded functional strength. User-friendly interface, extended inverter ranges up to 22kW, superb torque competence and small size of iG5A provides an optimum use environment. Standard compliance Compactness iG5A High performance Userfriendliness & Easy maintenance 2 Compact & Powerful Inverter iG5A Contents 4 8 9 11 13 15 16 18 20 23 25 32 33 Overview Model & Type Standard Specifications Wiring Terminal Configurations Keypad Features Parameter Setting Trial Run Dimensions Braking Resistors and Peripheral Devices Function List Protective Functions Fault Remedy 3 iG5A Powerful & Upgraded Performance iG5A provides sensorless vector control, PID control, and ground-fault protection through powerful built-in functions. Sensorless vector control The built-in sensorless vector control provides the superb speed control and powerful high torque. Torque (%) Speed vs Torque Characteristics Ground-fault protection during running The ground-fault protection of output terminal is possible during running. Speed (Hz) Vector Control Mode: Auto tuning Measure maximum Condition: Sensorless torque (%) at each speed (1/5/10/20/30/40/50/60Hz) Analog control from -10V to 10V Inputting analog signals from -10V to 10V provides user-friendly operation. +10 Forward Reverse -10 Built-in PID control The built-in PID function enables to control flow-rate, oil-pressure, temperature, etc without any extra controller. ◀ PID PID control PIDcontrol control ◀ PIcontrol control PI PI control Built-in dynamic braking circuit ◀ The built-in dynamic braking circuit minimizes deceleration time via braking resistors. Speed With braking resistor Normal state ◀ Time Built-in 485 communication The built-in RS-485 communication supports remote control and monitoring between iG5A and other equipment. Wide product range iG5A consists of the product range from 0.4 to 22KW. 4 Reducing deceleration time Modbus communication 5 . Frequency. etc) Easy parameter setting Available to control up to 31 Inverters RS-485. Chinese) Remote Control Convenient remote control to modify operation status (Forward/Reverse operation. Frequency. Current. etc) Easy parameter setting Available to control up to 31 Inverters RS-485.232C converter Monitoring Checking operation status (Voltage. English.Compact & Powerful Inverter iG5A RS-485 communication Connected to PC RS-485 . Modbus communication Connected to XGT panel Monitoring Checking operation time Automatic list-up of trip record Language support (Korean. etc) Checking modified parameters Windows support Remote Control Convenient remote control to modify operation status (Forward/Reverse operation. Frequency. Easy change of fan iG5A is designed to be the fan changeable structure in preparation for a fan breakdown. External loader (Optional) The external loader away from a panel enables to control and monitor conveniently. REMOTE KPD 2M (SV-iG5A) INV. Loader type + External type (Optional) Model name INV. iG5A provides a virtually quiet environment according to the status of operation. Cooling fan control By controlling the cooling fan. REMOTE KPD 3M (SV-iG5A) INV. And iG5A supports easy maintenance via diagnosis and fan changeable structure. User-friendly interface The 4 directions key provides easy handling and monitoring.iG5A User-friendly Interface & Easy Maintenance The parameter setting becomes easier by adopting the 4 directions key. REMOTE KPD 5M (SV-iG5A) Remarks 2m 3m 5m 6 . And the parameters made by external loader can be copied and applicable to other Inverters. iG5A can diagnose the status of output module. Diagnosis of output module Through easy parameter setting. users will be given wider choices of selecting the controller. 7 .4 to 4. PNP/NPN input Both PNP and NPN inputs become possible and these enable to use the outer power. To do so.0kW (128mm) Global standard compliance CE UL Global standard iG5A series complies with CE and UL standards.Compact & Powerful Inverter iG5A Compact Size The compact size achieves cost-efficiency and various applications. Same height from 0. 5kW (7.4HP) 5.5kW (2HP) 2.7kW (5HP) 4.iG5A Model & Type Applicable motor ranges 0. 3: 3 phase 380~480[V]) 8 . 2: 3 phase 200~230[V].0kW (5.4kW~220: 22kW) iG5A series Input voltage (1: 1 phase 200~230[V].0kW (15HP) 15.0kW (20HP) 18.5HP) 7.2kW (3HP) 3.4kW (0.5HP) 0.5kW (10HP) 11.5kW (25HP) 22.75kW (1HP) 1.0kW (30HP) 1 Phase 200V SV004iG5A-1 SV008iG5A-1 SV015iG5A-1 3 Phase 200V SV004iG5A-2 SV008iG5A-2 SV015iG5A-2 SV022iG5A-2 SV037iG5A-2 SV040iG5A-2 SV055iG5A-2 SV075iG5A-2 SV110iG5A-2 SV150iG5A-2 SV185iG5A-2 SV220iG5A-2 3 Phase 400V SV004iG5A-4 SV008iG5A-4 SV015iG5A-4 SV022iG5A-4 SV037iG5A-4 SV040iG5A-4 SV055iG5A-4 SV075iG5A-4 SV110iG5A-4 SV150iG5A-4 SV185iG5A-4 SV220iG5A-4 SV 015 iG5A 2 STARVERT Motor rating (kW) (004: 0. 76 1. capacity 1) (HP) (kW) Capacity (kVA) 2) Output rating FLA (A) 3) Max frequency Max voltage Input rating Rated voltage Rated frequency 004 0.5 88 Output rating 24 400 [Hz] 4) 3 phase 200~230V 5) 3 phase 200~230 (+10%. -15%) 50~60 [Hz] (±5%) Forced air cooling 4) 015 2 1. 5) Max.5 3. capacity 1) (HP) (kW) Capacity (kVA) 2) FLA (A) 3) Max frequency Max voltage Input rating Rated voltage Rated frequency N/C 6) 0.3 13. It can be programmable below input voltage.3 45 400 [Hz] 3 phase 380~480V 5) 3 phase 380~480 VAC (+10%.84 3 Phase 200V SV ��� iG5A-2 �� Max.84 1.5 6 037 5 3.9 2.5 0.12 1.89 004 0.3 13.5 9.9 5 015 2 1.4 4.75 1.77 1.9 5 400 [Hz] 3 phase 200~230V 5) 1phase 200~230 VAC (+10%.89 1. -15%) 50~60 [Hz] (±5%) Forced air cooling 3.66 3.89 2) 004 0.5 12 037 5 3.84 1.3 Cooling method Weight (kg) 3 Phase 400V SV ��� iG5A-4 �� Max.5 9 055 7.1 12 4) 075 10 7.1 8 040 5.4 0.9 30 185 25 18.25 008 1 0.0 4 022 3 2. output voltage cannot be higher than the input voltage.89 1.5 3.5 5.5 008 1 0.5 17 055 7.0 13.4 0.66 9.76 0.76 0. 3) Refer to 15-3 of user’s manual when carrier frequency setting (39) is above 3kHz. capacity 1) (HP) (kW) Capacity (kVA) Output rating FLA (A) 3) Max frequency Max voltage Input rating Rated voltage Rated frequency N/C 6) 0. frequency setting range is extended to 300Hz when H40 (Control mode select) is set to 3 (Sensorless vector control).0 6.7 6.2 4.75 1.75 1.77 1.5 9.2 4.2 74 220 30 22 33.5 12.4 0.2 16 110 15 11 18.5 5.5 0.95 2. 6) Self-Cooling 9 .1 16 040 5.5 29.0 9. -15%) 50~60 [Hz] (±5%) Forced air cooling 3.5 008 1 0.0 13.3 24 150 20 15 22.1 075 10 7.95 2.95 1.0 8 022 3 2.2 32 110 15 11 17.3 Cooling method Weight (kg) 1) Indicate the maximum applicable motor capacity when using 4 pole LS standard motor.0 6.7 6.9 60 185 25 18.5 28.66 3.Compact & Powerful Inverter iG5A Standard Specifications 1 Phase 200V SV ��� iG5A-1 �� Max.12 1.5 46 150 20 15 22.4 4.12 1. 2) Rated capacity is based on 220V for 200V series and 440V for 400V series. 4) Max.5 3.66 9.0 8 Cooling method Weight (kg) 0.7 39 220 30 22 34.5 0.5 12.0 9.5 015 2 1. Oil mist or dust Trip Protective function Alarm Momentary power loss Protection degree Ambient temp Storage temp Environ ment Humidity Altitude/Vibration Atmospheric pressure Location 1) Means average braking torque during Decel to stop of a motor. Communication error. Jog operation. 2nd motor select. Output voltage. Under voltage.: Continuous operation (Should be within rated input voltage. 1A 0~10Vdc (less than 10mA): Output freq. Low. Mid. Inverter overheat. PID-Inverter (V/F) operation bypass. Frequency UP/Down. Fan trip Stall prevention. External trip A. Loss of speed command. Hardware fault. Squared. Fault reset. B.) Less than AC 250V. Low. Ground fault current detection. 3-wire NPN/PNP selectable Multi-function terminal P1~P8 FWD/REV RUN. Multi-step Accel/Decel-High.: 60Hz) Digital command: 0. rated output power.6G) 70~106 kPa Protected from corrosive gas. Output phase open. Sensorless vector control Digital command: 0.000m. Combustible gas.9m/sec 2 (0. Overload Below 15 msec. 3-wire operation. Analog Hold. Over current. output frequency Analog command: 0. 5. Output current.: Auto restart enable IP 20. Multi-step Frequency-High. Mid. Duty Operation mode Frequency setting Operation features Linear. DC link selectable Over voltage. 