PCVVN1520aprvWarning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. S SERIES For residential and commercial use Specifications, designs and other content appearing in this brochure are current as of March 2015 but subject to change without notice. c All rights reserved Y.K. Heat Pump 50 Hz Engineered for Flexibility First launched in Japan in 1982, the Daikin VRV system has been embraced by world markets for over 30 years. Now, Daikin proudly S SERIES VRV indoor units combine with residential indoor units, all in one system. introduces the new VRV IV S series-the ideal air conditioning system for homes, shops and offices. BP unit Max. 14 indoor units Residential indoor units VRV indoor units * VRV is a trademark of Daikin Industries, Ltd. OFFICES Contents Main Features Indoor Unit Lineup Specifications Option List Control Systems Air Treatment Equipment Lineup P03 P09 P35 P47 P53 P65 SHOPS HOMES 01 02 Main Features Compact & lightweight design Enhanced lineup The new design has been optimised for the VRV IV S series, with the height of 4 HP to 5 HP models reduced to only 990 mm. This design gives the building a sleek look externally and provides the occupants with a clear, unobstructed view of the scenery. The VRV IV S series is now slim and compact, with outdoor units that require minimal installation space. VRV S 4, 5 HP 1,345 mm VRV 990 mm 320 mm 320 mm S SERIES Mo/C* S SERIES 4, 5 HP To suit a variety of room sizes, VRV IV S series expands our range to include 8 HP and 9 HP. 4 HP S SERIES S (11.2 kW) 4 HP (11.2 kW) Height 1,345 mm Height 990 mm 26% Decrease Product Weight 125 kg Product Weight 71 kg 43% Decrease Mo/C* Mo/C* 4 HP 5 HP 6 HP 8 HP 9 HP *Mo/C represents Model Change Lineup 8 HP (22.4 kW) S SERIES 8 HP 8 HP 765 mm 940 mm 930 mm (22.4 kW) 5 models Model Name RXYMQ4AVE Power Supply 1,430 mm 1,657 mm S SERIES 8 HP Height 1,657 mm Height 1,430 mm Product Weight 185 kg Product Weight 138 kg Decrease Footprint 0.71 m2 Footprint 0.30 m2 58% Decrease 320 mm 14% RXYMQ5AVE RXYMQ6AVE 1-phase, 220-230 V/220 V, 50/60 Hz RXYMQ8AY1 RXYMQ9AY1 3-phase, 380 – 415 V, 50 Hz Decrease Capacity Range 4 HP (11.2 kW) 5 HP (14.0 kW) 6 HP (16.0 kW) 8 HP (22.4 kW) 9 HP (24.0 kW) 25% Capacity Index 100 125 150 200 215 Wide variety of indoor units Indoor units can be selected from 2 lineups, both VRV and residential indoor units, to match rooms and preferences. A mixed combination of VRV indoor units and residential indoor units can be included into one system, opening the door to stylish and quiet indoor units. External view of a condominium Elegant appearance with European style Internal view of a condominium unit CTXG-P series indoor unit 03 04 Initial setting. and outdoor temp. 05 06 .3 dB(A) Step 1: 49 dB(A) Step 2 max. reducing overall turbulence. This motor can save energy because it generates more power with a smaller electric power than an AC or conventional DC motor. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. further improving operating efficiency. Escaping eddies are sucked in by the bent blade edges. so that the machine compress the non-expanded gas. and a locally obtained timer are necessary. 46 dB(A) (Step 2) and 43 dB(A) (Step 3). DC fan motor structure Without the bent blade edge 8:00 Note: • This function is available in setting at site. Automatic mode Large load High capacity Peak in outdoor temperature 100 8 hrs 10 hrs (Initial setting) 50 (Initial setting) 0 52 Night Mode Step 1 max. S 3 2 Motor efficiency (%) Cooling Operation COP 1 Compressor equipped with Reluctance DC motor S SERIES Reluctance DC motor 90 80 Conventional DC motor 70 More than 20% 60 AC motor 50 0 30 60 90 Reluctance DC motor 1 120 Rotational speed (rps) Small load Low capacity Quiet operation Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory using Daikin products. *2 The torque created by the change in power between the iron and magnet parts. *3.2 0 3. Automatic mode Load % Mode 1.Main Features Energy saving Higher Coefficient of Performance (COP) Collection of cutting-edge technologies realises efficient and quiet operation VRV IV S series provides greater energy saving as compared to VRV III S series. The high efficiency compressor to achieve a higher COP 12% Increase VRV 3. of 27ºCDB.49 4 HP 5 HP 6 HP 8 HP 9 HP (11. 6AVE RXYMQ8. The capacity reduction rate differs depending on the operation sound level step selected. completely solving the refrigerant leakage and the wear problem caused by the mechanical friction between the rotor and the blade.0 kW) (22. DTA104A53/61/62.) Use of an optimised sine wave smoothes motor rotation.4 kW) (24. 49 46 43 8:00 Night mode starts 12:00 16:00 20:00 Night mode ends 0:00 4:00 With the bent blade edge Suction 3 DC fan motor Efficiency improved in all areas compared to conventional AC motors. 3.19ºCWB.2 kW) (14. especially at low speeds.6 dB(A) Step 2: 46 dB(A) Step 3 max. . *2. which enhances the compressor efficiency and makes the compressor more quiet and durable.*3 Daikin swing compressor has integrated the rotor with the blade. Can be selected from 8. The operation sound level for the night mode can be selected from 49 dB(A) (Step 1).4 3.56 3. 9AYI >> Swing compressor >> The structural scroll Capacity % Set on the outdoor PCB. In case of 4 HP outdoor unit during cooling operation Operation sound dB(A) Mode 2. Combined mode Combinations of modes 1 and 2 can be used depending on your needs. 5. further reducing turbulence.6 3. Sucked gas is compressed in the Scroll section scrolling part before the Discharge Motor section heated motor. of 35ºCDB. Mode 1.9 dB(A) Step 3: 43 dB(A) 2 Smooth Air Inlet Bell Mouth and Aero Spiral Fan These two features work to reduce sound. Time of maximum temperature is memorised. Initial setting. and normal operation will resume 10 hours*2 after that.86 3. 8 and 10 hours.0 kW) (16.80 3.89 4 3. . The Reluctance DC motor uses 2 different types of torque. 9 and 10 hours.0 kW) *Cooling operation conditions: Indoor temp. resulting in high efficiency compression. Manual mode Starting time and ending time can be input. Can be selected from 6. *1 A neodymium magnet is approximately 10 times stronger than a standard ferrite magnet.77 Daikin DC inverter models are equipped with the Reluctance DC motor for compressor. (An external control adaptor for outdoor unit.8 3. Mode 3. • The relationship of outdoor temperature (load) and time shown in the graph is just an example. . The low operating mode will initiate 8 hours*1 after the peak temperature in the daytime. especially for 6 HP. neodymium magnet*1 and reluctance torque*2. The Aero Spiral Fan features fan blades with the bent blade edges. *1. Sine wave DC inverter Nighttime quiet operation function >> Smooth sine wave DC inverter Operation sound level selectable from 3 steps for the night mode RXYMQ 4. BP unit e First indoor branch Total piping length c d g f h i Max. allowable piping length BP unit .the BP unit 07 g f BP Refrigerant piping length >> REFNET piping system d 08 . Max. Between the outdoor unit and the indoor unit Daikin’s advanced REFNET piping system makes installation easy. while using small-diameter piping. piping. k If indoor unit capacity index is 71 m 10 m 15 m 15 m If the outdoor unit is above n 30 m 30 m 50 m If the outdoor unit is below n 30 m 30 m 40 m o 30 m 30 m 40 m Between BP units Max. 250 m b a 100 m c e First indoor branch Total piping length >> Super wiring system A super wiring system is used to enable shared use of the wiring between indoor and outdoor units and the central control wiring. including wiring. Only two main refrigerant lines are required in any one system. 14 Max. making the VRV IV S series a remarkably versatile system. REFNET greatly reduces the imbalances in refrigerant flow between units. allowable level difference VRV indoor units Automatic test operation Simply press the test operation button and the unit performs an automatic system check. with a relatively simple wiring operation. Simple wiring and piping connection When a mixed combination of VRV and residential indoor units is connected or when only residential indoor units are connected Actual piping length Unique piping and wiring systems make it possible to install a VRV IV S series quickly and easily.Main Features Design flexibility and simplified installation Long piping design possible Connectable up to 14 indoor units Long piping length offers flexibility in the choice of installation positions. a b Actual piping length Max. and simplifies system planning. allowable piping length Total piping length Between the first indoor branch and the farthest indoor unit 4 HP 5 HP 6 HP 8. 