Home
Login
Register
Search
Home
Short Circuit Calculation
Short Circuit Calculation
March 27, 2018 | Author: Maulana Adi | Category:
Electrical Conductor
,
Electrical Components
,
Force
,
Building Engineering
,
Physics
DOWNLOAD
Share
Report this link
Comments
Description
Short-circuit Calculations© ABB Ltd – 03-03 Talk will cover Short circuit calculation Demo of DOCWin © ABB SACE – BM - 2 Three phase 66/22kV Primary 75 MVA Transformer Secondary Tertiary 66kV 22kV IF = V/ 3 (Zt + Zs) = 1.1035 p.u IF = 22kV/ 1.1035 = 11.5 kA 3 Zs can be neglected, % impedance voltage between pri & sec windings = 17.1% (given) © ABB SACE – BM - 3 Zt = Usc x E2 100 x (MVA) = 17.1 x (22)2 100 x (75) Three phase 66/22kV Primary 75 MVA Transformer Secondary Tertiary 66kV 22kV Normally PG operates the transformers in parallel.5kA or nearly 25kA This gives upstream power short circuit : © ABB SACE – BM .4 3 x 22kV x 25 kA = 1000 MVA . total fault current = 2 x 11. 5 Tabel mV/A/m of cable [R + JX] : Rc = R mΩ/m x Lm / Xc = X mΩ/m x Lm / 3 3 IF = ? . Upstream Network : Psc : Upstream power short circuit in MVA : 1000 MVA Zup = U 2 / Psc = 400 2 / 1000 = 0.38 m/m Xc = 0. Transformer : ZT = Usc x U2 / Sn x 10-3 RT = Wc x XT = U2 / Sn x 10-3 Usc :short circuit voltage (%) Wc : Copper Loss (W) 4 x 1c 120mm2 XLPE flat touching on cable tray length 50m 120mm2 cable data Rc = 0.24 m/m A (ZT2 – RT2) 400V B 3. Cable : © ABB SACE – BM .16 mΩ 22kV/400V 1MVA 5% 22kV 1000MVA 2.Consultant’s method 1. 16 + 8) = 28.24 m/m A 400V B 400 © ABB SACE – BM .98 mΩ 400 Fault current at A = 3 x (0.16 + 8 + 12.38 x 50 / V3 = 10.38 m/m Xc = 0.6 Fault current at B = 3 x (0.16 mΩ Impendance of transformer (ZT) = 8 mΩ 22kV/400V 1MVA 5% 22kV 1000MVA Impendance of cable : Rc = 0.94 2) = 12.98) = 10.3 kA 4 x 1c 120mm2 XLPE flat touching on cable tray length 50m 120mm2 cable data Rc = 0.Consultant’s method Impendance upstream network (Zup) = 0.24 x 50 / V3 = 6.98 2 + 6.94 mΩ Zc = (10.94 kA IF = ? .98 mΩ Xc = 0. 24 m/m 400V 120mm2 A Hence the difference in total impedance up to the point of fault is negligible.7 . 22kV 1000MVA 22kV/400V 1MVA 5% 4 x 1c XLPE flat touching on cable tray length 50m 120mm2 cable data Rc = 0. IF = ? B © ABB SACE – BM .Consultant’s method To show why fault level at HV side can be ignored.001 This value is insignificant compared to the transformer and cable impedance.0 MVA 1000 MVA = 0.38 m/m Xc = 0. Per unit impedance of 22kV source = 1. 4 kA IF = ? .9 400V B © ABB SACE – BM . therefore the trend is to calculate ‘worse case’.9 = 28.24 m/m 120mm2 22kV 1000MVA 22kV/400V 1MVA 5% A Isc = fault current / 0.US Consultant’s method Sometimes Consultant is very thorough.3kA / 0.38 m/m Xc = 0. Because UL standard 1561 allows the marked impedance of a transformer to vary + 10%.8 = 31. 4 x 1c XLPE flat touching on cable tray length 50m 120mm2 cable data Rc = 0. 9 V Ib = 600.2 A L = 50 m 400V -QF3 S7S 1600 PR211-I R1600 B © ABB SACE – BM .90 Ir = 600.18 % .Use ABB DOCwin software 22kV 1000MVA U -U1 Vref = 22000 V LLL / IT Plf = 374 kW Qlf = 181 kvar 22kV/400V 1MVA 5% -TM1 Vr2 = 400 V Sn = 1000 kVA 2nd: LLLN / TN-S -B3 Df = 1.00 V = 391.2 kA I> -QF5 4 x 1c XLPE flat touching on cable tray length 50m 120mm2 cable data Rc = 0.9 -QF4 S7S 1600 PR211-I R1600 IF = ? L -L1 Sr = 415.0 A Cosphi = 0.3 V Ib = 600.38 m/m Xc = 0.91 I"k LLL = 23.0 A Cosphi = 0.00 V = 394.0 A Iz = 669.69 kVA Cosphi = 0.91 I"k LLL = 28.63 % Ib = 600.24 m/m -B1 Df = 1.9 kA 120mm2 A -WC1 12x(1x120)+4x(1x70)+1G70 dV = 0.0 A UF = 100% dV = 2. 434.2. © ABB SACE – BM .the source is impedant (set).10 in all cases.Short-circuit current General rules in accordance with the rules in articles IEC 364-434.3 and IEC 364533. the thermal and electrodynamic withstand of the ducts and switchgear. the maximum prospective short-circuit current at the origin of the circuit and the minimum prospective short-circuit current at the end of the circuit must be determined for each circuit.2. . protection must be compatible with the cable heat stress ∫ I2dt ≤ K2 S2 . the maximum prospective short-circuit current determines : the breaking capacity (Icu) of the circuit-breakers Icu ≥ than prospective Icc.protection of persons depends on it (TN-IT). the minimum prospective short-circuit determines : choice of trip units (curve) and