50mA (N.. NEMA1 (Optional) -10℃~50℃ -20℃~65℃ Below 90% RH (No condensation) Below 1. -10~10V.01% of Max. Option-inverter (V/F) operation bypass. Motor overheat.) Above 15 msec.iG5A Standard Specifications Control method Frequency setting resolution Frequency accuracy Control V/F pattern Overload capacity Torque boost Dynamic braking Max. User V/F 150% per 1 min.C.06Hz (Max. output frequency Input Operation Open collector terminal Output Multi-function relay Analog output (AM) Fault output and inverter status output Less than DC 24V. 0~20mA Digital: Keypad PID. Up-down. Emergency stop. Manual/Auto torque boost 20% 1) 150% when using optional DB resistor 2) Keypad/ Terminal/ Communication option/ Remote keypad selectable Analog: 0~10V.1% of Max. N. 1A. 2) Refer to Chapter 16 of user’s manual for DB resistor specification. Less than DC 30V. Accel/Decel stop V/F. DC braking at stop. Overload protection.01Hz Analog command: 0. freq. 10 .O. braking torque Max. High AM CM Multi-function analog output signal: 0~10V 3A A contact output 3C A/B contact common 3B B contact output Potentiometer (1kohm. .Low P7 Multi-step freq. Current signal input: 0~20mA MO Multi-function open collector output MG MO Common S+ RS-485 communication terminal S- CM Input signal common 11 .Middle P8 Multi-step freq. . Setting Voltage signal input: -10~10V I Freq.4~7. .Compact & Powerful Inverter iG5A Wiring 0.5kW DB resistor (Optional) 3 phase AC input (Rated input voltage) B1 R S T G Ground B2 U V W 24 24V output P1 FX (Forward run) P2 RX (Reverse run) CM Input signal common P3 BX (Emergency stop) P4 RST (Trip reset) P5 JOG (Jog operation) CM Input signal common P6 Multi-step freq. 1/2W) VR 10V power supply for potentiometer V1 Freq. Current signal input: 0~20mA MO Multi-function open collector output MG MO Common S+ RS-485 communication terminal S- CM Input signal common 12 . .iG5A Wiring 11.Low P7 Multi-step freq. .0kW DB resistor (Optional) DC reactor 3 phase AC input (Rated input voltage) P1(+) R S T G B1 B2 N(-) U V W Ground 24 24V output P1 FX (Forward run) P2 RX (Reverse run) CM Input signal common P3 BX (Emergency stop) P4 RST (Trip reset) P5 JOG (Jog operation) CM Input signal common P6 Multi-step freq.Middle P8 Multi-step freq. 1/2W) VR 10V power supply for potentiometer V1 Freq. . Setting Voltage signal input: -10~10V I Freq.High AM CM Multi-function analog output signal: 0~10V 3A A contact output 3C A/B contact common 3B B contact output Potentiometer (1kohm.0~22. Compact & Powerful Inverter iG5A Terminal Configuration Specifications for power terminal block wiring • 0.0kW (3 phase) T B1 B2 U V W U V • 5.5 M3.5 M3.6 30.7 15/13 15/13 15/13 32/28 32/28 30.5/26.5 3.5/26.5 5.5 3.6 30.7 10/8.5kW (3 phase) R S T B1 U B2 V W • 1.5 M4 M4 M4 M5 M5 M6 M6 M8 M8 M3.5 3.7/26.7/26.5 3.5 30.75kW (1 phase) R T B1 B2 W • 0.5 8 14 22 30 38 2 2 2 2 2 2 3.5 5.5kW (3 phase) B1 R S B2 T U V R S • 11~22kW (3 phase) W R(L1) R.5 M4 M3.5 3.5 M4 M4 M4 M4 M5 M5 M5 M5 M6 M6 Screw Torque (kgf.5 10/8.5 3.5 30. W wire mm2 2 2 2 2 2 2 2 3.5 3.7 15/13 10/8.5 M3.2~4.5 13 .5 14 14 22 22 2 2 2 2 2 2 3.5kW (1 phase) B1 R T • 2.5 3.5 3.5 3.7 10/8.5 5.5 5.7/26.5 8 8 14 AWG 14 14 14 14 14 14 14 12 12 10 8 6 4 2 2 14 14 14 14 14 14 14 12 10 8 8 6 B2 U V W S(L2) T(L3) P1(+) B1 B2 N(-) U V W Ground wire mm2 3.cm) / lb-in 10/8.7/26.5 5.7 10/8.5 8 14 22 30 30 2 2 2 2 2 2 2 3. S.5kW~7.6 30. V. T wire U.6 30.5 M3.5 8 8 14 14 AWG 12 12 12 12 12 12 12 12 12 10 10 6 6 4 4 14 14 14 14 14 14 12 12 8 8 6 6 mm2 SV004iG5A-1 SV008iG5A-1 SV015iG5A-1 SV004iG5A-2 SV008iG5A-2 SV015iG5A-2 SV022iG5A-2 SV037iG5A-2 SV040iG5A-2 SV055iG5A-2 SV075iG5A-2 SV110iG5A-2 SV150iG5A-2 SV185iG5A-2 SV220iG5A-2 SV004iG5A-4 SV008iG5A-4 SV015iG5A-4 SV022iG5A-4 SV037iG5A-4 SV040iG5A-4 SV055iG5A-4 SV075iG5A-4 SV110iG5A-4 SV150iG5A-4 SV185iG5A-4 SV220iG5A-4 2 2 2 2 2 2 2 3.4kW~1.7 10/8.5 3.7 15/13 15/13 15/13 15/13 32/28 32/28 30.5/26.5 5.4kW~0.5 14 14 22 AWG 14 14 14 14 14 14 14 12 12 10 8 6 4 2 2 14 14 14 14 14 14 12 12 10 6 6 4 Terminal Screw Size M3.5/26.5 3. 4 0.5 1.4 0.0 1.6 M2.4 0. output current: 100mA Below DC 26V.4 0.6 M2.0 1.5 1.5 1.4 Specification Output voltage: 12V Max. 1A V1 I AM MO MG 24 3A 3B 3C 1) Use the recommended tightening torque when securing terminal screws.iG5A Terminal Configuration Control terminal specifications MO MG 24 P1 P2 CM P3 P4 S- S+ 3A 3B 3C P5 CM P6 P7 P8 VR V1 I AM Terminal P1~P8 CM VR Description Multi-function input T/M 1-8 Common terminal Power supply for external potentiometer Input terminal for voltage operation Input terminal for current operation Multi-function analog output terminal Multi-function terminal for open collector Ground terminal for external power supply 24V external power supply Multi-function relay output A contact Multi-function relay output B contact Common for multi-function relays Wire size (mm2) Single wire 1.0 1.5 1.4 0. output current: 100mA Below AC 250V.6 M2.4 0. ※ When you use external power supply (24V) for multi-function input terminal (P1~P8).4 0.5 1. output voltage: 11V Max.6 M2.5 1. 1A Below DC 30V.4 0. input voltage: -12V~+12V input 0~20mA input Internal resistor: 500ohm Max.5 1.100mA Max. Otherwise.6 M2.5 1.6 M2.4 0.0 1.6 M2.4 0.0 1.0 Stranded 1.6 M2.0 1.6 M2.5 1.4 0. apply voltage higher than 12V to activate.0 1. ※ Tie the control wires more than 15cm away from the control terminals.5 1.6 Torque (Nm) 0.0 1.0 1. 14 .0 1. output current: 100mA Potentiometer: 1~5kohm Max.6 M2.5 1) Screw size M2.5 1.6 M2.0 1. it interferes front cover reinstallation. Compact & Powerful Inverter iG5A Keypad Features Display RUN STOP/RESET ▲ KEY ▼ ▶ ◀ ● FWD LED 1) Term Run key STOP/RESET key Up key Down key Right key Left key Enter key Forward run Reverse run Run key Setting Run command Description STOP: Stop command during operation. RESET: Reset command when a fault occurs.6 5 2. Dimensions 36.4 RUN 2-∅4.9 23.4 95 83 70 C L 15 . Used to scroll through codes or increase parameter value Used to scroll through codes or decrease parameter value Used to jump to other parameter groups or move a cursor to the right to change the parameter value Used to jump to other parameter groups or move a cursor to the left to change the parameter value Used to set the parameter value or save the changed parameter value Lit during forward run Lit during reverse run Lit during operation Lit during parameter setting REV RUN SET 1) 4 LEDs above are set to blink when a fault occurs.1 13.1 3.2 SET RUN FWD REV 72.5 STOP RESET ENT 65. Parameter group Drive group Function group 1 Function group 2 I/O (Input/Output) group Description Basic parameters necessary for the inverter to run. Parameters necessary to make up a sequence using multi-function input/output terminal.0. 16 . Parameters such as Target frequency. Even though the preset value is 0. Accel/Decel time settable. Moving to other groups Moving to other groups using the Right (▶) key 1) Moving to other groups using the Left (◀) key 1) 1) Target frequency can be set at 0. Basic function parameters to adjust output frequency and voltage. Advanced function parameters to set parameters for such as PID Operation and second motor operation.0 (the 1st code of drive group). The changed frequency will be displayed after it is changed. it is user-settable.iG5A Moving to Other Groups Parameter groups There are 4 different parameter groups in iG5A series as shown below. ∙Preset value is 5. Pressing the Ent (●) key in this status will enter the value into memory.0 sec to 16.0 to 16. ∙The digit 5 in 5. ∙Press the Up (▲) key once. ∙0. ∙Return to the first code of Drive group. and the cursor is in the digit 0. Accel time is changed from 5. ∙ACC [Accel time] is displayed.0 is blinking will disable the setting. ∙Press the Ent (●) key once. ∙Press the Ent (●) key once.0. ∙Press the Up (▲) key again.60 is displayed. 1) ∙Press the Ent (●) key once again to return to the parameter name.Compact & Powerful Inverter iG5A When changing ACC time from 5.00” . ∙16. ∙The value is increased to 6. ∙The last code in Drive group "drC” is displayed. ∙Keep pressing the Up (▲) key until the last code appears. Then press the Up (▲) key once. ∙Use Down (▼) key for the opposite order. ∙The 2nd code in Drive group “ACC” is displayed. ∙Press the Left (◀) key once to move the cursor to the left. pressing the Left (◀) or Right (▶) key while 16.0 is active. ∙The 3rd code “dEC” in Drive group is displayed.0 is blinking. 7 8 1) Pressing the Left (◀)/Right (▶)/Up (▲)/Down (▼) key while a cursor is blinking will cancel the parameter value change.0 sec. The first 0 in 0.60 is active. Code change in Drive group 1 2 3 4 5 ∙In the 1st code in Drive group “0.0 is set. press the Up (▲) key once to go to the second code. ※ In step 7.0 ∙Press the Left (◀) key to move the cursor to the left. ∙Press the Up (▲) key once. press the Up (▲) key once.00” . 