40 m m k Max. allowable level difference Outdoor unit . j 15 m Residential indoor units Refrigerant piping length Max.indoor unit Min. The results are returned automatically after the check finishes. stop valves. j. The DIII-NET communication system is employed to enable the use of advanced control systems.the first indoor branch a 5m 5m 5m Between the indoor units l 10 m 15 m 15 m If indoor unit capacity index is 60 h. b+c+d 40 m 40 m 40 m 2 m–15 m 2 m–15 m 2 m–15 m 2 m–12 m 2 m–12 m 2 m–12 m 2 m–8 m 2 m–8 m 2 m–8 m If indoor unit capacity index < 60 Max. and refrigerant charging amount. i l RA 15 m BP j RA VRV Max.the farthest BP or VRV indoor unit 4 HP 5 HP 6-9 HP a+b+c+g+k. RA 15 m Central remote controller VRV RA Indoor unit Max. & min. allowable piping length Outdoor unit . a+b+c+d 50 m 70 m 100 m a+b+c+d+e+f+g+h+i+j+k 250 m 250 m 250 m b+c+g. o 50 m h n Outdoor unit Max. indoor units 120 m BP unit Max. As many as 14 indoor units can be connected to a single outdoor unit.the indoor unit Outdoor unit .9 HP a+b+c+d+i 50 m 70 m 120 m 100 m a+b+c+d+e+f+g+h+i 250 m 300 m 300 m 300 m b+c+d+i 40 m 40 m 40 m 40 m j 10 m 15 m 15 m 15 m If the outdoor unit is above k 30 m 30 m 50 m 50 m If the outdoor unit is below k 30 m 30 m 40 m 40 m Between the indoor units Max. allowable piping length Total piping length The first indoor branch . i. When only VRV indoor units are connected Note: Total capacity index of connectable indoor units must be 50-130% of the capacity index of the outdoor unit. Max. Refer to page 46 for the maximum number of connectable indoor unit. Max. 50 m k 300 m Max. 5HP 3HP 3.1 Capacity Index 20 25 35 50 60 71 FBQ-BV1 CDXS-EAVMA (700 mm width type) Slim Ceiling Mounted Duct Ceiling Mounted Cassette (Double Flow) 9 types 28 models 20 FDXS-CVMA (900/1.25HP 1. opening the door to stylish and quiet indoor units.0 6. all in one system.5 5.0 7.25 40 50 62. VRV indoor units Type Ceiling Mounted Cassette(Round Flow with Sensing) 19 types 89 models 20 25 32 40 50 63 71 80 100 Model Name Capacity Range 0.Indoor Unit Lineup Enhanced range of choices A mixed combination of VRV indoor units and residential indoor units can be included into one system.6HP 2HP 2.100 mm width type) (without drain pump) Slim Ceiling Mounted Duct (Compact Series) FXDQ-SPV1 VRV indoor units combine with indoor units. 09 Floor Standing FXLQ-MAVE Concealed Floor Standing FXNQ-MAVE Floor Standing Duct FXVQ-NY1 10 .5 71 80 100 Capacity Index 125 5HP 125 140 6HP 140 200 8HP 200 250 10HP 250 Residential indoor units with connection to BP units Type Model Name FXFQ-SVM Ceiling Mounted Cassette FCQ-BVE Ceiling Mounted Cassette (Round Flow) FXFQ-LUV1 Ceiling Mounted Cassette (Compact Multi Flow) FFQ-BV1B Ceiling Mounted Cassette (Compact Multi Flow) FXZQ-MVE Ceiling Mounted Built-in 4-Way Flow Ceiling Suspended FXUQ-AVEB FXCQ-MVE Ceiling Mounted Cassette Corner FXKQ-MAVE 25 35 50 60 71 Rated Capacity (kW) 2.0 2.2HP 4HP 20 25 31.8HP 1HP 1.5 3. 14 Wall Mounted indoor units Residential indoor units VRV indoor units FXAQ-PVE *Refer to page 46 for the maximum number of connectable indoor units. FXMQ-PVE Ceiling Mounted Duct BP unit FXMQ-MAVE Ceiling Suspended FXHQ-MAVE Max.100 mm width type) CTXG-PVMAW CTXG-PVMAS FXDQ-PBVE (with drain pump) Wall Mounted FTXS-DVMA FXDQ-PBVET Slim Ceiling Mounted Duct (Standard Series) (700 mm width type) (without drain pump) FTXS-EVMA FXDQ-NBVE (with drain pump) FXDQ-NBVET FTXS-FVMA (900/1. lightweight. quietness and static pressure switching Slim and compact design for easy and flexible installation Ceiling Mounted Duct Type Ceiling Suspended Type FXMQ-PVE FXHQ-MAVE Flexible air discharge unit to fit various forms of space Slim and smooth design suits your shallow ceiling Wall Mounted Type Wall Mounted Type CTXG-PVMAW FTXS-DVMA FTXS-EVMA CTXG-PVMAS FTXS-FVMA FXMQ-MAVE High external static pressure allows flexible installations 11 Slim body with quiet and wide airflow Elegant appearance with European style Stylish flat panel harmonises with your interior décor 12 . Ceiling Mounted Cassette (Compact Multi Flow) Type 4-Way Flow Ceiling Suspended Type Quiet. and designed for user comfort Ceiling Mounted Built-in Type Slim Ceiling Mounted Duct Type Slim design for flexible installation Slim Ceiling Mounted Duct Type (Compact Series) FBQ-BV1 CDXS-EAVMA FXDQ-SPV1 FDXS-CVMA FXDQ-NBVE(T) Slim design. and designed for user comfort FXUQ-AVEB This slim and stylish indoor unit achieves optimum air distribution.Indoor Unit Lineup Daikin offers a wide range of indoor units includes both VRV and residential models responding to variety of needs of our customers that require air-conditioning solutions. compact. and easy to install in narrow ceiling spaces Slim Ceiling Mounted Duct Type (Standard Series) FXDQ-PBVE(T) Ceiling Mounted Cassette Corner Type Suitable for perimeter zone air conditioning Floor Standing Duct Type FXVQ-NY1 Large airfiow type for large spaces. modern interior finish Quiet. and can be installed without the need for ceiling cavity FXNQ-MAVE Stylish flat panel design harmonised with your interior décor FXCQ-MVE Thin. Residential indoor units with connection to BP units Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Double Flow) Type FXLQ-MAVE Concealed Floor Standing Type Ceiling Mounted Cassette (Round Flow) Type Presence of people and floor temperature can be detected to provide comfort and energy savings FXZQ-MVE Floor Standing Type FCQ-BVE Ceiling Mounted Cassette (Compact Multi Flow) Type FFQ-BV1B FXKQ-MAVE Specially designed for false ceilings —for a smooth. Flexible interior design for each tenant. compact. Wall Mounted Type FXAQ-PVE VRV indoor units Ceiling Mounted Cassette (Round Flow with Sensing) Type FXFQ-SVM FXFQ-LUV1 360 airflow improves temperature distribution and offers a comfortable living environment. we end up raising the temperature setting. Infrared floor sensor The sensor detects the floor temperature and automatically adjusts operation of the indoor unit to reduce the temperature difference between the ceiling and the floor.5m 4. the airflow rate is automatically increased. DC fan motor. When human presence detected.. because the area around the feet does not get too cold. Without sensing function Thanks to the individual airflow direction control function.. FXFQ25S / FXFQ32S / FXFQ40S Auto airflow direction mode (default: OFF) *1. 16m Drain pump is equipped as standard accessory with 850 mm lift. To increase comfort. Feet are warm. Energy savings 850 mm Selectable airflow rate: 3 steps and Auto. Low operation sound level FXFQ-S 25/32 40 50 63 80 100 20°C near floor In order to reduce drafts. approx. *1.. Uncomfortable draft occurs. *2. Without sensing function 30°C near ceiling Room temperature is detected as 30°C. When air is blown horizontally. which is lower. Energy is saved. It can be set ON using the remote controller. The infrared floor sensor detects at the floor surface. 14 ..7m 3.5m 13. Heating Individual airflow direction control With sensing function 125 Sound level 30/28. The infrared presence sensor detects 80 cm above the floor. Infrared presence sensor Improved energy efficiency thanks to a new heat exchanger with smaller tubes. but draft is strong.Indoor Unit Lineup VRV Indoor Units Ceiling Mounted Cassette (Round Flow with Sensing) Type Sensing function Draft prevention function Dry Cooling Heating When human presence not detected. For this reason. airflow direction can be individually adjusted for each air discharge outlet to prevent uncomfortable drafts and to deliver optimal air distribution. 20°C near floor The floor temperature.Both airflow direction and airflow rate shoud be set to Auto. Room temperature is Roo calculated lated ted as 27°C in the area which is in th the vicinity of the person. When the difference becomes small.0m approx. Ceiling height 2.*2 When air is blown downward. because air is blown downward. 13 4. *2. approx. air is blown horizontally where a person is located. the airflow rate is automatically reduced. approx. the unit automatically returns to controlling the flaps for an unoccupied room. 24°C near floor Automatic control using the temperature near the person as the room temperature.. Blown downward Blown downward Blown horizontally When a person is detected. Dead spot of airflow (diameter)*1 The floor temperature. *1. (Auto airflow rate is available when BRC1E62 is used. drafts are prevented by making the flap horizontal. y.5m approx. because you are warmed up from the feet. When human presence not detected.Draft prevention function is set OFF in the initial setting. 17°C near floor Area near floor doesn’t reach set temperature and feet feel cold. The sensor detects human presence and adjusts the airflow direction automatically to prevent drafts. because warm air collects near the ceiling. Ceiling height 2. but feet get cold.Draft prevention function is OFF in the initial setting.5m *1. Detection range (diameter) *2 11m 14m *2. Area around feet gets too cold because air conditioner continues until the temperature near the ceiling reaches the set temperature. and DC drain pump motor. 2 When human presence detected. Drafts are minimal. Comfortable because draft is reduced and area around feet is warm. 2 Detecting the presence of people in 4 areas Cooling Floor temperature is detected and over cooling prevented. When there is a large difference between the ceiling and floor temperatures. which is lower than near the ceiling.7m 3. Detecting the average temperature of indoor floor 20°C near floor Energy savings Indoor unit offers 360° airflow discharges air in all directions with more uniform temperature distribution. is detected. flaps are controlled to deliver optimal air distribution for both cooling and heating operations when there are no people. is detected and warm air is blown downward where no person is present. When a person is not detected for 5 minutes. air direction is changed to horizontal and feet get cold.) The tendency of people to raise the temperature too much is prevented. Auto airflow rate mode controls the airflow in accordance with the difference between floor and ceiling temperatures. Auto airflow direction mode + Auto airflow rate mode Comfort and Energy saving preventing over Cooling / Heating *1..0m approx. The temperature near the person is automatically calculated by detecting the temperature of the floor.Airflow direction shoud be set to Auto. With sensing function Feet get cold. 30°C near ceiling Feet are kept warm and comfortable while reducing uncomfortable drafts.5m 11. FXFQ50S / FXFQ63S / FXFQ80S FXFQ100S / FXFQ125S Swing Presence of people and floor temperature can be tected to provide co detected comfort and energy savings Swing Blown horizontally With the Auto airflow direction mode. Detection range 8.