fuse when : . the making capacity of the devices.cables are very long. . c. k is a factor that takes into account the resistivity. temperature factor and heat capacity of the conductor material. and the appropriate initial and final temperatures..s. S cross-sectional area in mm2 I effective short-circuit current in A expressed.S2 t= k2 S2 I2 t duration in s. value.m. as the r.11 . or max.Short-circuit current General rules for whatever type of short-circuit current (min.). the protection device must clear the Isc within a time t < 5sec that is compatible with the thermal stress that can be withstood by the protected cable ∫ I2dt ≤ k2. for a. © ABB SACE – BM . for calculation of the effects of shortcircuit current limiting initial temperature °C 70 60 85 90 80 70 105 70 60 85 90 80 limiting final temperature °C 160/140 200 220 250 160 160 250 160/140 200 220 250 160 conductor material copper insulation material pve 60°C rubber 85°C rubber 90°C thermosetting impregnated paper mineral .Short-circuit current General rules values of k for common materials. the lower value relates to 2 cables having conductors with a cross-sectional area greater than 300mm .12 note : where two values of limiting final temperature and k are given.sleeves and seals pvc 60°C rubber 85°C rubber 90°C thermosetting impregnated paper k 115/103 141 134 143 108 115 135 76/68 93 89 94 71 Aluminum © ABB SACE – BM .conductor . installation method.current ratings . • environment : ambient temperature. cross-section. number of contiguous circuits.voltage drops © ABB SACE – BM .duty factor . . breaking capacity inst. trip setting Isc at head of final switchboards breaking capacity inst. trip setting Isc of main LV switchboard outgoers breaking capacity inst.power factor.foreseeable expansion factor conductor characteristics • busbars : length. trip setting Isc at head of secondary switchboards breaking capacity inst.Short-circuit current Short-circuit calculation procedure upstream Scc HV/LV transformer rating Usc (%) Isc at transformer terminals . • cables : type of insulation single-core or multicore. . thickness.feeder . trip setting load rating Isc at end of final outgoers final distribution circuit breaker secondary distribution circuit breaker main circuit breaker main LV switchboard distribution circuit breaker .13 .coincidence factor. width. length. 14 .Short-circuit current Definition a short-circuit current is an overcurrent resulting from a fault of negligible impedance between points at different potentials in normal service. Zt = R2 + X2 Icc3 = U = Z U R2 + X2 A Zt Zt mΩ) U ZI U ZI B © ABB SACE – BM . Zsc = 0.86. Isc3 .Short-circuit current The various short-circuits currents three-phase fault ZL ZSC ~ ZL ZL V I sc3 = U/ 3 Zsc phase-to-phase fault ZL ZSC ~ © ABB SACE – BM .15 U ZSC I sc2 = ZL U 2. 5. Isc3 phase-to-earth fault ZL ZSC ~ © ABB SACE – BM .16 V Z(0) I sc(0) = U/ 3 Zsc + Z(0) Z(0) .Short-circuit current The various short-circuits currents phase-to-neutral fault ZL ZSC ZLn ~ V ZLn I sc1 = U/ 3 Zsc + ZLn = 0. to calculate the Isc at the end of a line . U + Zc .17 the conventional method : which can be used when the impedance or the Isc in the installation upstream of the given circuit are not known. Zk k k the composition method : which may be used when the characteristics of the power supply are not known U IscB = IscA . IscA © ABB SACE – BM .Short-circuit current How to calculate a balanced short-circuit the “impedance method” : used to calculate fault currents at any point in an installation with a high degree of accuracy Un Un Isck = = 3 R2 + X2 3 . Short-circuit current The case of several transformers in parallel feeding a busbar what happens with the breaking capacity of each CB D1 D2 D1 D2 D3 D4 D4 © ABB SACE – BM .20 . 