17 . ∙ACC is displayed. ∙16.0 sec 1 2 3 4 5 6 ∙In the first code “0. High (80)] Max. If P1 (FX) turns on. And after turning off. Middle. and High. frequency change: From 60Hz to 80Hz Wiring S1 P1 (Forward) S2 P2 (Reverse) 3 phase AC input P6 (Low) R S T G U V W S3 S4 P7 (Middle) S/W S5 P8 (High) P1 (Forward) P2 (Reverse) CM P6 (Low) P7 (Middle) P8 (High) CM 1. it stops according to the deceleration time. This value may change. VR V1 CM Parameter setting Step 1 2 3 4 5 6 Command Max. frequency change (FU1) Multi-step frequency (DRV) Multi-step frequency (DRV) Multi-step frequency (I/O) Forward run (P1: FX) Reverse run (P2: RX) Code F21 st1 st2 I30 I17 I18 Description Change Max. 3. S. This value may change. Set ‘Low’ step. If P2 (RX) turns on. T are connected to 3 phase AC input. V. the motor operates in forward. it stops according to the deceleration time. the motor operates in reverse. And after turning off. The default is FX. please set the frequency of multi-step among Low. 4. frequency. frequency change Operation condition Operation command: Run/Stop via FX/RX Frequency command: Multi-step operation [Low (20). 2. Please make sure that R. Set ‘Middle’ step. The default is RX. After supplying the power. Middle (30).iG5A Trial Run Multi-step operation + Run/Stop via FX/RX + Max. Set ‘High’ step. and U. Default 60Hz 10Hz 20Hz 30Hz FX RX After change 80Hz 20Hz 30Hz 80Hz FX RX 18 . W are also motor connection terminals. 4. it stops according to the deceleration time. the motor operates in forward. please set the frequency of multi-step among Low. If P2 (RX) turns on. Please make sure that R. Middle. 2.Compact & Powerful Inverter iG5A Potentiometer (Volume) + Run/Stop via FX/RX + Accel/Decel time change Operation condition Operation command: Run/Stop via FX/RX Frequency command: 0~60Hz analog input via potentiometer Accel/Decel time: Accel-10sec. And after turning off. S. 5. T are connected to 3 phase AC input. 3. Default 1 (FX/RX-1) 0 (Keypad-1) 5sec (Accel) 10sec (Decel) FX RX After change 1 (FX/RX-1) 3 (V1: 0~10V) 10sec (Accel) 20sec (Decel) FX RX 19 . 1/2W Parameter setting Step 1 2 3 4 5 Command Operation command (DRV group) Analog input (DRV group) Accel/Decel time (DRV group) Forward run (P1: FX) Reverse run (P2: RX) Code Drv Frq ACC dEC I17 I18 Description Turn on/off motor via terminal. The default is FX. And after turning off. 1/2W Motor 3 VR 2 1 V1 CM 0~60Hz 3 phase AC input R S T G U V W P1 (FX) Forward P2 (RX) Reverse CM 1. VR V1 CM Potentiometer 1~5kohm. V. Control the motor’s speed via potentiometer. Change keypad command to analog voltage command. and U. W are also motor connection terminals. and High. the motor operates in reverse. Decel-20sec Wiring Potentiometer 1~5kohm. If P1 (FX) turns on. This value may change. This value may change The default is RX. Set Accel time to 10sec in ACC Set Decel time to 20sec in dEC. After supplying the power. it stops according to the deceleration time. 76 0.77 0.5 95.4 0.5 4.5 B (mm) 4.0 4.0 A (mm) 4.75 0.5 4.5 4.5 4.4 0. SV004iG5A-4 / SV008iG5A-4 W W1 A A ∅ H D B W1 H1 mm (inches) Inverter model SV004IG5A-2 SV008IG5A-2 SV004IG5A-4 SV008IG5A-4 (kW) 0.0 (kg) 0.76 0.iG5A Dimensions SV004iG5A-2 / SV008iG5A-2.0 4.0 4.0 4.5 W (mm) 100 100 W1 (mm) 95.0 4.5 4.5 (kg) 1.5 H (mm) 128 128 H1 (mm) 120 120 D (mm) 130 130 ∅ 4.5 65.5 65.5 4.75 W (mm) 70 70 70 70 W1 (mm) 65.5 1.77 SV015iG5A-2 / SV015iG5A-4 W W1 A A1 ∅ H D B W1 H1 mm (inches) Inverter model SV015IG5A-2 SV015IG5A-4 (kW) 1.5 65.5 B (mm) 4.0 4.12 20 .5 A (mm) 4.12 1.5 H (mm) 128 128 128 128 H1 (mm) 119 119 119 119 D (mm) 130 130 130 130 ∅ 4. 84 1.66 3.5 4.5 4. SV055iG5A-4 / SV075iG5A-4 W A W ∅ A H1 H D B W B mm (inches) Inverter model SV055IG5A-2 SV075IG5A-2 SV055IG5A-4 SV075IG5A-4 (kW) 5. SV022iG5A-4 / SV037iG5A-4 / SV040iG5A-4 W C L ∅ A B H1 D H B W1 mm (inches) Inverter model SV022IG5A-2 SV037IG5A-2 SV040IG5A-2 SV022IG5A-4 SV037IG5A-4 SV040IG5A-4 (kW) 2.5 4.5 4.89 SV055iG5A-2 / SV075iG5A-2.5 120.5 120.5 7.5 4.0 W (mm) 140 140 140 140 140 140 W1 (mm) 132 132 132 132 132 132 H (mm) 128 128 128 128 128 128 H1 (mm) 120.5 W (mm) 180 180 180 180 W1 (mm) 170 170 170 170 H (mm) 220 220 220 220 H1 (mm) 210 210 210 210 D (mm) 170 170 170 170 ∅ 4.89 1.5 D (mm) 155 155 155 155 155 155 ∅ 4.5 4.84 1.5 4.7 4.5 4.66 3.5 A (mm) 5 5 5 5 B (mm) 4.5 4.5 B (mm) 4.5 4.5 120.5 (kg) 1.Compact & Powerful Inverter iG5A SV022iG5A-2 / SV037iG5A-2 / SV040iG5A-2.5 (kg) 3.5 4.5 120.5 4.5 4.5 4.5 120.89 1.2 3.66 21 .5 4.5 4.2 3.7 4.5 A (mm) 4.5 7.5 4.5 4.0 2.5 4.89 1.5 4.5 4.5 5.66 3. 0 10.00 9.0 7.0 15.3 10.0 7.0 10.0 10.0 A (mm) 10.00 9.5 208.0 B (mm) 7.0 22 .5 ∅ 10.5 189.0 8.0 10.0 A (mm) 8.00 9.00 SV185iG5A-2 / SV220iG5A-2 / SV185iG5A-4 / SV220iG5A-4 W ∅ A W1 A H1 H D B W1 B mm (inches) Inverter model SV185iG5A-2 SV220iG5A-2 SV185iG5A-4 SV220iG5A-4 (kW) 18.0 7.0 10.0 10.5 208.iG5A Dimensions SV110iG5A-2 / SV150iG5A-2 / SV110iG5A-4 / SV150iG5A-4 W A W1 ∅ A H1 H D B W1 B mm (inches) Inverter model SV110iG5A-2 SV150iG5A-2 SV110iG5A-4 SV150iG5A-4 (kW) 11.0 B (mm) 10.0 7.0 (kg) 13.0 15.0 8.0 7.5 22.0 10.0 (kg) 9.5 22.5 ∅ 7.0 W (mm) 260 260 260 260 W1 (mm) 240 240 240 240 H (mm) 410 410 410 410 H1 (mm) 392 392 392 392 D (mm) 208.3 13.0 W (mm) 235 235 235 235 W1 (mm) 219 219 219 219 H (mm) 320 320 320 320 H1 (mm) 304 304 304 304 D (mm) 189.5 189.0 7.0 10.0 10.5 189.0 10.5 208.0 18.0 11.0 8. 0 18.EBs53 Voltage [V] GMC-85 GMC-100 GMC-12 GMC-12 GMC-12 GMC-22 GMC-22 GMC-22 GMC-22 GMC-22 GMC-22 GMC-25 GMC-40 GMC-50 23 .0 15.EBs33 ABS33b.000 2.EBs53 ABS33b.600 3.400 2.EBs33 ABS33b.000 2.EBs53 ABS203b.400 2.400 2.EBs33 ABS33b.5 22.EBs53 ABS103b.200 2.5 2.EBs33 ABS53b.EBs53 Voltage [V] GMC-12 GMC-12 GMC-12 GMC-12 GMC-12 GMC-12 GMC-12 GMC-18 GMC-22 GMC-22 GMC-22 GMC-32 GMC-50 GMC-65 Model 185iG5A-2 220iG5A-2 004iG5A-4 008iG5A-4 015iG5A-4 022iG5A-4 037iG5A-4 040iG5A-4 055iG5A-4 075iG5A-4 110iG5A-4 150iG5A-4 185iG5A-4 220iG5A-4 Breaker Current [A] ABS203b.EBs33 ABS33b.000 1.800 300 150 60 50 33 20 15 10 8 5 5 1.7 5.4 0.0 18.400 2. Breakers Model 004iG5A-1 008iG5A-1 015iG5A-1 004iG5A-2 004iG5A-2 008iG5A-2 015iG5A-2 022iG5A-2 037iG5A-2 040iG5A-2 055iG5A-2 075iG5A-2 110iG5A-2 150iG5A-2 Breaker Current [A] ABS33b.EBs33 ABS33b.000 2.EBs33 ABS33b.EBs33 ABS33b.200 2.2 3.400 3.EBs33 ABS33b.EBs33 ABS33b.5 2.800 900 450 300 200 120 90 60 45 35 30 Watt [W]1) 50 100 200 300 500 700 1.4 0.EBs53 ABS103b.0 15.5 22.7 5.5 7.200 600 300 200 130 85 60 40 30 20 20 150% braking Resistor [Ω] Watt [W] 1) 100 150 300 400 600 800 1.EBs53 ABS203b.600 200V Series 400V Series 1) The wattage is based on Enable Duty (%ED) with continuous braking time 15sec.EBs33 ABS33b.EBs53 ABS103b.EBs33 ABS33b.Compact & Powerful Inverter iG5A Braking Resistors and Peripheral Devices Braking resistors Voltage Inverter 0.5 11.600 3.800 50 100 200 300 500 700 1.5 11.600 100 150 300 400 600 1.EBs53 ABS103b.EBs33 ABS33b.EBs53 ABS103b.000 1.EBs33 ABS33b.5 7.EBs33 ABS33b.000 1.0 0.400 3.75 1.EBs33 ABS53b.400 2.EBs33 ABS33b.75 1.0 100% braking Resistor [Ω] 400 200 100 60 40 30 20 15 11 9 8 1.EBs33 ABS33b.2 3. 8 A 3.iG5A Braking Resistors and Peripheral Devices Fuses & AC reactors Model 004iG5A-1 008iG5A-1 015iG5A-1 004iG5A-2 008iG5A-2 015iG5A-2 022iG5A-2 037iG5A-2 040iG5A-2 055iG5A-2 075iG5A-2 110iG5A-2 150iG5A-2 185iG5A-2 220iG5A-2 004iG5A-4 008iG5A-4 015iG5A-4 022iG5A-4 037iG5A-4 040iG5A-4 055iG5A-4 075iG5A-4 110iG5A-4 150iG5A-4 185iG5A-4 220iG5A-4 AC external fuse Current [A] 10 A 10 A 15 A 10 A 10 A 15 A 25 A 30 A 30 A 30 A 50 A 70 A 100 A 100 A 125 A 5A 10 A 10 A 10 A 20 A 20 A 20 A 30 A 35 A 45 A 60 A 70 A Voltage [V] 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V 500V AC reactor 4.20 mH. 29 A 2. 15 A 1.12 mH.49 mH. 2. 3. 1.81 mH.7 A 1. 20 A 0.20 mH. 10 A 0. 7.56 mH. 40 A 0.20 mH.74 mH. 112 A 18.56 mH. 14 A 0. 10 A 1.5 A 2. 55 A 24 . 20 A 0. 38 A 0.20 mH. 20 A 0.10 mH.54 mH.39 mH.5 A 2. 10 A 2. 50 A 0. 59 A 0.13 mH.3 A 8.18 mH. 48 A 1.81 mH. 71 A 0. 4. 75 A 0.34 mH.63 mH.45 mH.5 A 2.7 A 1.0 mH.57 mH. 91 A 0.79 mH. 96 A 0.34 mH.28 mH. 56 A 0.22 mH.15 mH.13 mH. 3.39 mH. 5. 5. 10 A 4.23 mH.88 mH.61 mH.20 mH. 30 A 0.14 mH. 30 A 0. 107 A 2. 58 A DC reactor 0.76 mH.8 A 4. 36 A 1.42 mH. It cannot be set greater than F21. during run 0.Compact & Powerful Inverter iG5A Function List Drive Group LED display Address for communication Parameter name Min/Max range commanded to output. Sets Multi-Step frequency 3 during Multi-step operation.00 A100 [Frequency command] 0 ~ 400 [Hz] During Stop: Frequency Command During Run: Output Frequency During Multi-step operation: Multi-step frequency 0. Sets Multi-Step frequency 2 during Multi-step operation.00 20. Displays DC link voltage inside the inverter. 0.00 O 5.00 O O O Analog Run/Stop via Run/Stop key on the keypad FX: Motor forward run RX: Motor reverse run FX: Run/Stop enable RX: Reverse rotation select RS485 communication Set to Field Bus communication Digital 1) Description This parameter sets the frequency that the inverter is Factory defaults Adj.00 30. This parameter displays the item selected at H73.