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35 (H/M/L) To avoid draft. Indoor Unit Lineup VRV Indoor Units Ceiling Mounted Cassette (Round Flow with Sensing) Type Individual airflow direction control Individual airflow setting Sensing sensor mode*1*2 Sensing sensor low mode (default: OFF) Airflow direction of each of the four air outlets can be controlled individually. Based on preset user conditions. If people do not return.These functions are not available when using the group control system. Swing. In case of FXFQ63S type (Data is based on Daikin research. airflow will be on the high side.*2 Airflow block for cabinet side Easy setup with remote controller Airflow block Horizontal H i t l fl flow *1. 60. the air conditioner will raise the temperature 1℃ every 30 minutes and then operate at 30℃. This function only works when all-round flow is used. Airflow block function*1 Total comfort by individual airflow direction control and “airflow block function” The system automatically saves energy by detecting whether or not the room is occupied. (Positions 0 to 4. 90 or 120 minutes respectively with remote controller.3m/s. 0. 30. 16 . Airflow block air velocity approx. Sensing sensor stop mode (default: OFF) When there are no people in a room. set • Cooling setpoint: 26℃ • Shift temperature: 1. Airflow block function prevents uncomfortable drafts by reducing air velocity to approx. A 2 28℃ 27℃ 26℃ 26℃ Occupied Automatically reverts when people return.3m/s*1 Airflow block function prevents uncomfortable drafts by reducing air velocity. *2. Absent stop time can be selected from 1 to 24 hrs in 1 hr increments with remote controller. Blocked. the airflow value may differ depending on the effect of surrounding conditions and the way in which the temperature was adjusted. Setpoint (℃) Example 28 27 26 Example 1 Blocked Operation is reduced in places where there are no people. *2. Time After 30 min After another 30 min Shift temperature and time can be selected from 0. air conditioner will not switch on automatically. Under actual conditions. • Limit cooling temperature:30℃ Unoccupied Example No individual 2 setting blocked If people do not return. The system automatically saves energy by detecting whether or not the room is occupied. Time After 30 min Setpoint (℃) 20 19 18 (Auto direction) No ind. *3.*3 The system automatically saves energy by detecting whether or not the room is occupied. if the airflow rate is set to High.5℃ increments and 15. A gap of 1500 mm is required if the air block function is not used.User can set these functions with remote controller. 4 Swing 4 20℃ Position 2 Outlet mark 20℃ 19℃ 18℃ Unoccupied Automatically reverts when people return. *3. the system automatically stops operation if the room is unoccupied. • Limit heating temperature: 16°C Occupied 1 Airflow Ai fl bl block k *3 500 mm Wall *1. 45. Works in one direction only.0°C • Shift time: 30 min. the set temperature is shifted automatically. It cannot be used when sealing material is used in the air discharge outlet (option). It can be set using the BRC1E62 remote controller. the system stops automatically. however.Please note that upon re-entering the room. Also can support such case The airflow block function is useful when rearranging the room layout.) When there are no people in a room. The set temperature is shifted automatically if the room is unoccupied. There is no need for sealing material of air discharge outlet (option). and No individual setting are selectable. 15 3 Position 2 Swing After another 30 min • Heating setpoint: 20°C • Shift temperature: 1.5 to 4℃ in 0. the air conditioner will lower the temperature 1°C every 30 minutes and then operate at 16°C.0℃ • Shift time:30 min. The set temperature is shifted automatically if the room is unoccupied.) When using FXFQ80S type or higher. 0. The industry’s first* Round Flow Ceiling Mounted Cassette type offers 360° airflow with improved temperature distribution. which repel dirt. Drain pump is equipped as a standard accessory with a 850 mm lift. Note: Whatever the discharge direction. Low operation sound level FXFQ-LU 25/32 40 50 (dB(A)) 63 80 100 125 Sound level 30/28. Their non-flocking surfaces.5/31 43/37.5/27 34/31/28 36/33. an air discharge outlet sealing material (option) must be used to close each unused outlet. other than standard setting (0°-60°). 4-way flow 3-way flow 0° 0° Drain pump is equipped as standard accessory with 750 mm lift. with a panel surface that has been treated with a dirt-repellant coating. as well as 2-way to 4-way flows. Resists soiling Control of the airflow rate can be selected from 3-step control. 18 .5/27 31/29/27 32/29. 4-way flow Quiet. If installing for other than all-round flow. and 4-way airflow patterns are available. 750 mm 2 2-. and designed for user comfort Dimensions correspond with 600 mm X 600 mm architectural module ceiling design specifications. so you can choose the most suitable airflow pattern depending on location or room layout. the same type of panel is used. There are much fewer areas of uneven temperature. mould and bacteria that cause blockages and odours. The air filter has an anti-mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter. the release date for Japan. preventing the growth of slime. Untreated surface Dirt and grime • Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space. the sealing material for air discharge outlet (option) must be used to close each unused outlet.5 kg for FXFQ25-50LU models makes installation easy. 17 0° 60° A modern sophisticated decoration panel has been applied. compact. Low operation sound level (230 V)(dB(A)) FXZQ-M 20/25 32 40 50 Sound level (H/L) 30/25 32/29 32/26 33/29 36/28 36/30 41/33 41/34 Round Flow Comfortable airflow There are areas of uneven temperature. 3-.Indoor Unit Lineup VRV Indoor Units Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type FXFQ25LU / FXFQ32LU / FXFQ40LU FXZQ20M / FXZQ25M / FXZQ32M FXFQ50LU / FXFQ63LU / FXFQ80LU FXZQ40M / FXZQ50M FXFQ100LU / FXFQ125LU 360° airflow improves temperature distribution and offers a comfortable living environment. Treated surface 0° 850 mm 4-way flow 3-way flow L-shaped 2-way flow *For 3-way or 2-way flow installation. L-shaped 2-way flow All-round flow is available. The horizontal louvres prevent dew condensation. 60° 60° *Angles can be also set on site to prevent drafts (0°-35°) or soiling of the ceiling (25°-60°). enabling installation in the corner of a room.5/32 44/39/34 (HH/H/L) Example of airflow patterns: All-round flow 60° Fixed angles: 5 levels An antibacterial treatment that uses silver ions has been applied to the drain pan. are easy to clean. 1 Wide discharge angle: 0° to 60° Auto swing * As of April 2004. The light weight unit at 19. Low operation sound level 198 mm Built-in electronic expansion valve eliminates the need for a BEV unit. Auto airflow rate control can be selected with wired remote controller BRC1E62. A flat-type suction grille and a detachable blade make cleaning easy. New model Energy efficiency has been improved thanks to the adoption of a new heat exchanger with smaller tubes. which improves flexibility of installation. DC fan motor and DC drain pump motor. The unit can be used for various locations such as the ceilings with no cavity and bare ceilings. 3-way and 4-way discharge patterns are available. colourimetric method). and easy to install in narrow ceiling spaces BEV unit is not needed With adoption of the individual flap control. which gives a simple appearance. lightweight. (When a high-efficiency filter is attached. All models feature a compact design with a depth of only 600 mm. the auto swing mechanism realises even distribution of airflow and room temperature.) Unified slim height of 198 mm for all models that gives the unified impression even when models with different capacities are installed in the same area. Current model Control of the airflow rate has been improved from 2-step to 3-step control. Position 2 Position 3 Swing A long-life filter (maintenance free up to one year*) is equipped as standard accessory. The thin unit (only 305 mm high) can be installed in a ceiling space as narrow as 350 mm. For dust concentration of 0. Depending on installation site requirements or room conditions.Indoor Unit Lineup VRV Indoor Units 4-Way Flow Ceiling Suspended Type Ceiling Mounted Cassette (Double Flow) Type FXCQ20M / FXCQ25M / FXCQ32M FXUQ71A / FXUQ100A FXCQ40M / FXCQ50M / FXCQ63M FXCQ80M / FXCQ125M This slim and stylish indoor unit achieves optimum air distribution. 4-way flow (220 V)(dB(A)) FXCQ-M 20 25/32 40/50 63 80 125 Sound level (H/L) 32/27 34/28 34/29 37/32 39/34 44/38 Designed with higher airflow suitable for high ceiling application up to 3 metres. Drain pump is equipped as standard accessory with 600 mm lift. Drain pump is equipped as a standard accessory. Unit body and suction panel adopted round shapes and realised a slim appearance design. 305 mm Flaps close automatically when the unit stops. Providing 2 different settings of standard and ceiling soiling prevention. L-shaped 2-way flow 19 20 . the unit's height is 400 mm. airflow direction adjustment can be individually set for each air outlet.15 mg/m3 3-way flow Individual airflow direction example case Position 0 Two types of optional high-efficiency filter are available (65% and 95%. 