21 n value of Icc3 at the terminals of a set Icc3 = (1) Sn V3 Un . X’d (1) = transient reactance expressed as (30%) The value of the transient reactance should be check to genset manufacture . limited thermal withstand.Short-circuit current The case of a generator n generator set characteristics : low short-circuit current depending on its transient reactance (2 to 5 ln). n protection characteristics : long time protection acting quickly (<15s) for an overload of 1. low short time protection (< 2ln). G 250 KVA 400 x’d = 30% load shedding non-priority priority © ABB SACE – BM .5 ln. 1 X’d . x’d if no info = 30 % n zero sequence reactance : xo in % Xo = Un Sn 2 x.xo if no info = 6 % © ABB SACE – BM .Short-circuit current The case of a generator n subtransient reactance : x”d in % X’’d = Un Sn 2 x.22 Note : to be checked to the manufacturer .x’’d if no info = 20 % n transient reactance : x’d in % X’d = Un Sn 2 x. cable heating is reduced hence longer cable life. measuring equipment situated near an electric circuit less affected the cascading technique offers substantial savings on equipment. thus electric contacts less likely to be deformed or broken.Short-circuit current Limitation : why n Installation of current limiting circuit breakers offers several advantages : current limiting circuit breakers considerably reduce the undesirable effects of short-circuit currents in an installation.24 . enclosures and design by using lower rated devices downstream. electrodynamic forces reduced. © ABB SACE – BM . 25 .Short-circuit current Principle of limitation i u U arc prospective current limited current arc voltage t network voltage © ABB SACE – BM . = 55 kA peak Limited value = 25 kA peak prospective Isc limited Isc peak 9x I2 t 106 total energy let through during half cycle without limitation limited Isc © ABB SACE – BM .Short-circuit current What it is limitation : tables to use for applications circuit breaker limitation capability : the limitation capability of a circuit breaker is that characteristic whereby only a current less than the prospective fault current is allowed to flow under short-circuit conditions.26 t 6 x 106 energy let through during half cycle with limitation 0 30 kA rms . kA peak 55 without limitation 25 with limitation 0 Isc prospective Isc peak 30 kA rms example : system prospective = 30 kA rms. no discrimination discrimination CB1 CB1 CB2 CB2 © ABB SACE – BM . is the coordination of automatic protective devices in such a manner that a fault appearing at a given point in a network is cleared by the protective device installed immediately upstream of the fault.27 CB1 and CB2 open only CB2 open why is discrimination useful ? Discrimination contributes to continuity of service. . a necessity in many industrial.Short-circuit current Definition : discrimination discrimination (selectivity). and by that device alone. commercial or institutional installations. Short-circuit current Current discrimination by comparing the characteristic operating curves for : limitation of the downstream circuit breaker (D1) : ∫i2 dt no tripping energy of the upstream circuit breaker (D2) ∫i2 dt tripping no-tripping D2 © ABB SACE – BM .28 D1 . Short-circuit current Full or restricted current discrimination case of full discrimination 2 • i dt case of restricted discrimination i dt • 2 D2 D2 D1 D1 I D2 Is I © ABB SACE – BM .29 Icc D1 . Short-circuit current Improvement (continued) n zone selective interlocking D1 logic relay I D2 logic relay © ABB SACE – BM .30 D3 logic relay III . 05 tD • 10ms © ABB SACE – BM .31 I .g.1 =2 0.Short-circuit current Discrimination between HV fuses and LV circuit breaker HV circuitbreaker imag D +20% 10% "current " safety IF ≥ 1.35 ICB HV/LV transformer D ± 20% I F ± 10% Icc > minimum breaking current of HV circuitbreakers Icc t tF "time" safety tF tCB ≥ 2 e. 0. the principle of cascading has been recognised by the IEC 364-434. © ABB SACE – BM . They thus allow circuit breakers of lower breaking capacity than the prospective short-circuit current at their point of installation to operate under the stress conditions of normal breaking.Short-circuit current Definition : cascading cascading is the use of the current limiting capacity of circuit breakers to permit installation of lower rated and therefore lower cost downstream circuit breakers.32 . comments : the upstream CB acts as a barrier against short-circuit currents.3 standard cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer. 33 .© ABB SACE – BM .
Report "Short Circuit Calculation"
×
Please fill this form, we will try to respond as soon as possible.
Your name
Email
Reason
-Select Reason-
Pornographic
Defamatory
Illegal/Unlawful
Spam
Other Terms Of Service Violation
File a copyright complaint
Description
Copyright © 2024 DOKUMEN.SITE Inc.