[Max frequency]. this parameter serves as Accel/Decel time 0. Displays the number of Motor RPM. 0 1 drv A103 [Drive mode] 0~3 Terminal operation 2 3 4 0 1 2 3 Frq A104 [Frequency setting method] 0~7 4 5 6 7 8 9 St1 St2 St3 CUr rPM dCL A105 A106 A107 A108 A109 A10A [Multi-Step frequency 1] [Multi-Step frequency 2] [Multi-Step frequency 3] [Output current] [Motor RPM] [Inverter DC link voltage] 0 ~ 400 [Hz] Digital Volume Set to Field Bus communication 1) 10. vOL POr tOr Output voltage Output power Torque vOL - 1) This function can be available with iG5A Communication Option Module.0 O O 1 × Keypad setting 1 Keypad setting 2 V1 1: -10 ~ +10 [V] V1 2: 0 ~ +10 [V] Terminal I: 0 ~ 20 [mA] Terminal V1 setting 1 + Terminal I Terminal V1 setting 2+ Terminal I 0 × RS485 communication Sets Multi-Step frequency 1 during Multi-step operation. 25 .[Monitoring vOL A10B [User display select] item select]. Displays the output current to the motor.0 10. ACC dEC A101 A102 [Accel time] [Decel time] 0 ~ 6000 [Sec] During Multi-Accel/Decel operation. If H58 is 0. 2) It is indicated when H49(PID control selection) is 1.00 0 A111 feedback amount 1) Only displayed when one of the Multi-function input terminals 1-8 [I17~I24] is set to “22”. If H58 is 1. it is expressed as a [%] unit. frequency and operating status at the Factory defaults - Adj. In [%] unit. during run O 26 . Function group 1 LED display F0 Address for communication A200 Parameter name [Jump code] [Forward/ F1 A201 Reverse run disable] F2 F3 A202 A203 [Accel pattern] 0~1 [Decel pattern] 1 S-curve 0~2 Min/Max range 0 ~ 71 Description Sets the parameter code number to jump. it is expressed as a [Hz] unit. frequency. F r 0 1 drv2 A10E [Drive mode 2] 0~3 Terminal operation 2 3 4 0 1 2 [Frequency Frq2 1) Description Displays the types of faults.iG5A Function List Drive Group LED display nOn Address for communication A10C Parameter name [Fault Display] [Direction of drC A10D motor rotation select] F. In [Hz] unit. 100% means Max. It indicates a feedback amount in PID control. it is expressed as a [Hz] unit. during run - Forward Reverse Run/Stop via Run/Stop key on the keypad FX: Motor forward run RX: Motor reverse run FX: Run/Stop enable RX: Reverse rotation select RS-485 communication Set to Filed Bus Communication 3) Digital Keypad setting 1 Keypad setting 2 V1 1: -10 ~ +10 [V] V1 2: 0 ~ +10 [V] Analog Terminal I: 0 ~ 20 [mA] Terminal V1 setting 1 + Terminal I Terminal V1 setting 2+ Terminal I RS485 communication Digital Volume Set to Filed Bus Communication 3) F O 1 × 3 0~7 4 5 6 7 8 9 A10F setting method 2] 0 × PID control rEF 2) A110 standard value setting PID control Fbk 2) 0~400[Hz] or 0~100 [%] If H58 is 0.[Drive mode] is set to either 0 or 1. 3) This function can be available with iG5A Communication Option Module. 0 1 2 0 Fwd and rev run enable Forward run disable Reverse run disable Linear 0 × 0 × Factory defaults 1 Adj. If H58 is 1. frequency more than (F21). it is expressed as a [%] unit. you can’t set Max. r Min/Max range time of the fault Sets the direction of motor rotation when drv . 0. [Motor rated current]. during run This parameter sets DC brake start frequency.50 × F27 F28 F29 A21B A21C A21D 0 2 2 × × × This parameter sets the amount of torque boost applied to a motor 0 ~ 15 [%] during forward run.1 50 1. Max. This parameter sets low limit of the run frequency.00 O F21 2) A215 [Max frequency] 40 ~ 400 [Hz] frequency Caution Any frequency cannot be set above Max frequency except Base 60.0 × × × × 0 × Description Factory defaults Adj. DC voltage is applied to the motor for DC Brake start time before motor accelerates.1 ~ 10 [Hz] 0~1 0 ~ 400 [Hz] 0. This parameter sets the highest frequency the inverter can output. This parameter sets the frequency for Jog operation. This parameter sets the time taken to apply DC current to a motor while motor is at a stop.00 × × × × F26 A21A 0.[Frequency high limit] and below F23 . This parameter sets high and low limit of run frequency.00 0.1 × 10. It is set in percent of H33 . It is set in percent of Max output voltage. The inverter starts to output its voltage at this frequency. 1) Only displayed when F 4 is set to 1 (DC brake to stop). This parameter sets the amount of torque boost applied to a motor during reverse run. This parameter sets the amount of DC voltage before a motor starts to run. It cannot be set above F21 .00 × F22 F23 F24 F25 3) A216 A217 A218 A219 [Base frequency] [Start frequency] [Frequency high /low limit select] [Frequency high limit] [Frequency low limit] [Torque Boost select] [Torque boost in forward direction] [Torque boost in reverse direction] 30 ~ 400 [Hz] 0.[Motor rated current]. It cannot be set above F21 . It is set in percent of H33 . the inverter holds the output for the setting time before starting DC brake. frequency is settable up to 300Hz.50 0 60. When DC brake frequency is reached.[Start frequency]. It is frequency reference for Accel/Decel (See H70) F12 A20C 50 × F13 A20D 0 × 0.Compact & Powerful Inverter iG5A Function group 1 LED display Address for communication Parameter name [Stop mode select] [DC Brake start frequency] [DC Brake wait time] [DC Brake voltage] [DC Brake time] Min/Max range 0 F4 A204 0~3 1 2 3 F 8 1) F9 F10 F11 A208 A209 A20A A20B 0. This parameter sets high limit of the run frequency.[Max frequency]. It cannot be set above F25 . 2) If H40 is set to 3 (Sensorless vector). 27 . It is set as a percent of Max output voltage.1 ~ 60 [Hz] 0 ~ 60 [sec] 0 ~ 200 [%] 0 ~ 60 [sec] [DC Brake start voltage] [DC Brake start time] [Time for F14 A20E magnetizing a motor] F20 A214 [Jog frequency] 0 ~ 200 [%] 0 ~ 60 [sec] 0 ~ 60 [sec] 0 ~ 400 [Hz] Decelerate to stop DC brake to stop Free run to stop Power Braking stop 5. 3) Only displayed when F24 (Frequency high/low limit select) is set to 1. This parameter applies the current to a motor for the set time before motor accelerates during Sensorless vector control.00 0. It is the frequency low limit. This parameter sets the amount of DC voltage applied to a motor.[Start frequency].[Max frequency]. It cannot be set below F23 .1 ~ 400 [Hz] 0~1 The inverter outputs its rated voltage to the motor at this frequency (see motor nameplate). 0 1 Manual torque boost Auto torque boost 60. This parameter sets max current capable of flowing to the motor 50 ~ 200 [%] continuously for 1 minute. It cannot be set below F52 . 28 .[Max frequency].[Motor rated current].00 50 45. [Electronic F52 A234 thermal level for continuous] This parameter sets the amount of current to keep the motor 50 ~ 150 [%] running continuously.[Electronic thermal level for continuous]. This parameter is activated when the motor is overheated (timeinverse). The set value is the percentage of H33. It cannot be set higher than F51 .[Motor rated current]. 0 0~1 1 30 ~ 150 [%] 0 ~ 30 [Sec] Standard motor having cooling fan directly connected to the shaft A motor using a separate motor to power a cooling fan.00 75 60.[Electronic thermal level for 1 minute]. 1 2 F31 1) F32 F33 F34 F35 F36 F37 F38 F39 F40 F50 A21F A220 A221 A222 A223 A224 A225 A226 A227 A228 A232 {Linear} {Square} {User V/F} 15.[Overload warning level] flows to the motor for F55[Overload warning time]. This parameter decreases output voltage according to load status. 2) Set F50 to 1 to display this parameter. The set value is the percentage of H33 . The values of the lower-numbered parameters cannot be set above those of higher-numbered.00 25 30.00 100 100 0 0 × × × × × × × × × 0 0 0 × Description Factory defaults Adj.iG5A Function List Function group 1 LED display F30 Address for communication A21E Parameter name [V/F pattern] [User V/F frequency 1] [User V/F ] voltage 1 [User V/F frequency 2] [User V/F voltage 2] [User V/F frequency 3] [User V/F voltage 3] [User V/F frequency 4] [User V/F voltage 4] [Output voltage adjustment] [Energy-saving level] [Electronic thermal select] [Electronic F51 2) A233 thermal level for 1 minute] Min/Max range 0 0~2 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 0 ~ 400 [Hz] 0 ~ 100 [%] 40 ~ 110 [%] 0 ~ 30 [%] 0~1 This parameter adjusts the amount of output voltage. during run It is used only when V/F pattern is set to 2(User V/F) It cannot be set above F21 . This parameter issues an alarm signal when the current greater than F54. The set value is the percentage of input voltage. I55). 10 0 150 0 F55 A237 1) Set F30 to 2(User V/F) to display this parameter. F53 A235 [Motor cooling method] F54 A236 [Overload warning level] [Overload warning time] This parameter sets the amount of current to issue an alarm signal at a relay or multi-function output terminal (see I54. 0 0 100 0 150 0 The value of voltage is set in percent of H70 .[Motor rated voltage]. 