600 mm Major maintenance work can be performed by removing the panel. * 8 hr/day. and the lift height has been improved from 500 mm to 600 mm. 25 day/month. 2-way. and can be installed without the need for ceiling cavity. BEV unit is needed Thin. which realises the optimum air distribution. 5 directions of airflow and auto-swing can be selected with wired remote controller BRC1E62. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). 10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models. 15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models. Great for hotel use! (m) 3 Min. Providing 3 different settings of standard. * 8 hr/day.15 mg/m3 21 FXDQ-PB/NBVE: with a drain pump (750 mm lift) as a standard accessory FXDQ-PB/NBVET: without a drain pump (dB (A)) FXDQ-PB/NB 20/25 32 40 50 63 Sound level (HH/H/L) 28/26/23 28/26/24 30/28/26 33/30/27 33/31/29 * The values of operation sound level represent those for rear-suction operation.Indoor Unit Lineup VRV Indoor Units Ceiling Mounted Cassette Corner Type Slim Ceiling Mounted Duct Type (Standard Series) Slim design. Set for front discharge using a suspended ceiling. draft prevention and ceiling soiling prevention. 25 day/month. Suspension bolt* Air filter 240 mm AIR Main body Discharge grille * 500 mm Suction grille * Downward discharge AIR Air discharge grille (Option) * To be obtained locally External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model. 24˚C 20 mm Single-flow type allows effective air discharge from corner or from drop-ceiling. 750 mm Ceiling 22 . * Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa. the unit can be installed in the minimum space of 195 mm. quietness and static pressure switching FXKQ25MA / FXKQ32MA FXKQ40MA / FXKQ63MA Suited to use in drop-ceilings! Slim design for flexible installation FXDQ20PB / FXDQ25PB / FXDQ32PB Slim body needs only 220 mm space above the ceiling. this model is suitable to install in limited spaces like drop-ceilings in hotels.195 mm FXDQ40NB / FXDQ50NB / FXDQ63NB 4 5 200 mm Only 6 (m) 200 mm 900 mm 700 mm * 1. Main body FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.100 mm in width for the FXDQ63NB model. If you use a panel spacer (option). the auto swing mechanism realises even distribution of airflow and room temperature. Only 700 mm in width and 23 kg in weight. Front discharge is possible with an air discharge unit (option). 0 20˚C 1 2 3 Only 200 mm in height. which allows the installation in the drop-ceiling or sagging wall. Low operation sound level Downward discharge is shut off and air is blown straight out (front discharge). this model can be installed in rooms with as little as 240 mm in height for the ceiling space between the drop-ceiling and ceiling slab. Panel spacer 2 28˚C 32˚C 30˚C 26˚C 22˚C 1 Drain pump is equipped as standard accessory with 500 mm lift. Air discharge grille (Option) Control of the airflow rate has been improved from 2-step to 3-step control. FXDQ-NB: external static pressure of 15 Pa. A long-life filter (maintenance free up to one year*) is equipped as standard accessory. For dust concentration of 0. mould and bacteria that cause blockages and odours. The depth of the product is only 450 mm which is suitable to install in limited spaces. The weight of the FXMQ40P has been reduced from 44 kg to 28 kg.Indoor Unit Lineup VRV Indoor Units Slim Ceiling Mounted Duct Type (Compact Series) Ceiling Mounted Duct Type FXMQ20P / FXMQ25P / FXMQ32P FXMQ40P / FXMQ50P / FXMQ63P FXMQ80P / FXMQ100P / FXMQ125P FXMQ140P FXDQ20SP / FXDQ25SP FXDQ32SP / FXDQ40SP FXDQ50SP / FXDQ63SP Slim and compact design for easy and flexible installation Middle and high static pressure allows for flexible duct design It comes with a slim and compact design with a height of only 200 mm that requires as little as 240 mm in height for the ceiling space between the drop-ceiling and ceiling slab. preventing the growth of slime. Without drain pump 200 mm Air suction Drain pump is equipped as standard accessory with 750 mm lift. Control of the airflow rate has been improved from 2-step to 3-step control. Low operation sound level Duct FXMQ-P 32 40 50 (dB (A)) 63 80/100 125 140 Sound level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43 (HH/H/L) Canvas bellows and air suction panel Air discharge 20/25 Energy-efficient The adopted DC fan motor is much more efficient than the conventional AC motor. 25 mm Indoor unit Indoor unit 24 . 240 mm and above 0–250 mm 750 mm Top view Ceiling 23 470 mm 470 mm Ceiling Side view With drain pump 222 mm Simplified Static Pressure Control External static pressure can be easily adjusted using a change-over switch inside the electrical box to meet the resistance in the duct system. 200 mm 700 mm* Only 450 mm *For FXDQ20-32SP models Drain pump is equipped as standard accessory with 700 mm lift. Air suction Duct Air discharge FXMQ200MA/FXMQ250MA Improved ease of installation Airflow rate can be controlled using a remote controller during test operation. An antibacterial treatment that uses silver ions has been applied to the drain pan. increasing design flexibility. With the conventional model. 700 mm Ceiling It is available in two types – ceiling return and ordinary duct to suit different installation conditions. an improvement over the 390 mm height of conventional models. 30 Pa–100 Pa for FXMQ20P-32P 30 Pa–160 Pa for FXMQ40P 50 Pa–200 Pa for FXMQ50P-125P 50 Pa–140 Pa for FXMQ140P Great for residential use All models are only 300 mm in height. Built-in Drain Pump (Option) Housing the drain pump inside the unit reduces the space required for installation. yielding an approximate 20% decrease in energy consumption (FXMQ125P). A DC fan motor increases the external static pressure capacity range to include middle to high static pressures. the airflow rate was controlled from the PC board. Improved ease of maintenance The drain pan can be detached for easy cleaning. It is automatically adjusted to the range between approximately ±10% of the rated HH tap airflow for FXMQ20P–125P. Vertical auto-swing realises efficiency of air distribution. Drain pump kit is available as optional accessory. * 8 hr/day.15 mg/m3 26 . 100° 25 Height of drain-up Flexible installation Drain pipe can be fitted to from either left or right sides. Uses the quiet stream fan and many more advanced technologies. Discharge angle is automatically set at the same angle as the previous operation when restarting. For dust concentration of 0. 600 mm (dB(A)) FXAQ-P 20 25 32 40 50 63 Sound level (H/L) 35/31 36/31 38/31 39/34 42/37 47/41 Drain pan and air filter can be kept clean by mould-proof polystyrene. which lifts the drain 1. 25 day/month. Flat panel can also be easily removed and washed for more thorough cleaning. 5 steps of discharge angle can be set by remote controller. Drain pump kit Indoor unit A long-life filter (maintenance free up to one year*) is equipped as standard accessory. Maintenance is easy Non-dew Flap with no implanted bristles Bristle-free Flap minimises contamination and makes cleaning simpler.000 mm from the bottom of the unit. Sound absorption member Turbulent flow is produced Flat panel can be cleaned with only the single pass of a cloth across their smooth surface. Non-dew Flap 1. Quiet stream fan Low operation sound level Straightening vane Low operation sound level (dB(A)) FXHQ-MA 32 63 100 Sound level (H/L) 36/31 39/34 45/37 Installation is easy Drain pump kit (option) can be easily incorporated.000 mm Easy-to-clean flat design Maintenance is easier because everything can be performed from below the unit. The louvre closes automatically when the unit stops.Indoor Unit Lineup VRV Indoor Units Ceiling Suspended Type Wall Mounted Type FXAQ20P / FXAQ25P FXHQ32MA / FXHQ63MA FXAQ32P / FXAQ40P FXHQ100MA FXAQ50P / FXAQ63P Slim body with quiet and wide airflow Stylish flat panel design harmonised with your interior décor Adoption of QUIET STREAM FAN Stylish flat panel design creates a graceful harmony that enhances any interior space. (Initial setting: 10° for cooling and 70° for heating) Drain pump kit (built inside main unit) Wide air discharge openings produce a spreading 100° airflow. A wide range of optional accessories are available such as high-efficiency filters. Highly flexible installation is possible. * 8 hr/day. Flexible interior design for each tenant. FXNQ50MA / FXNQ63MA Designed to be concealed in the perimeter skirting-wall * 8 hr/day. A long-life filter (maintenance free up to one year*) is equipped as standard accessory. The unit is concealed in skirting-wall of perimeter. Air conditioning Outdoor air introduction * Air introduced from the outside and circulated air must be mixed in the air conditioner primary side before introduction into the air conditioner. Full-scale duct connection airflow allows for air conditioning evenly in spacious areas.Indoor Unit Lineup VRV Indoor Units Floor Standing Type Floor Standing Duct Type FXLQ20MA / FXLQ25MA FXVQ125N / FXVQ200N FXLQ32MA / FXLQ40MA FXVQ250N FXLQ50MA / FXLQ63MA Suitable for perimeter zone air conditioning Floor Standing types can be hung on the wall for easier cleaning. is considerably easier. FXNQ20MA / FXNQ25MA A long-life filter (maintenance free up to one year*) is equipped as standard accessory.15 mg/m3 Connecting port Refrigerant piping * Applies also to Floor Standing type (FXLQ-MA). For dust concentration of 0. The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier. * Note that the operation sound increases by approximately 5 dB(A). 25 day/month. 