00 × 0 × 0. voltage limit select F63 A23F [Save up/down frequency select] [Save up/down frequency] This parameter decides whether to save the specified frequency 0~1 during up/down operation. This parameter stops accelerating during acceleration. If ‘Save up/down frequency’ is selected at F63. it means increase or decrease of frequency according to up-down input 0 Inverter doesn’t run as a draw mode V1(0~10V) input draw run I(0~20mA) input draw run V1(-10~10V) input draw run 1 2 3 F70 A246 0~3 0 × F71 A247 [Draw rate] 0~100[%] Sets rate of draw 0.[Motor rated current]. The value is the percentage of H33. Constant or Decel run. select 1 30 ~ 200 [%] This parameter sets the amount of current to activate stall prevention function during Accel.00 0 1) It is indicated when setting bit 2 of F59 as 1 2) Set F63 to 1 to display this parameter. The set value is the percentage of the H33. This parameter sets the amount of overload current.[Motor rated current]. if you want to limit output voltage. decelerating during constant speed run and stops decelerating during deceleration. frequency Increases as many as step frequency according to edge input Available to combine 1 and 2 0. When 1 is selected. 150 × During constant run During Accel Bit 1 Bit 0 0 × 60 0 Description This parameter turns off the inverter output when motor is Factory defaults 1 180 Adj. 29 . frequency/Min.Compact & Powerful Inverter iG5A Function group 1 LED display F56 F57 Address for communication A238 A239 Parameter name [Overload trip select] [Overload trip level] [Overload trip time] Min/Max range 0~1 30 ~ 200 [%] 0 ~ 60 [Sec] overloaded. this parameter saves the frequency before the inverter stops or decelerated. the up/down frequency is saved in F64.00 × 0 × 0~1 In Stall prevention run during deceleration. during run 0 0 F58 A23A F64 2) A240 In case of choosing F65 as a 1 or 2. We can select up-down mode among three thing F65 A241 [Up-down mode select] 0~2 0 1 2 F66 A242 [Up-down step frequency] [Draw run mode select] 0~400 [Hz] Increases goal frequency as a standard of Max. This parameter turns off the inverter output when the F57[Overload trip level] of current flows to the motor for F58[Overload trip time]. During Decel Bit 2 F59 A23B [Stall prevention select] 0 0~7 1 2 3 4 5 6 7 F60 A23C [Stall prevention level] [When Stall F61 1) A23D prevention during deceleration. 00 25.iG5A Function List Function group 2 LED display H0 H1 H2 H3 H4 H5 H6 Address for communication A300 A301 A302 A303 A304 A305 A306 Parameter name [Jump code] [Fault history 1] [Fault history 2] [Fault history 3] [Fault history 4] [Fault history 5] [Reset fault history] Min/Max range 0~95 0~1 Clears the fault history saved in H 1-5.00 × Stores information on the types of faults.00 15. When run frequency is issued.1~400 [Hz] dwell frequency is applied to the motor during H8. The frequency values of the low numbered parameters cannot be set above those of the high numbered ones.[Fault history 1].00 20. Settable within the range of F21 and F23. H18 are used when F2. 0.00 35. during run O O 0 O This parameter is activated when drv is set to 1 or 2 (Run/Stop H20 A314 0~1 via Control terminal). linear zone gets smaller. linear zone gets smaller.[Start frequency]. H8 H10 H11 1) H12 H13 H14 H15 H16 H17 H18 A308 A30A [Dwell time] [Skip frequency select] A30B A30C A30D A30E A30F A310 A311 A312 [Skip frequency low limit 1] [Skip frequency high limit 1] [Skip frequency low limit 2] [Skip frequency high limit 2] [Skip frequency low limit 3] [Skip frequency high limit 3] [S-Curve accel/ decel start side] [S-Curve accel/ decel end side] [Input/output H19 A313 phase loss protection select] [Power On Start select] 0~3 1~100 [%] 1~100 [%] Set the speed reference value to form a curve at the start during accel/decel. Motor starts acceleration after AC power is applied while FX or RX terminal is ON. [Restart after H21 A315 fault reset selection] 0 ~1 This parameter is activated when drv is set to 1 or 2 (Run/Stop via Control terminal). 0~10 [sec] 0~1 Sets the time for dwell operation.[Dwell time]. the frequency. If it is set higher. Description Sets the code number to jump.00 40 40 × × × × × × × × × × 5.[Max frequency] and F23. [Dwell frequency] can be set within the range of F21.00 30. If it is set higher. the current and the Accel/Decel condition at the time of fault. Sets the frequency range to skip to prevent undesirable resonance and vibration on the structure of the machine. 0 O 0 O 1) only displayed when H10 is set to 1. 0 Disabled 1 Output phase protection 2 Input phase protection 3 Input/output phase protection 0. Factory defaults 1 nOn nOn nOn nOn nOn 0 Adj. F3 are set to 1 (S-curve) 30 .1~400 [Hz] Run frequency cannot be set within the range of H11 thru H16. The latest fault is automatically stored in the H 1. motor starts to accelerate after H7 A307 [Dwell frequency] 0. # H17. Set the speed reference value to form a curve at the end during accel/decel.0 0 10. Motor accelerates after the fault condition is reset while the FX or RX terminal is ON. H202. 2) H30 is preset based on inverter rating. 0.2 ~ 22. Restart after instant power failure Bit 2 Bit 1 Bit 0 3.0 This parameter sets the time between restart tries. H20[Power H22 1) A316 [Speed Search Select] 0 ~ 15 5 6 7 8 9 10 11 12 13 14 15 [Current level H23 A317 during Speed search] H24 H25 A318 A319 [P gain during Speed search] [I gain during speed search] 80~200 [%] 0~9999 0~9999 This parameter limits the amount of current during speed search. Operation [Power On start] 0 1 2 3 4 1. It is the Proportional gain used for Speed Search PI controller. Deactivated during active protection function (OHT.2kW ~ 22. Restart 3. H27 A31B [Auto Restart time] [Motor type select] [Number of motor poles] 0~60 [sec] 0.5 2) × 1. HWT etc.2~ 22. This function is active when [drv] is set to 1 or 2 {Run/Stop via control terminal}. Auto Restart is deactivated if the fault outnumbers the 0 ~10 restart tries.Compact & Powerful Inverter iG5A Function group 2 LED display Address for communication Parameter name Min/Max range Description This parameter is active to prevent any possible fault when the inverter outputs its voltage to the running motor.0 O 0 O 100 O On start] Bit 3 2. Even though #4 is selected along with other bits. during run O 100 200 O O H30 A31E H31 A31F This setting is displayed via rPM in drive group.0kW 4 × 7. EXT. The set value is the percentage of the H33. Inverter performs Speed search #4.0 2 ~ 12 0. LVT.[Motor rated current].). 31 . It is the Integral gain used for Speed search PI controller. This parameter sets the number of restart tries after a fault H26 A31A [Number of Auto Restart try] occurs. Normal accel after instant power failure after fault 4. Operation after fault 4. 1. Normal accel Factory defaults 0 Adj. 1) Normal acceleration has first priority. H48 A330 PWM mode select H49 A331 PID select Selects whether using PID control or not 1) H32 ~ H36 factory default values are set based on OTIS-LG motor.iG5A Function List Function group 2 LED display Address for communication Parameter name Min/Max range fs = fr H32 A320 [Rated slip frequency] 0 ~ 10 [Hz] Description × p [ rpm 120 ] 2. If the set value is higher. This is the value of the motor stator resistance. select 2 phase PWM mode. 0 0~3 1 3 0~1 0 ~ 28 [Ϊ] 0~ 300. 32 .[No Load Motor Current]. during run Where.1~ 50 [A] 50~100 [%] Enter motor rated current on the nameplate. 0 1 0~1 Normal PWM mode 2 phase PWM mode 0 × 0 × Limits output torque in sensorless mode. the inverter sound is quieter but the noise from the inverter and leakage current will become greater.0 × × × O O × 0 × 3 O H40 A328 H41 H42 H44 H45 2) H46 H47 A329 A32A A32C A32D A32E A32F If this parameter is set to 1. noise 1 ~ 15 [kHz] emission from the inverter. fs = Rated slip frequency fr = Rated frequency rpm = Motor nameplate RPM p = Number of Motor poles H33 A321 [Motor rated current] [No Load Motor Current] 0. Enter the current value detected when the motor is rotating in 26. Enter the 50% of the rated current value when it is difficult to measure H34 . it automatically measures parameters of the H42 and H44. 87 × H37 A325 [Load inertia rate] 0~2 0 1 2 Less than 10 times About 10 times More than 10 times 0 × [Carrier H39 A327 frequency select] [Control mode select] [Auto tuning] [Stator resistance (Rs)] [Leakage inductance (Lσ )] [Sensorless P gain] [Sensorless I gain] [Sensorless torque limit] This parameter affects the audible sound of the motor. 2) Set H40 to 3 (Sensorless vector control) to display this parameter.0 [mH] {Volts/frequency Control} {Slip compensation control} {Sensorless vector control} 0 1000 100 180.3 × H34 A322 rated rpm after the load connected to the motor shaft is removed.33 1) × Factory defaults Adj. 0~1 It has more noise in comparison to Normal PWM mode. 11 × H36 A324 [Motor efficiency] Enter the motor efficiency (see motor nameplate). Select one of the following according to motor inertia. and leakage current. This is leakage inductance of the stator and rotor of the motor. inverter temp. P gain for Sensorless control 0~ 32767 I gain for Sensorless control 100~220 [%] If you want to limit a inverter leakage current.5~150 [A] 0. Sets KEB action start level according to level. 0 1 Description Terminal I input (0 ~ 20 mA) Terminal V1 input (0 ~ 10 V) Factory defaults 0 300. frequency(F21) [Wake up level] [KEB drive select] [KEB action start level] [KEB action stop level] [KEB action gain] [Frequency Reference for Accel/Decel] 0~100[%] Sets a wake up level in PID control drive.9 [%] 0.1 ~ 400 [Hz] Normal PID control Process PID control 60. Sets a sleep frequency when executing a sleep function in PID [Sleep frequency] 0~400[Hz] control drive.0 0.0 130. The value is settable within the range of F21 ? [Max frequency] and F23 . 33 . You can’t set more than Max. 2) Set H49 as a 1 3): it is indicated when setting H64(KEB drive select) as a 1 (KEB does not operate when cut power after loading ting input (about 10%).0 0 125.0 0. during run × O O O H54 A336 This parameter limits the amount of the output frequency through the PID control.1 ~ 400 [Hz] 0. 0~1 0 1 0 1 2 3 0 × H60 A33C [Self-diagnostic select] 0~3 0 × H61 2) H62 H63 H64 H65 H66 H67 A33D A33E A33F A340 A341 A342 A343 [Sleep delay time] 0~2000[s] Sets a sleep delay time in PID drive. 0~1 110~140 [%] 110~145 [%] 1~20000 Sets KEB drive.0 1.0 [sec] 0 ~ 30.00 35. Sets KEB action stop level according to level.0 1000 × O O × × × × H70 A346 0 × 1) Set H49 to 1 (PID control) to display this parameter. Standard value is indicated in “rEF” of Drive group. Based on Max freq (F21) 60.1~32.50 O H57 A339 [PID standard value select] 0~4 1 2 3 4 0 × H58 A33A PID control unit select Selects a unit of the standard value or feedback amount.[Start frequency]. 0 0~1 1 Based on Delta freq.Compact & Powerful Inverter iG5A Function group 2 LED display H50 1) H51 H52 H53 Address for communication A332 A333 A334 A335 Parameter name [PID F/B select] [P gain for PID] [Integral time for PID [Differential time for PID (D gain)] [PID control mode select] [PID output H55 A337 frequency high limit] [PID output H56 A338 frequency low limit] Min/Max range 0~1 0~ 999. 0 Loader digital setting 1 Loader digital setting 2 V1 terminal setting 2: 0~10V I terminal setting: 0~20mA Setting as a RS-485 communication Frequency[Hz] Percentage[%] Self-diagnostic disabled IGBT fault/Ground fault Output phase short & open/ Ground fault Ground fault (This setting is unable when more than 11kW) 0.0 [sec] Selects PID control mode 0~1 0 1 0.00 O 0 × This parameter sets the gains for the PID controller.0 Adj. Sets KEB action gain. Selects PID standard value. 01 second. 34 . during run This parameter selects the parameter to be displayed on the keypad when the input power is first applied. this code is hidden. 0 O 0 O 1 ~ 1000 [%] Output voltage [V] Output power [kW] Torque [kgf∙m] 100 O 0 O This parameter is used to change the motor rotating speed (r/min) to mechanical speed (m/mi) and display it. 0 H77 1) A34D 0~1 1 Always ON Keeps ON when its temp is higher than inverter protection limit temp.0 × 0 ~ 30 [%] 0~1 1 Use DB resistor for the H76 set time. 0 Continuous operation when cooling fan malfunctions. Activated only during operation when its temp is below that of inverter protection limit. Settable unit: 1 second. 1. 0~2 0 1 2 H74 A34A [Gain for Motor rpm display] [DB resistor H75 A34B operating rate limit select] H76 A34C [DB resistor operating rate] [Cooling fan control] [Operating H78 A34E method select when cooling fan malfunctions] H79 A34F [S/W version] 0 ~ 10. 1) Exception: Since SV004iG5A-2/SV004iG5A-4 is Natural convection type.1 second. 0 Unlimited 1 O This parameter displays the inverter software version. Settable unit: 0.iG5A Function List Function group 2 LED display H71 Address for communication A347 Parameter name [Accel/Decel time scale] Min/Max range 0 0~2 1 2 Description Settable unit: 0.[User display H73 A349 [Monitoring item select] select]. 1 O Factory defaults Adj. 0 1 2 3 4 5 6 H72 A348 [Power on display] 0 ~ 15 7 8 9 10 11 12 13 14 15 16 17 Frequency command Accel time Decel time Drive mode Frequency mode Multi-Step frequency 1 Multi-Step frequency 2 Multi-Step frequency 3 Output current Motor rpm Inverter DC link voltage User display select (H73) Fault display Direction of motor rotation select Output current 2 Motor rpm 2 Inverter DC link voltage 2 User display select 2 0 O One of the following can be monitored via vOL . 10 O Set the percent of DB resistor operating rate to be activated during one sequence of operation.0 0~1 1 Operation stopped when cooling fan malfunctions. This parameter is used to initialize parameters back to the factory default value. 35 .00 0 5 5 Adj.1~100 [A] 0~1 0~1 Copy the parameters from inverter and save them into remote loader. 150 × 30 ~ 400 [Hz] 0~2 0 ~ 6000 [sec] Min/Max range Description Factory defaults 5. during run O O × × × × 150 O Password for H95-[Parameter lock]. 0 O 0 × 26. 2) H91. Only Function group 2 is initialized. Copy the parameters from remote loader and save them into inverter. Only Function group 1 is initialized.0 10. Only Drive group is initialized. This parameter is able to lock or unlock parameters by typing password registered in H94. Only I/O group is initialized. UL (Unlock) L (Lock) Parameter change enable Parameter change disable H95 A35F [Parameter lock] 0 ~ FFFF 0 O 1) It is indicated when choosing I17~I24 as a 12 (2nd motor select).H92 parameters are displayed when Remote option is installed. Set as Hexa value.0 60. 0 H93 A35D [Parameter initialize] 0~5 1 2 3 4 5 H94 A35E [Password register] 0 ~ FFFF All parameter groups are initialized to factory default value.Compact & Powerful Inverter iG5A Function group 2 LED display H81 1) H82 H83 H84 H85 H86 H87 Address for communication A351 A352 A353 A354 A355 A356 A347 Parameter name [2nd motor Accel time] [2nd motor Decel time] [2nd motor base frequency] [2nd motor V/F pattern] [2nd motor forward torque boost] [2nd motor reverse torque boost] [2nd motor stall prevention level] [2nd motor H88 A358 Electronic thermal level for 1 min] [2nd motor H89 A359 Electronic thermal level for continuous] H90 H91 2) H92 A35A A35B A35C [2nd motor rated current] [Parameter read] [Parameter write] 0.3 0 0 × × × 50~150 [%] 100 O 30~150 [%] 50~200 [%] 0 ~ 15 [%] This parameter actives when the selected terminal is ON after I17-I24 is set to 12 {2nd motor select}. 00 60.00 10 60.00 20.Low Multi-Step freq . Sets the maximum voltage of the NV input.High 5 6 Multi-Step freq . * Each multi-function input terminal must be set differently.00 10 4. 36 .00 0. Sets the inverter output minimum frequency at minimum voltage of the V1 input.0 60. * See °∞Chapter 14 Troubleshooting and maintenance°± for External trip A/B contact. Sets the minimum voltage of the NV (-10V~0V) input.00 0. 0 1 2 0 Disabled activated below half of set value. Sets the minimum voltage of the V1 input. Sets the input section’s internal filter constant for I input.iG5A Function List Input/output group LED display I0 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15 Address for communication A400 A402 A403 A404 A405 A406 A407 A408 A409 A40A A40B A40C A40D A40E A40F Parameter name [Jump code] [NV input Min voltage] [Frequency corresponding to I 2] [NV input Max voltage] [Frequency corresponding to I 4] for V1 input] [V1 input Min voltage] [Frequency corresponding to I 7] [V1 input Max voltage] [Frequency corresponding to I 9] [Filter time constant for I input] [I input Min current] [Frequency corresponding to I 12] [I input Max current] [Frequency corresponding to I 14] [Criteria for I16 A410 Analog Input Signal loss] [Multi-function I17 A411 input terminal P1 define] [Multi-function I18 A412 input terminal P2 define] [Multi-function I19 A413 input terminal P3 define] [Multi-function I20 A414 input terminal P4 define] 7 Multi-Step freq . activated below set value. Sets the minimum current of I input. during run O O O O O O O O O O O O O O O [Filter time constant 0 ~ 9999 Adjusts the responsiveness of V1 input (0 ~ +10V). Sets the maximum voltage of the V1 input.00 10.Mid 3 O 3 0 ~ 27 4 Jog operation command 2 O Reset when a fault occurs {RST} 1 2 Reverse run command Emergency Stop Trip 1 O 0~2 0 ~ 9999 0 ~ 20 [mA] 0 ~ 400 [Hz] 0 ~ 20 [mA] 0 ~ 400 [Hz] Sets the inverter output maximum frequency at maximum current of I input. Sets the inverter output minimum frequency at minimum voltage of the NV input. Forward run command 0 O 0 O Sets the inverter output minimum frequency at minimum current of I input. Description Sets the code number to jump. Factory defaults 1 0. Min/Max range 0 ~ 87 0 ~ -10 [V] 0 ~ 400 [Hz] 0 ~ -10 [V] 0 ~ 400 [Hz] Sets the inverter output maximum frequency at maximum voltage of the NV input.00 Adj.00 10 0 0. Sets the Maximum current of I input. 