25 day/month. All-fresh (using outdoor air only) system Outside *When using the unit as an outdoor-air processing unit. The connecting port faces downward. greatly facilitating on-site piping work. For dust concentration of 0. Strictly follow the restrictions specified in the Engineering Data Book. Various installations can be supported from full-scale duct connection airflow to direct airflow that allows for easy installation. Cleaning under the unit. For dust concentration of 0. 27 A long-life filter (maintenance free up to one year*) is equipped as a standard accessory. Concealed Floor Standing Type FXNQ32MA / FXNQ40MA Design with high maintainability that allows major services and maintenance services to be performed at the front.15 mg/m3 Wall hanging Floor installation Duct connection airflow type Adding the plenum chamber (option) allows for simple operation with direct airflow. Outdoor air introduction Air conditioning Return + Outdoor air mixed system Outside Circulated air Outdoor air intake mode is useable as an outdoor-air processing air conditioner. Running the piping from the back allows the unit to be hung on walls.15 mg/m3 Direct airflow type The high static pressure type driven by the belt drive system allows for use of air discharge outlets in various shapes as well as long ducts. that enables to create high class interior design. Large airflow type that fits for spacious areas such as factories and large stores. * 8 hr/day. Large airflow type for large spaces. there are some restrictions. where dust tends to accumulate. 26 day/month. 28 . Min. and designed for user comfort Three convenient patterns for auto-swing operation Designed to fit 600 mm wide ceiling grids Low draft performance is designed for your comfort. Option Note: Remote controller cables not included. Low operation sound level 29 (H/L) FCQ35B FCQ50B FCQ60B FCQ71B 33/29 dB (A) 33/29 dB (A) 35/30 dB (A) 35/30 dB (A) These models have the power to provide a comfortable airflow even with a ceiling height of up to 3. 5 direction AUTO-SWING 700 mm Decoration panel is optional Setting to prevent soiling of ceiling 600 mm 600 mm (Set on site) Auto-swing between 0 and 60 60 Settable to 5 different levels between 0 and 60 0 0 Auto-swing between 0 and 35 35 25 60 Auto-swing between 25 and 60 Settable to 5 different levels between 0 and 35 35 25 60 Settable to 5 different levels between 25 and 60 Note: Angles shown above are provided as a guide. 575 mm Standard 0º Horizontal Flow 0º 575 mm Less draught 286 950 mm mm act Comp e panel tiv decora Draft prevention Same for all models Comfortable across all areas Conditioned air is distributed Adjustable airflow angle to evenly by Auto-swing operation. Option Signal receiver unit Note: Wireless remote controllers and signal receiver units are sold as a set.8 m. 245 mm Draft prevention setting T-bar (Set on site) 750 mm 0 0 60 Ceiling panel Drain pump is equipped as standard with 750 mm. compact. 700 mm 950 mm Soiling prevention Standard setting T-bar grid does not need to be cut. They may differ depending on the installation site. 750 mm 30 . modern interior finish All models feature a decoration panel with the same compact size and simple design for easier planning of lighting systems and harmonising of interior décor. suit all room conditions. Cables should be obtained locally. Specially designed for false ceilings —for a smooth.5/24. Low operation sound level Max.8 m (H/L) FFQ25B FFQ35B FFQ50B FFQ60B 29. 3. Cables should be obtained locally. The indoor units weigh only 24 kg and require an installation space with a height of just 245 mm. Option Signal receiver unit Note: Wireless remote controllers and signal receiver units are sold as a set. Quiet.Indoor Unit Lineup Residential Indoor Units with connection to BP units Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Compact Multi Flow) Type FFQ25B / FFQ35B / FFQ50B / FFQ60B FCQ35B / FCQ50B / FCQ60B / FCQ71B Option Note: Remote controller cables not included.5 dB (A) 32/25 dB (A) 36/27 dB (A) 41/32 dB (A) Drain pump is equipped as standard accessory with 750 mm lift. Indoor Unit Lineup Residential Indoor Units with connection to BP units Ceiling Mounted Built-in Type Slim Ceiling Mounted Duct Type CDXS25EA / CDXS35EA FBQ60B / FBQ71B FDXS25C / FDXS35C FDXS50C / FDXS60C Option Note: Remote controller cables not included. Slim and smooth design suits your shallow ceiling Flexible air discharge unit to fit various forms of space The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab. * Home Leave Operation can be selected for any temperature from 18 to 32˚C for cooling operation and 10 to 30˚C for heating operation. To prevent an increase in operation noise. Slim Ceiling Mounted Duct type models do not have drain-up pumps. Standard accessory Note: Remote controllers other than the standard accessory wireless remote controller cannot be used. Air discharge duct* Suspension bolt* Suction duct* Air filter Air discharge grille* AIR 240 mm Chamber Signal receiver wire Length = 1. Grilles. 1 Air suction Air discharge 45 mm Ceiling return Ceiling return with high-efficiency filter 2 Air conditioner 2 Air conditioner 450 mm or more 4 6 Long-life filter Air suction 4 9 7 11 11 Ordinary duct (procured locally) 540 mm or more Air suction Air discharge 460 mm or more 8 Air discharge Air suction Air discharge 1 2 3 Decoration panel Air discharge adaptor Canvas duct 4 5 6 Flexible duct Air discharge grille Air discharge chamber To cope with the challenges of L-shaped or U-shaped spaces. 32 . because the unit includes a sensor that detects room temperature. 7 8 9 High-efficiency filter Service access panel Rear intake blocking pad (Blind board) 10 11 12 L-shaped room U-shaped room Long room 200 mm Air suction flange Rear suction filter chamber Buttom suction filter chamber Only 700 mm Drain pump is equipped as standard accessory with 250 mm lift. (H/L) FBQ60B Signal receiver Signals from the wireless remote controller are transmitted to the signal receiver. This means that an air-conditioned welcome awaits when you wake or return. avoid installing the air suction grille directly below the suction chamber. so are easily installed in limited spaces. It also works with both flexible and ordinary ducts. it is possible to install the air discharge unit away from the main unit. making them ideal for even shallow ceilings. different types of architectural space can be kept comfortable. 2. * Home Leave Operation function must be set using the remote controller when going to sleep or leaving the house. It also means that the indoor temperature can quickly return to your favourite comfort setting.900 mm Low operation sound level 31 CDXS-EA 10 9 8 5 Great for hotel use! Ordinary duct (procured locally) Air conditioner 8 5 Options 6 With ordinary ducts Low operation sound level FBQ71B 41/35 dB (A) 41/35 dB (A) Air suction grille* AIR * Locally obtained parts Notes: 1. and installation parts should be obtained locally.7 m3/min 9. Standard installation examples With high-efficiency filter In crawl space 6 With canvas duct and decoration panel (sold separately) 2 Air conditioner 4 2 Air conditioner 350 mm or more 4 6 5 425 mm or more 1 5 Air discharge 2 Air conditioner 4 6 3 5 1 Air suction 540 mm or more 7 12 3 Long-life filter Air suction Long-life filter Air discharge Models in the CDXS-EA series are only 700 mm in width and 21 kg in weight. piping connections. all models can be installed in rooms with as little as 240 mm depth between the drop ceiling and ceiling slab. Cables should be obtained locally. At the same time. The signal receiver unit must be located near the air suction inlet. 3. and after waking up or returning home. 250 mm Dimensions (H x W x D) Weight Airflow rate (H) External static pressure CDXS25EA CDXS35EA FDXS25C FDXS35C 200 x 700 x 620 mm 200 x 900 x 620 mm 21 kg 25 kg 8.5 m3/min 10 m3/min 30 Pa 40 Pa C(F)DXS25 C(F)DXS35 (H/L/SL) FDXS50 FDXS60 35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A) Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home. ducts. This extends the possibilities for coping with human gathering patterns or sun lighting. Just 200 mm in height. This elegant body houses state-of-the-art technology which delivers superior performance. To start 3D Airflow. airflow is directed away from him/her. 3D Airflow 3D Airflow combines Vertical and Horizontal Auto-Swing to reduce indoor temperature fluctuation. During cooling operation. During heating operation. Intelligent Eye automatically adjusts the set temperature by approximately 2°C to save energy. airflow is directed away from him/her. Wall Mounted indoor units achieve quiet sound levels of 22 dB (A) during cooling operation. The flaps and louvers swing in turn. Area 1 Comfort Airflow Mode Comfort Airflow Mode prevents uncomfortable drafts from blowing directly on to a person’s body. Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter. expanding the comfort zone. 33 Stylish flat panel harmonises with your interior décor Cooling operation Heating operation 34 . If there is no movement in a room for 20 minutes. it adjusts the temperature by 2˚C for energy savings. Area 1 Area 2 If a person is detected in area 1. Elegant appearance with European style Elegant Appearance with Curved Panel The sleek design of the CTXG-P indoor unit features a uniquely European style. Two-Area Intelligent Eye A combination of Comfort Airflow Mode and Intelligent Eye directs airflow away from people to avoid drafts. The CTXG-P series offers a versatile choice for home-owners. This function circulates air to every part of a room for uniform cooling or heating of even large spaces. When there is no movement. Area 2 Air filter Catches dust Titanium Apatite Photocatalytic Air-purifying Filter When you are in the room When you go out Comfort Airflow Mode prevents uncomfortable drafts from blowing directly on to your body. Bacteria Removal Test Testing method: dropping method Result certificate: No. The photocatalyst is activated simply by exposure to light. when you press the COMFORT button during cooling operation. the flap moves upward to prevent direct cold drafts. 