0 ~ 10 [V] 0 ~ 400 [Hz] 0 ~ 10 [V] 0 ~ 400 [Hz] Sets the inverter output maximum frequency at maximum voltage of the V1 input. 0 O O O 30.00 15.Compact & Powerful Inverter iG5A Input/output group LED display I21 Address for communication A415 Parameter name [Multi-function input terminal P5 define] [Multi-function I22 A416 input terminal P6 define] [Multi-function I23 A417 input terminal P7 define] 13 14 15 0 ~ 27 16 17 18 [Multi-function I24 A418 input terminal P8 define] 19 20 21 22 23 24 25 26 27 I25 I26 A419 A41A [Input terminal status display] [Output terminal status display] [Filtering time I27 A41B constant for Multi-function Input terminal] I30 I31 I32 I33 I34 I35 I36 A41E A41F A420 A421 A422 A423 A424 [Multi-Step frequency 4] [Multi-Step frequency 5] [Multi-Step frequency 6] [Multi-Step frequency 7] [Multi-Accel time 1] [Multi-Decel time 1] [Multi-Accel time 2] 0~ 6000 [sec] 0 ~ 400 [Hz] It cannot be set greater than F21 . during run 37 . 4 O BIT7 P8 -Reserved-ReservedUp-down 3-wire operation External trip: A Contact (EtA) External trip: B Contact (EtB) Self-diagnostic function Change from PID operation to V/F operation 2nd Source Analog Hold Accel/Decel Disable Up/Down Save Freq.0 4.00 O O 1 ~ 15 If the value is set higher.High 5 O Min/Max range 8 Description Multi Accel/Decel . the responsiveness of the Input terminal is getting slower. Initialization JOG-FX JOG-RX BIT6 P7 BIT1 3AC BIT5 P6 BIT4 P5 BIT3 P4 BIT2 P3 MO BIT1 P2 BIT0 BIT0 P1 0 0 O O 7 O Frequency increase (UP) command Frequency decrease command (DOWN) 11 12 DC brake during stop 2nd motor select 6 O 9 10 Multi Accel/Decel .Mid Multi Accel/Decel .[Max frequency].00 3.00 25.0 3. 20.Low 4 O Factory defaults Adj. 0 9.iG5A Function List Input/output group LED display I37 I38 I39 I40 I41 I42 I43 I44 I45 I46 I47 Address for communication A425 A426 A427 A428 A429 A42A A42B A42C A42D A42E A42F Parameter name [Multi-Decel time 2] [Multi-Accel time 3] [Multi-Decel time 3] [Multi-Accel time 4] [Multi-Decel time 4] [Multi-Accel time 5] [Multi-Decel time 5] [Multi-Accel time 6] [Multi-Decel time 6] [Multi-Accel time 7] [Multi-Decel time 7] Output item I50 A432 [Analog output item select] 0~3 0 1 2 3 I51 I52 A433 A434 [Analog output level adjustment] [Frequency detection level] [Frequency I53 A435 detection bandwidth] [Multi-function I54 A436 output terminal select] 0 1 2 3 0 ~ 19 I55 A437 [Multi-function relay select] 4 5 6 7 8 9 FDT-1 FDT-2 FDT-3 FDT-4 FDT-5 Overload (OLt) Inverter Overload (IOLt) Motor stall (STALL) Over voltage trip (Ovt) Low voltage trip (Lvt) 17 O 12 0 ~ 400 [Hz] Used when I54 or I55 is set to 0-4.0 Adj. Cannot be set higher than F21. 10.0 8.0 7.0 5.0 9.0 7. during run Based on 10V.00 O 10~200 [%] Output freq.00 O O 400V 0 O 0~ 6000 [sec] Min/Max range Description Factory defaults 4.0 8.0 6. Output current Output voltage Inverter DC link voltage Output to 10[V] 200V Max frequency 150 % AC 282V DC 400V AC 564V DC 800V 100 30.0 6.0 5. 38 . during run Set for RS485 communication Select the Baud rate of the RS485. Free Run stop (Output cut-off) Decel to stop 0 O 39 . 0 1200 [bps] 2400 [bps] 4800 [bps] 9600 [bps] 19200 [bps] 1 2 3 4 I61 A43D [Baud rate] 0~4 3 O It is used when freq command is given via V1 /I terminal or [Drive mode I62 A43E select after loss of frequency command] 0~2 RS485.Compact & Powerful Inverter iG5A Input/output group LED display Address for communication Parameter name Min/Max range 10 11 12 13 I55 A437 [Multi-function relay select] 0 ~ 19 14 15 16 17 18 19 Command loss During Run During Stop During constant run During speed searching Wait time for run signal input Multi-function relay select Warning for cooling fan trip Brake signal select When setting the auto restart try] Bit 2 0 I56 A438 [Fault relay output] 0~7 1 2 3 4 5 6 7 Multi-function relay [Output terminal I57 A439 select when communication error occurs] 0~3 0 1 2 3 Set communication protocol.[Number of other than low 17 O Description Inverter Overheat (OHt) Factory defaults Adj. 0 1 2 Continuous operation at the frequency before its command is lost. I59 I60 A43B A43C [Communication protocol select] [Inverter number] 1 ~ 250 0 ~1 0 1 Modbus RTU LS BUS 1 O 0 × Bit 1 Multi-function output terminal Bit 0 0 O When the trip voltage trip occurs Bit 1 Bit 0 2 O When the low voltage trip occurs H26 . 0 O Factory defaults Adj.1 ~ 120 frequency command or not. the communication format can be set. 40 . Stop Bit: 1 5 6 7 8 O 9 10 11 12 5 6 7 8 O 5 6 7 8 50. Parity: None. Frame communication time When the protocol is set.iG5A Function List Input/output group LED display Address for communication Parameter name [Wait time after I63 A43F loss of frequency command] I64 A440 [Communication time setting] Min/Max range Description This is the time inverter determines whether there is the input 0. Stop Bit: 2 Parity: Even. during run 1) 1) It is indicated when choosing I54~I55 as a 19 (Brake signal). Stop Bit: 1 Parity: None. It is set according to H33’s (motor rated current) size 0~42239 The user can register up to 8 discontinuous addresses and write them all with one Write command 0~42239 The user can register up to 8 discontinuous addresses and read them all with one Read command. I65 A441 [Parity/stop bit setting] 0 0~3 1 2 3 I66 I67 I68 I69 I70 I71 I72 I73 I74 I75 I76 I77 I78 I79 I80 I81 182 1) A442 A443 A444 A445 A446 A447 A448 A449 A44A A44B A44C A44D A44E A44F A450 A451 A452 [Read address register 1] [Read address register 2] [Read address register 3] [Read address register 4] [Read address register 5] [Read address register 6] [Read address register 7] [Read address register 8] [Write address register 1] [Write address register 2] [Write address register 3] [Write address register 4] [Write address register 5] [Write address register 6] [Write address register 7] [Write address register 8] [Brake open current] 0~180 [%] Sets current level to open the brake. If there is no frequency command [sec] 2 ~ 100 [ms] input during this time. inverter starts operation via the mode selected at I62. Stop Bit: 1 Parity: Odd.0 O O O 5 O 1. 00 Adj.00 1.Compact & Powerful Inverter iG5A Input/output group LED display 183 184 185 186 187 Address for communication A453 A454 A455 ` A456 A457 Parameter name [Brake open delay time] [Brake open FX frequency] [Brake open RX frequency] [Brake close delay time] [Brake close frequency Min/Max range 0~10 [s] 0~400 [Hz] 0~400 [Hz] 0~19 [s] 0~400 [Hz] Description Sets Brake open dely time.00 1. during run × × × × × 41 .00 1.00 2. Sets FX frequency to open the brake Sets RX frequency to open the brake Sets delay time to close the brake Sets frequency to close the brake Factory defaults 1. output phase short. The inverter turns off its output when the one or more of the output (U. When multi-function input terminal (I20-I24) is set to 19 {External fault signal input B: (Normal Close Contact)}. The inverter cannot protect the motor when driving a motor having more than 4 poles or multi motors.. When inverter operation is set via analog input (0-10V or 0-20mA input) or option (RS-485) and no signal is applied. Displayed when the inverter and the remote keypad do not communicate with each other. Displayed when IGBT damage. the inverter turns off the output. Displayed when the inverter cannot communicate with the keypad. W) phase is open. It does not stop inverter operation. The inverter turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value of the inverter. If the motor is overloaded. the inverter turns off the output. Used for the emergency stop of the inverter. T is open or the electrolytic capacitor needs to be replaced. Displayed after the inverter resets the keypad when a keypad error occurs and this . Caution: The inverter starts to regular operation when turning off the EST terminal while FX or RX terminal is ON. V. The inverter instantly turns off the output when the EST terminal is turned on. The internal electronic thermal of the inverter determines the overheating of the motor. the inverter turns off the output..iG5A Protective Functions Keypad display Protective functions Overcurrent Ground fault current Inverter Overload Overload trip Heat sink overheat Output Phase loss Over voltage Low voltage Electronic Thermal Input phase loss Self-diagnostic malfunction Parameter save error Inverter hardware fault Communication Error Remote keypad communication error Keypad error Cooling fan fault Instant cut off External fault A contact input External fault B contact input Operating method when the frequency command is lost Descriptions The inverter turns off its output when the output current of the inverter flows more than 200% of the inverter rated current. Inverter output is blocked when one of R. The inverter detects the output current to check the phase loss of the output. The inverter turns off its output when the output current of the inverter flows more than the rated level (150% for 1 minute). The inverter turns off its output if the output current of the inverter flows at 150% of the inverter rated current for more than the current limit time (1min). This fault can also occur due to a surge voltage generated at the power supply system. S. Displayed when user-setting parameters fails to be entered into memory. The inverter turns off its output if the heat sink overheats due to a damaged cooling fan or an alien substance in the cooling fan by detecting the temperature of the heat sink. 42 . output phase ground fault or output phase open occurs. Displayed when an error occurs in the control circuitry of the inverter. The inverter turns off its output if the DC voltage of the main circuit increases higher than 400V when the motor decelerates. The inverter turns off its output if the DC voltage is below 180V because insufficient torque or overheating of the motor can occur when the input voltage of the inverter drops. When multi-function input terminal (I20-I24) is set to 19 {External fault signal input A: (Normal Open Contact)}. operation is done according to the method set in I62 (Operating method when the frequency reference is lost).. Displayed when a fault condition occurs in the inverter cooling fan. Communication error between inverter keypad and remote keypad. → Install a cooling fan with a separate power supply. → Replace the inverter with appropriate capacity. → Make connection of magnetic switch at output of the inverter securely. Line voltage is low. → Check the wiring of the output terminal. External fault A contact input External fault B contact input Operating method when the frequency command is lost Remote keypad communication error Low voltage Electronic thermal The terminal set to “18 (External fault. → Check whether line voltage exceeds its rating. Load is greater than the inverter rating. Adjust the line capacity corresponding to the load. → Increase the Decel time. Heat sink overheat Output Phase loss Faulty output wiring. Overload trip → Upgrade the capacity of motor and inverter or reduce the load weight. → Reduce load weight and operating duty. → Use Dynamic Brake Unit. → Select correct inverter capacity. → Reduce torque boost scale. → Change a magnetic switch. Output short circuit or ground fault has occurred.HWT: Hardware fault . Faulty contact of magnetic switch at output. An old cooling fan is not replaced with a new one. → Check the ventilating slot and remove the clogged substances. → Change inverter with higher capacity. → Check output wiring. → Increase the Accel/Decel time. No frequency command is applied to V1 and I. → Replace the cooling fan. Inverter output is issued when the motor is free running.EEP: Parameter save error . Motor has overheated. motor with high starting current connected to the commercial line). → Adjust ETH level to an appropriate level. The insulation of the motor is damaged due to heat. ETH level is set too low.Err: Communication Error . Ambient temperature is too high. 43 . An alien substance is clogged in a ventilating slot. Cooling fan fault Inverter has been in use without changing a cooling fan. Faulty magnetic switch at the input side of the inverter. → Resume operation after stopping the motor or use H22 (Speed search).A)” or “19 (External fault-B)” in I20-I24 in I/O group is ON. Cooling system has faults. Ground fault current Inverter overload Load is greater than the inverter rating. → Check whether line voltage is below its rating. Load larger than line capacity is connected to line (ex: welding machine. operation must be started after the cause is removed to avoid damage to IGBT inside the inverter. Line voltage is too high. Mechanical brake of the motor is operating too fast. Load is greater than inverter rating. → Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input. → Check for connection of communication line and connector. . Ground fault has occurred at the output wiring of the inverter. Over voltage Decel time is too short compared to the GD2 of the load. → Replace the motor.Compact & Powerful Inverter iG5A Fault Remedy Keypad display Cause Remedy Caution: When an overcurrent fault occurs. Regenerative load is at the inverter output. → Check output wiring. → Check for alien substances clogged in the heat sink. → Replace the old cooling fan with a new one. Inverter has been operated at low speed for too long. Inverter capacity is incorrectly selected. → Check the incoming AC line. → Check the mechanical brake.COM: Keypad error → Check the wiring of V1 and I and frequency reference level. → Contact your LSIS sales distributor. Torque boost scale is set too large. → Keep ambient temperature under 50� C. Overcurrent Accel/Decel time is too short compared to the GD2 of the load. No1 Fuxing Road Chengdu.R.. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis. 214028. Dubai. Hochiminh City.15.com.biz Address: No. Higashi-Kan..R. Korea � � � � � � � Global Network �LS Industrial Systems (Middle East) FZE � � Dubai. United Arab Emirates Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected] Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected] �LS Industrial Systems (Wuxi) Co. No. please read user's manual thoroughly before operating. China Address: B-Tower 17FL. Japan Address: 16FL.Ltd.biz �LS Industrial Systems Shanghai Office � � Shanghai. China Address: 102-A . P.com. www.biz +82-2-2034-4645 / sungkyup@lsis. repair.com. Minato-ku Tokyo 107-8470. DongCheng-District. Shandong Road Qingdao 26600.R.cn 2010.E. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis. West Yan'an Road Shanghai 200050.Guangzhou. ⓒ 2005. 2-chome. or adjustment. � � Wuxi.7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis. P.biz �LS Industrial Systems Chengdu Office � � Chengdu. � Contact the nearest authorized service facility for examination. Jebel Ali Freezone P.� For your safety.36.14F.biz � HEAD OFFICE LS Tower 1026-6.com. Ltd.com.com �LS Industrial Systems Tokyo Office � � Tokyo.. China Address: Room 1403. Liaohexi 3-Road.cn Specifications in this catalog are subject to change without notice due to continuous product development and improvement. P.03 Printed in Korea STAFF . Gyeonggi-do 431-848. China Address: Room E-G. Ltd. National High & New Tech Industrial Development Area. China Tel: 86-10-5825-6025.O. No. Box 114216.biz +82-2-2034-4913 / jinhkang@lsis. P.Dong Anh .5 LS Industrial Systems Co.05/(11)2010.726.9. Vietnam Address: Nguyen Khe . No. Akasaka. 03 Starvert iG5A(E)2005. China Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis. Dalian 116600. huanminhanjun internationnal Building.biz +82-2-2034-4377 / younsupl@lsis. BeiSanHuanDong-Lu. P. � � Hochiminh . Address: LOB 19 JAFZA VIEW TOWER Room 205..China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis. Hogye-dong.lsis.cn �LS Industrial Systems Guangzhou Office � � Guangzhou.Beijing Global Trade Center B/D. Economic and Technical Development zone.. Ltd.R. China Europe Middle East South West Asia South East Asia CIS America +82-2-2034-4376 / ywsohn@lsis. Vietnam Address: 41 Nguyen Thi Minh Khai Str. China Address: 7B40. 12th Floor Huamin Empire Plaza. � � Hanoi.Haixin Guangchang Shenye Building B.Ha Noi . U.cn �LS Industrial Systems Beijing Office � � Beijing.R. � Please contact qualified service technician when you need maintenance. Jiangsu. Yoco Bldg 4th Floor. China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis. Dongan-gu. Anyang-si. All rights reserved. Ltd.biz �Dalian LS Industrial Systems Co.2 Zhongshan Liu Road.biz +82-2-2034-4707 / [email protected]. Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis. China Address: Room 1701 17Floor.com �LS-VINA Industrial Systems Co.R. � � Dalian. Vietnam Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected] �LS-VINA Industrial Systems Co. Wuxi. Do not disassemble or repair by yourself! Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned. 610041. P. Akasaka Twin Tower 17-22.New Poly Tower.biz +82-2-2034-4901 / [email protected]. Beijing 100013. �LS Industrial Systems Qingdao Office � � Qingdao.