012553-1 and 012553-2 Testing organisation: Japan Spinners Inspecting Foundation If a person is detected in area 2. (H/L/SL) FTXS20/25 FTXS35 FTXS50 FTXS60 FTXS71 37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A) Titanium apatite is a photocatalytic material with high adsorption power. the flap turns vertically downwards to drive warm air to the floor. The flaps and louvers swing in turn. it also moves downward to prevent direct drafts and deliver warm air to the floor. push both the Vertical and Horizontal Auto-Swing buttons. Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface. the flap moves upwards to prevent cold drafts. During heating operation. With this function.Indoor Unit Lineup Residential Indoor Units with connection to BP units Wall Mounted Type Wall Mounted Type FTXS20D / FTXS25E / FTXS35E CTXG25P / CTXG35P / CTXG50P Standard accessory* Standard accessory FTXS50F / FTXS60F / FTXS71F Standard accessory* * Remote controllers other than the standard accessory wireless remote controller cannot be used. designers and architects alike. These filters are not medical devices. Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room. 5/11.) •Sound level: Anechoic chamber conversion value.500 kW 3.000 Btu/h 9.5/10.700 9.0 kW 2.5/19.800 FXZQ40MVE FXZQ50MVE Cooling capacity kcal/h 1.600 10.900 8.034 0. 20) Model BYFQ60B3W1 Colour White (6.0 12.0/17.300 34.5 mm 50X950X950 kg 5.2 14.300 34.8 3.5/11 19/16.090 0.0 12.300 5.0 cfm 441/406/353 441/406/353 512/459/388 777/618/477 830/653/477 830/688/530 1.800 Btu/h 30.400 6.080 0.5 Note: Specifications are based on the following conditions.5/27. 220-240 V. 38.800 6. •Heating: Indoor temp.5/13. Equivalent piping length: 7.700 38.5 m.0 6. Outdoor temp.5 5.6 7.600 17. 220 -240 V/220-230 V.095 0. 50/60 Hz Cooling capacity 11. 6°CDB.130/918/706 1.037 0.073 Heating kW 0.8 3.100 7. measured at a point 1 m in front of the unit and 1 m downward.5/13.200 47.038 0.600 12.090 0. 220-240 V/220-230 V. 26/Internal Dia.027 0.174 0.5/10 15/13/11 16/13.107 Galvanised steel plate Sound level (H/M/L) Dimensions (H×W×D) mm 246×840×840 kg Machine weight 23 Liquid (Flare) Gas (Flare) 288×840×840 19 mm 26 6. Equivalent piping length: 7.179 Fresh white Sound level (H/M/L) Dimensions (H×W×D) Machine weight m3/min 22.800 kcal/h 2.800 13.400 4. Outdoor temp.3 8.200 30.5) Dimensions(H×W×D) Weight mm 55×700×700 kg 2. these values are normally somewhat higher as a result of ambient conditions.053 0.0 5. • Heating: Indoor temp.200 30.100 21.5/13.0 Cooling kW 0.800 3.3 8.100 24.8 3.600 12.700 54.5 Cooling kW 0.6 7.900 Btu/h kW Airflow rate (HH/H/L) Machine weight kcal/h kcal/h m3/min 13/11.9 VP20 (External Dia.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35 Airflow rate (H/M/L) Panel (Option) FXZQ32MVE 1-phase.900 13.400 3. •Capacity of indoor unit is only for reference. Equivalent piping length: 7.6 4.5 11/8 14/10 cfm 318/247 335/265 388/282 493/353 dB(A) 30/25 32/26 36/28 41/33 mm 286×575×575 kg 18 mm 12.090 0.5 m.115 Heating kW 0.900 13. Outdoor temp.031 0.4 9.2 4.800 Btu/h 7. 50/60 Hz kW Casing Piping connections FXZQ25MVE kcal/h Heating capacity Power consumption FXZQ20MVE MODEL Power supply Airflow rate (H/L) Sound level (H/L) 230 V Dimensions (H×W×D) Machine weight m3/min 9/7 9.600 12.066 0.200 MODEL 1-phase.0 6.033 0.076 0.800 3. (See Engineering Data Book for details.5/32 44/39/34 Airflow rate (H/M/L) Liquid (Flare) Piping connections Gas (Flare) 9. • Capacity of indoor unit is only for reference.5/27 30/28.165/989/794 Dimensions (H×W×D) FXUQ100AVEB FXUQ71AVEB Power supply Power consumption Galvanised steel plate Casing 35 4-way Flow Ceiling Suspended Type 1-phase. Actual capacity of indoor unit is based on the total capacity index.0/26.5 cfm 459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1.1 9.800 3.400 19. •Cooling: Indoor temp.: 20°CDB.5 m.7 VP25 (External Dia.200 8.3 Cooling kW 0.: 7°CDB.100 42.400 19. (FXUQ-A) Anechoic chamber conversion value.5/10.7 15.600 10.Specifications VRV Indoor Units Ceiling Mounted Cassette (Round Flow with Sensing) Type Ceiling Mounted Cassette (Compact Multi Flow) Type FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM MODEL Power supply 1-phase.600 27.0 12.9 Drain VP25 (External Dia.5 5.400 19.5/27 31/29/27 32/29.5 16.218/971/741 dB(A) 30/28.900 4.600 17.089 0.600 kW 3.5 m.600 12. Level difference: 0 m.2 2. During actual operation.) • Sound level: (FXZQ-M) Anechoic chamber conversion value.300 15.800 Btu/h 10.033 0. 220-240 V/220 V. Level difference: 0 m.: 20°CDB.7 Ceiling Mounted Cassette (Round Flow) Type FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1 MODEL Power supply Cooling capacity Heating capacity Power consumption kcal/h 2.5 m downward from the unit centre.400 6. 25) Fresh white Colour Weight 25 BYCP125K-W1 Model Dimensions(H×W×D) 288X840X840 22 6.300 7.900 8.800 6.187 0.0 10.200 2.5/0. 50/60 Hz Cooling capacity kcal/h 2.5Y9.000 Btu/h 9.0 10.: 27°CDB.194 0.5/16 31/26/21 cfm 794/688/565 1.5 Heating capacity Power consumption Cooling kW 0.100 7.100 3.400 3.0 11.5 Liquid (Flare) Piping Gas (Flare) connections Drain 47/44/40 198×950×950 mm mm 15.041 0.: 35°CDB.1 9.6 4. measured at a point 1.200 47.5/15.180 0.900 4. Actual capacity of indoor unit is based on the total capacity index. 32/Internal Dia. 36 .2 4.5 23.5 m downward from the unit centre.100 3.500 27.300 5.700 9.047 0. these values are normally somewhat higher as a result of ambient conditions. measured at a point 1.0 34.900 4. During actual operation.075 0.209 Heating kW 0.5/21.: 27°CDB.0 33.500 27.5 21/18/15 32/26/20 33/28/22.5/31 43/37.027 0. 19°CWB.093 0.0 5. Level difference: 0 m.5/10 13/11.0 11.0 5.6 4.0/11.600 Btu/h 8.800 13.400 4. 32/Internal Dia.700 42.095 0.199 0.0 14.5/27 34/31/28 36/33.075 0.100 21.0 12.0 kcal/h 2.300 5.100 21.200 Heating kW 0.900 13.300 15.9 12.5 23.: 35°CDB.100 3.5 16. Equivalent piping length: 7.094/918/741 dB(A) 40/38/36 kg 27 26 9.400 4.600 17.068 0.700 38.2 14. 50 Hz 0.7 6.0 22.600 12.800 kW 2.064 Galvanised steel plate Casing m3/min 12.5 15.4 Liquid (Flare) Piping Gas (Flare) connections Drain Panel (Option) VP20 (External Dia.5/27 30/28.0 kW 2. 26/Internal Dia.031 0.300 15.027 0.: 7°CDB.5 12.165/918/671 1. 6°CDB.400 Btu/h 10.052 0.0 Sound level (HH/H/L) kg 9. 25) Model BYCQ125B-W1 Colour Fresh white Dimensions(H×W×D) Weight mm 50×950×950 kg 5.2 10.100 2.5/13.700 Casing mm 6.6 2.100 24.400 3.080 0.073 Heating capacity dB(A) 30/28.2 4.5/19.500 9.5/18.5/11. (See Engineering Data Book for details. Outdoor temp.500 10. 19°CWB.219 0.5 3.5/7.700 kW 9.0 6.700 54. Level difference: 0 m.100 42.027 0. 20) • Cooling: Indoor temp.4 mm Drain Panel (Option) 246X840X840 19.900 2.5 5.0/19. 0 6.0 6.7 70X1.7 15.067 0.4 cfm kg Galvanised steel plate Airflow rate (H/L) m3/min Liquid (Flare) 53×1.430×680 53×1. 6.3 8.6 9.160 47.0 0.400 4.5 m. Outdoor temp. (See Engineering Data Book for details.200 12.097 0.070 0.300 34.5 5.300 5.0 5.0 10.0/7.6 4.300 32/27 2.0 6.665×600 305×1. Outdoor temp.400 19.4 6. 19°CWB.0/7.8 2.5/11.240X800 33/30/27 2.600 12.100×450 200×700×450 200×900×450 kg 17 20 mm 40-20 35/33/31 mm Liquid (Flare) Piping connections Gas (Flare) Drain 30-10 Pa 23 6.6 4.5 9.7 kg 44-15 kcal/h 12. (FXKQ-MA) Anechoic chamber conversion value.9 Machine weight BYBC63G-W1 BYBC50G-W1 8.4 282/254/226 Note: Specifications are based on the following conditions. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).1 kcal/h mm 6.100 21.8 3.0 m.0 8.2 4. (Factorysetting is 10 Pa for FXDQ20-32SP models and 20 Pa for FXDQ40-63SP models.100 Btu/h 9.100 mm width type 44/38 305×775×600 305×775×600 305×775×600 305×990×600 305×990×600 305×1.0 6.5/13.030×680 53×1.200 9.0 10. 50/60 Hz kcal/h 2.800 Sound level (HH/H/L) 70X1.7 12.5) MODEL kW 26.0 27.5 9.300 5.900 Btu/h 10.5 8.240X800 70X1.0/7.5 9.056 0.400 6.100 24.059 0.400 10.2/6.5/14.5/8.400 4.000 3.072 0.062 0.0 5.600 5.0 13.2 0.500 0.056 0. 20) Note: Specifications are based on the following conditions.0 8.168 Heating capacity Power consumption 1 kcal/h 2.5 9.070 0. 26/Internal Dia.180 0.100 4.030×680 53×1.110X710 215X1. Equivalent piping length: 7.6 7.0 2. •Capacity of indoor unit is only for reference.4 31.0/8. Outdoor temp.152 0.4 6.7 12.066 0. 50/60 Hz kcal/h 15. •Cooling: Indoor temp.900 2.665×600 Model Dimensions(H×W×D) Heating capacity 54. Equivalent piping length: 5. During actual operation. 25) mm Power consumption (FXDQ-PBVE) 1 26. Equivalent piping length: 7.400 4.0 Colour Weight 900/1.077 Dimensions (H×W×D) 3. FXDQ-NB: external static pressure of 15 Pa.400 3. Outdoor temp.0 5. measured at a point 1. 19°CWB. FXDQ40-63SP: external static pressure of 20 Pa.100 Btu/h 4.5 12/9 12/9 16.300 15.256 Heating kW 0.: 7°CDB.5 m.0 BYBC32G-W1 kg Cooling 26.100 12. Level difference: 0 m.2 Casing Panel (Option) 21.240 V/220 V.2/6.300 6.7 12.400 3.030×680 53×1. 38 .092 0.6 7. 220-240 V/220 V.100 3. Equivalent piping length: 7.5 m downward from the unit centre.4 282/254/226 Slim Ceiling Mounted Duct Type (Compact Series) 6.0 FXKQ63MAVE 1-phase.600 17. 19℃WB.: 27°CDB.5 30/28/26 200×700×620 200×700×620 200×700×620 200×900×620 200×900×620 200×1.5 33/31/29 2.0 9.) •Sound level: (FXCQ-M) Anechoic chamber conversion value.: 35°CDB.600 17.110X710 215X1.240X800 28/26/24 583/512/459 2 kW 12.5 12.700 2. •Heating: Indoor temp.0 Cooling kW 0.: 7℃DB.086 32.4 BYK45FJW1 White (10Y9/0.7 15. 1 : Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa.300 24.0 28.0 6.8 3.500 27.152 0.100 1.130 0.900 4.800 kW 2.180 0.0 m.300 15.5 7.7 12.8 Casing Galvanised steel plate Airflow rate (HH/H/L) 1 3 Dimensions (H×W×D) 8. 6°CWB.168 Galvanised steel plate Casing Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) 1 3 48.2 4.085 m /min cfm Sound level (H/L) 220 V Dimensions (H×W×D) Machine weight 27.196 Heating kW 0.076 0.100 Btu/h 7. 6°CDB.200 kW 2.) •Sound level: Anechoic chamber conversion value.5 12.5 20.0/16.126 0.0 White (10Y9/0.300 Piping connections Gas (Flare) Drain 11/9 11/9 13/10 18/15 388/318 388/318 459/353 635/530 dB(A) mm 38/33 38/33 40/34 42/37 215X1. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).900 6.0/10.5 9/6.200 2.0 23. This pressure means "High static pressure .0/8. Level difference: 0 m.800 6.067 0.161 0. Actual capacity of indoor unit is based on the total capacity index.200 2.: 20°CDB.600 13.500 10.500 27.800 3. •Cooling: Indoor temp.147 0.067 0.800 Btu/h 8.4 6.0/12.600 dB(A) Cooling capacity 1.067 0.147 0.4 6.1 14.500 10.176 0.059 0. (See Engineering Data Book for details. This pressure means “High static pressure .5) 8.4 Model 8.0 12.152 0.0 VP25 (External Dia.6/6.078 0. 50/60 Hz Cooling capacity 47.070 0. Level difference: 0 m. 2 : External static pressure is changeable to set by the remote controller. •Cooling: Indoor temp.400 Btu/h kW Sound level (H/L) FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE 12.165/883 mm 34/28 34/29 34/29 37/32 39/34 Power consumption 0.: 20℃DB.4 6.046 0. During actual operation.046 0.059 0.9 VP20 (External Dia.4 6.075 0.9 15.6 2. (See Engineering Data Book for details. measured at a point 1 m in front of the unit and 1 m downward.0 kcal/h 2. 23. Equivalent piping length: 5. Outdoor temp.0 16.175×600 305×1.5 3.2 15.245×680 53×1.400 4. During actual operation. Level difference: 0 m.4 Colour 8.2/6.209 0.0 15. these values are normally somewhat higher as a result of ambient conditions.086 31.168 Power consumption (FXDQ-PBVET) 1 Cooling kW 0.5 m.) 3 : The values of operation sound level represent those for rear-suction operation.0 5.900 3.900 7.3 8.800 kcal/h Btu/h Heating capacity with drain pump Power supply FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE MODEL Power consumption MODEL Machine weight m3/min 8. 20) FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 1.2 2.900 13.400 24.0 8.900 Btu/h 8.100 21.5 5.800 Liquid (Flare) 19. these values are normally somewhat higher as a result of ambient conditions.7 12.1 3.0 Power supply Heating capacity 0.200 3.5 Machine weight 4.: 27°CDB.5 m downward from the unit centre.700 2.100 27. 220-240 V.7 mm 441/388/353 1-phase.4 6.223 Galvanised steel plate m3/min 7/5 9/6.5 m. 6℃WB.900 7.4 6. •Capacity of indoor unit is only for reference.110X710 215X1. •Heating: Indoor temp.400 6.067 0.600 12.900 FXDQ25PBVE 6.0/7.) •Sound level: Anechoic chamber conversion value.152 0.5 cfm 307/268/229 318/282/247 353/318/282 530/459/371 706/565/441 dB(A) 2 33/31/29 50-20 34/32/30 2 2 37/35/33 200×1.500 kW 220 V 1-phase. 2 : External static pressure is changeable to set by the remote controller.) 3 : The values of operation sound level represent those for rear-suction operation.5 12.100×620 2.600 17.165 0.168 Heating kW 0.100 3.3 8.0 23.5 FXKQ32MAVE FXKQ40MAVE BYBC125G-W1 12.500 9.092 Piping Gas (Flare) connections Drain 24.300 kW 2.2 4.130 0.100 kW 3.900 8. 26/Internal Dia.920×680 53×1.044 0.1 kcal/h 2.600 3. 1 : Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa.4 9.800 9.Standard".0 16.5 Note: Specifications are based on the following conditions.5 Dimensions (H×W×D) 12.: 20°CDB. (Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models. Outdoor temp.600 17.: 7°CDB. Level difference: 0 m.440X800 8.9 VP20 (External Dia. •Heating: Indoor temp. •Capacity of indoor unit is only for reference.067 0.5/13 26/21 33/25 cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1.181 Heating kW 0.7 12.920×680 FXKQ25MAVE 3 37 0.5 3.Standard”. 220 .5 VP25 (External Dia. Actual capacity of indoor unit is based on the total capacity index. Actual capacity of indoor unit is based on the total capacity index.200 kg 15.900 8.400 6.300 5.310X710 kg 31 31 31 34 Liquid (Flare) mm Piping Gas (Flare) connections Drain Dimensions(H×W×D) Weight 282/254/226 Pa mm Cooling capacity 70X1.0/10.152 0.5 m downward from the unit centre.5/9. Equivalent piping length: 7.7 12.: 35℃DB.5 9.6 4.500 FXDQ20PBVE without drain pump FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET 4. 32/Internal Dia. Level difference: 0 m.0 371/335/300 2 30-10 Power supply 6.0 Casing Panel (Option) 0.9 15.0/9.0 Ceiling Mounted Cassette Corner Type Cooling capacity 0.147 0.: 35°CDB.7 15.400 3. measured at a point 1.300 kW 2.9 8.900 3. measured at a point 1. 50 Hz External static pressure BYK71FJW1 mm MODEL 9.5 12.7/7.097 0.900 13. these values are normally somewhat higher as a result of ambient conditions.4 9.0/13.100 30.100 kW 34/28 3.7 12.089 35.066 0.245×680 53×1. 220-240 V/220 V. 32/Internal Dia.0 8.500 19.0 Cooling kW 0.800 3.900 13.100 Cooling Airflow rate (HH/M/L) 700 mm width type FXDQ32PBVE 7. 25) 28/26/23 dB(A) 10.105 Heating kW 0.400 7.: 27℃DB.Specifications VRV Indoor Units Slim Ceiling Mounted Duct Type (Standard Series) Ceiling Mounted Cassette (Double Flow) Type Power supply 1-phase. 5 9.9 15. measured at a point 1.5 Galvanised steel plate Sound level(H/L) 220 V Machine weight FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE 2 132-221 48/45 48/45 mm 470X1.364 1 0.0 11. (See Engineering Data Book for details.100 6.0 8.300 34.218 1 0.380X1.203 1 Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) Dimensions (H×W×D) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain m3/min cfm Pa dB(A) 9/7.000X700 300X1.5 318/265/230 30-100 (50) 318/265/230 2 30-100 (50) 33/31/29 16/13/11 335/282/247 2 33/31/29 Power consumption 30-100 (50) 565/459/388 2 30-160 (100) 34/32/30 39/37/35 50-200 (100) 300X550X700 300X550X700 300X550X700 300X700X700 300X1.5 m.5 m. 25) kcal/h 3.5 Cooling kW 0.400 Casing 18/16.0 16.4 22. During actual operation.100 9.400X700 1.5/6.294 1 1.465 1 m3/min 58/50 72/62 cfm 2.0 12.449 1 kW 4.100 76.100 kg 137 137 Liquid (Flare) Piping connections Gas (Flare) Drain 2 Pa dB(A) mm 191-270 9.0 kcal/h External static pressure kg 6. 32/Internal Dia.000X700 25 25 25 28 36 mm 6.7 12.2 4. Equivalent piping length: 7.: 35°CDB.800 54.5 2.5 3.160×680 195×1.0 33. Actual capacity of indoor unit is based on the total capacity index.130/953/812 Pa 50-200 (100) dB(A) mm 42/40/38 2 50-200 (100) 2 43/41/39 300X1. 19°CWB.100 470X1.765 2. 6°CDB.000X700 50-200 (100) 39/33/28 2 43/41/39 300X1.800 15.7 12. Outdoor temp. Level difference: 0 m.5/6.0 kcal/h 6. Equivalent piping length: 7.800 13.377/1.3 kW 0.900 13.286 1 0.5/15 mm Power supply Power consumption 9. The standard static pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.0 10.0 Cooling kW 1.6 7.800 Cooling kW 0.400X700 300X1. fourteen (FXMQ50125P) or ten (FXMQ140P) levels of control.6 4.4 6.300 Btu/h 1 Galvanised steel plate Casing kcal/h Heating capacity 1 FXMQ250MAVE 1-phase.500 kW 25.5 9.Specifications VRV Indoor Units Ceiling Mounted Duct Type Ceiling Mounted Duct Type MODEL FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE Power supply 1-phase. Equivalent piping length: 7.6 2.) • Sound level: (FXMQ-MA) Anechoic chamber conversion value.900 2. Level difference: 0 m.400 kW 3.9 15. Actual capacity of indoor unit is based on the total capacity index.5) Casing 2 46/45/43 kg 36 Power consumption 46/39/32 Note: Specifications are based on the following conditions. 2: External static pressure is changeable to change over the connectors inside electrical box. 19°CWB.047/1. Equivalent piping length: 7.700 38. these values are normally somewhat higher as a result of ambient conditions 1: Power consumption values are based on conditions of standard external static pressure.5/20 32/27/23 cfm 688/618/565 883/794/706 1.0 6. 6°CDB.300 42.400 3.000 13. 1: Power consumption values are based on conditions of rated external static pressure.0 28.5/16 25/22. 40 .5/8/7 19.0 5.500 10.7 12. Outdoor temp.5 9.600 Btu/h 12.542/2.182 1 1 0. Level difference: 0 m.0 kcal/h 3.1 11.5 cfm 424/353 618/494 883/688 dB(A) 36/31 39/34 45/37 mm 195×960×680 195×1. 220-240 V/220 V.600 12.135 Heating kW 0.400 Btu/h 8.: 7°CDB.900 8.400X700 36 9.294 1 1. 39 21. 25) MODEL 28.800 3.189 31.: 7°CDB. 50/60 Hz Cooling capacity kcal/h 1.5/14 25/19.5 m downward from the unit centre.4 95.: 20°CDB.069 1 1 0.500 Btu/h 27. • Capacity of indoor unit is only for reference.7 15.100 42.900 10.1 9.) •Sound level: Anechoic chamber conversion value.9 15.800 Btu/h 7. 220-240 V/220 V.5 m downward from the unit centre.7 27. These values indicate the lowest and highest possible static pressures.400×680 kg 24. Outdoor temp.0 6.135 Heating capacity Airflow rate (HH/H/L) External static pressure Sound level (HH/H/L) Dimensions (H×W×D) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Cooling capacity Heating capacity Galvanised steel plate Casing m3/min 19.165/988 1. these values are normally somewhat higher as a result of ambient conditions.200 30.300 5.300 24.284 1 0.100 7.300 15.600 27. thirteen (FXMQ40P).200 47.5 m.4 2 41/39/37 6.600 10.800 Btu/h 24.5/17.151 0.2 14.500 Dimensions (H×W×D) VP25 (External Dia.100 kW kcal/h Heating capacity Power consumption Cooling Heating 2.: 20°CDB.0 18. • Heating: Indoor temp. During actual operation.111 0.1 22.900 4. 26/Internal Dia.8 3.2 kW 8.069 1 0. • Cooling: Indoor temp.4 9.400 19. measured at a point 1 m in front of the unit and 1 m downward.200 White (10Y9/0.5 12.0 12.9 Liquid (Flare) Piping connections Gas (Flare) Drain mm VP20 (External Dia.2 PS1B Ceiling Suspended Type 1-phase.4 6.: 35°CDB.128 0.100 Btu/h 85.9 15.115 0. 220-240 V/220 V. Outdoor temp.377/1.138 1 0.056 0.100 3.300 107.600 17. Level difference: 0 m. 20) • Cooling: Indoor temp.5 9.200 FXMQ200MAVE MODEL Power supply Airflow rate (H/L) Sound level (H/L) Dimensions (H×W×D) Machine weight m3/min 12/10 17. • Heating: Indoor temp.056 kW 0.9 15.600 12. 50/60 Hz Cooling capacity kcal/h 6. this pressure means "Standard-High static pressure".700 54. (See Engineering Data Book for details.5 m.400 6.185 1 0. 220-240 V/220 V.500 9. 2: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P). •Capacity of indoor unit is only for reference.2 2.: 27°CDB.7 12.100 21.449 1 0.600 FXHQ32MAVE MODEL FXHQ63MAVE FXHQ100MAVE 1-phase.060 1 0.500 kW 2.130 50-200 (100) 44/42/40 2 50-140 (100) 300X1.400 4.5 9. 32/Internal Dia. (FXHQ-MA) Anechoic chamber conversion value.700 9.405 1 Btu/h 13.9 46 46 47 VP25 (External Dia.115 0.5 9.624/1.073 1 0.500 kW Airflow rate (H/L) 635/582/530 2 24.465 1 Heating kW 1.215 1 0. 50/60 Hz Cooling capacity 5. measured at a point 1.380X1.700 Heating kW 0.5 9/7.5 mm 15.5 19.200 38.5 16.4 12. 50/60 Hz Power supply kW 7.: 27°CDB.111 0.600 61. 4 6.5 m.8 3.670×1.070×220 610×1.400 19. Actual capacity of indoor unit is based on the total capacity index.033 0.0 25.500 9.100 Btu/h 7.300 24.800 6.4 6.100 21.400 4.050×238 11.5/1) Casing colour 15/12 530/424 19/14 671/494 35/31 36/31 38/31 39/34 42/37 47/41 290×795×238 290×795×238 290×795×238 290×1.020 0.100 7.9 Dimensions (H×W×D) mm 1.500 27. 50 Hz kcal/h 3.900 13.61 4.200 2.300 Btu/h 8. Level difference: 0 m.7 12. 220-240 V/220 V.0 25. Equivalent piping length: 7. FCQ50BVE FCQ35BVE MODEL Power supply FCQ71BVE m3/min (cfm) dB (A) 14.049 0.0 6. 6°CDB. Outdoor temp.800 6. • Capacity of indoor unit is only for reference.500 10.300 5.5 0.75 1.4 6.6 4. 19°CWB. During actual operation. 18/Internal Dia.7 15.400 6.6 4.200 kW 2.0 6.0 27.0 23.5 m.900 2.5 Belt drive system Drive system Floor Standing Type/Concealed Floor Standing Type 22.436 3.600 85.2 2.030 0.900 4.800 3.5 m.110 0. • Heating: Indoor temp.0 19.100 3.4 6.9 BYC125K-W1 Colour Weight 9. •Capacity of indoor unit is only for reference.0 22.8 3.049 0.300 Btu/h 54.500 7.670×950×510 1. of 27°CDB.1 kcal/h 2.7 12.5 12.: 7°CDB.4 9.000×222 600×1.300 107.53 1. 19°CWB.33 1.020 0. 13) MODEL FXVQ250NY1 Btu/h 3.5/4.5 14/11 16/12 cfm 247/212 247/212 282/212 388/300 494/388 565/424 35/32 35/32 35/32 38/33 39/34 40/35 dB(A) mm 610×930×220 610×930×220 610×1.4 6. 50/60 Hz Cooling capacity Power consumption 1.600 kW 2.170×510 kg 118 144 169 dB(A) 52 56 60 Machine weight Sound level *1 Liquid mm Piping connections Gas Drain mm Long-life filter (anti-mould resin net) 0.019 0.028 Heating kW 0. Residential indoor units with connection to BP units FXLQ: Ivory white (5Y7. •Heating: Indoor temp. 50/60 Hz Notes: Specifications are based on the following conditions.7 12.039 0. Equivalent piping length: 7.5 265/159 8/5 282/177 8.0 30. *2 The value is the external static pressure with standard pulley. (See Engineering Data Book for details.2 2.090 0. 50/60 Hz White mm 40X950X950 kg 5 Note: * For 220 V operation.5 12.200 2.2 (Brazing) 19.7 12.600 12.0 14. these values are normally somewhat higher as a result of ambient conditions.800 3.7 15.900 FXVQ125NY1 MODEL Power supply 1-phase.3 8.600 17.420×222 600×1.4 mm 9.5 (Brazing) Type Air filter VP13 (External Dia.7 12. 220-240 V/220 V. • Cooling: Indoor temp. (See Engineering Data Book for details. measured at a point 1 m in front of the unit and 1 m downward.7 12.5 I. (FXLQ-MA.900 Btu/h 8.5 3. and outdoor temp.) *1 Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).: 7°CDB.5 m in front of the unit at a height of 1. 220 -240 V/220 V.9 21O.900 13.300 15. It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.5 300/194 12/9 424/318 Cooling capacity Heating capacity Power consumption Ivory white (5Y7. of 35°CDB.0 31.350×220 kg Liquid (Flare) Piping connections Gas (Flare) Drain 600×1.2 4.420×222 mm Ceiling Mounted Cassette Type Airflow rates (H) Sound levels (H/L)* 25.2 4.050×238 290×1.500 5.100 24. Level difference: 0 m.5 m.5 5.0 (494) 15.Specifications VRV Indoor Units Wall Mounted Type Floor Standing Duct Type MODEL FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE Power supply kcal/h Cooling capacity 2.5 5.350×220 610×1.800 76.070×220 610×1.400 12.0 5.518 2.0 Temperature control 6.400 95.5 3. •Cooling : Indoor temp.5 12.140×222 600×1.400 19.800 21. measured at a point 1.100 21.1 kW 14.7 12.0 11.) • Sound level: (FXAQ-P) Anechoic chamber conversion value.7 12.1 (Brazing) Rp1 (PS 1B internal thread) kW Motor output Airflow rate FXLQ 15.0 5. 380–415 V.400 3.000×222 600×1.0 (671) 33/29 35/30 2 steps Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Microcomputer control mm 6. 41 42 .61 0.090 0.0 6.0 30.53 1.4 9. Outdoor temp.6 kcal/h 2. 6°CDB.100 Btu/h Heating capacity Power consumption 1. Outdoor temp.000 19.400 4.D ø25XO.300 15.0 Cooling kW 0.0 11.090 0.500 27.: 35°CDB.0 kW 16.110 Heating capacity FXNQ kcal/h 1.D.060 Heating kW 0.049 0.0 14.0 23.4 6. Actual capacity of indoor unit is based on the total capacity index. FXNQ-MA) Anechoic chamber conversion value.4 28. Level difference: 0 m.0 36.7 15.670×750×510 1.034 White (3.140×222 600×1.035 0.090 0.500 27.300 kW 2.5/5.0 27.110 Heating kW 0.500 9.4 6.110 0.0 Cooling kW 0.0 (530) 19.900 kcal/h 13.100 17.: 20°CDB.5/0.900 kW Casing FXVQ200NY1 3-phase 4-wire system.600 12.4 6.050 Cooling kW 0.5 m3/min 43 69 86 cfm 1.029 0.0Y8.400 6.0 Fan speed 19.3 8.5) m3/min Airflow rate (H/L) cfm dB(A) Sound level (H/L) Dimensions (H×W×D) mm kg Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain mm 7.: 20°CDB.036 Pa 152 217 281 External static pressure *2 FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE 1-phase.200 2.5/1)/FXNQ: Galvanised steel plate Casing Airflow rate (H/L) Sound level (H/L) 220 V FXLQ Dimensions (H×W×D) FXNQ Machine weight FXLQ FXNQ m3/min 7/6 7/6 8/6 11/8.050×238 290×1.9 (Brazing) mm Fan Power supply 9.100 24.D ø32 Both liquid and gas pipes Model Dimensions (HXWXD) 230X840X840 24 kg Heat insulation Panel (Option) FCQ60BVE 1-phase.0 36.6 7.33 1.100 47. Equivalent piping length: 7.049 0.500 10.: 27°CDB.0 14. 1 kW class residential indoor units Connectable indoor units Min.0 (600) 19. rated capacity of connectable indoor units kW 2.9 (314) 14.4 (438) Cooling 38/25/21 45/26/22 46/35/32 41/28/21 45/29/22 47/35/32 m 3/min( cfm) dB (A) Heating 5 steps.7 55X1.000X800 mm kg Sound levels (H/L/SL) Cooling Heating Heating m3/min (cfm) dB (A) 8.5 3 for power supply (including earth wiring). Wall Mounted Type Ceiling Mounted Built-in Type FTXS20DVMA FTXS25EVMA FTXS35EVMA FTXS50FVMA FTXS60FVMA FTXS71FVMA MODEL MODEL FBQ60BV1 Power supply Airflow rates (H) Sound levels (H/L)* FBQ71BV1 17.5 12. 50 Hz m3/min (cfm) 1-phase.4 mm 9.0 (565) 37/33/31 38/34/32 Temperature control Dimensions (HXWXD) mm 200X700X620 kg 21 200X900X620 25 Liquid (Flare) Piping Gas (Flare) connections Drain 200X1. 20) Both liquid and gas pipes Heat insulation External static pressure 27 6.4 Liquid (Flare) Piping connections Gas (Flare) Drain 1-phase.0 (670) dB (A) 41/35 Fan speed 2 steps Temperature control Dimensions (HXWXD) Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain Microcomputer control 300X1. quiet and automatic Microcomputer control Temperature control 12.5 (335) 8.2 Note: * Total auxiliary piping length.9 Machine weight Liquid (Flare) Piping connections Gas (Flare) Drain I.5 Dimensions (HXWXD) 15.8 14.0 (353) 12. measured according to JIS parameters and criteria.7 Dimensions (HXWXD) VP20 (External Dia. 26/Internal Dia.100X620 30 12.3 (293) 10. rated capacity of connectable indoor units kW Max.1X1 15. 220 -240 V.5 12.D ø25XO. 50/60 Hz Power supply m3/min (cfm) mm kg CTXG25PVMAW CTXG25PVMAS CTXG35PVMAW CTXG35PVMAS CTXG50PVMAW CTXG50PVMAS MODEL FFQ60BV1B 2 steps Microcomputer control Temperature control Dimensions (HXWXD) Panel (Option) FFQ50BV1B 1-phase.9X2 Both liquid and gas pipes 2. 50/60 Hz Power supply BYBS71DJW1 mm 283X800X195 kg 9 12 6.5X1 6.7 (307) 8.4 (332) 9.5 15.5 kW class to 7.9 (420) 12.6 (374) 10. 220-240 V/220-230 V. quiet and automatic Machine weight BPMKS967A3 Power supply Main mm Branch mm Main mm Branch mm 8 7.5 mm White Front panel colour 6.4X2 19. 220 -240 V/220-230 V.4 9.100X500 kg 4.0 (424) 5 steps.5 (759) 37/25/22 39/26/23 43/34/31 45/36/33 46/37/34 37/28/25 38/29/26 42/33/30 44/35/32 46/37/34 5 steps.7 (519) 16.D ø32 Both liquid and gas pipes Model Weight Cooling 12.4 mm Pa 30 Number of ports 3 (connectable to 1-3 indoor units) Power consumption Dimensions (HXWXD) Machine weight 40 Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for CDXS-EA and 40 Pa for FDXS-C. 50/60 Hz Running current 12. 43 44 .5 Model BYFQ60B8W1 Colour White Dimensions (HXWXD) Weight Cooling Sound level (H/L/SL) White mm 55X700X700 kg 2.0 (318) 10. 50/60 Hz Power supply Airflow rates (H) Sound levels (H/L/SL)* m3/min (cfm) 9.0 Heat insulation White mm 290X1.7 (307) dB (A) 10.240 V/220-230 V. 220 -240 V.2 (572) 17. quiet and automatic Microcomputer control Temperature control 6. 2 for interunit wiring (outdoor unit-BP. 50 Hz Machine weight mm 303x998x212 kg 12 Liquid (Flare) Piping connections Gas (Flare) Drain 6. During operation these values are somewhat higher owing to ambient conditions.5/24.2 (572) 17.4X3 6.5 20.0 (353) 35/31/29 Fan speed 16.5 VP20 (External Dia.0 (530) dB (A) 29.9X3 Heat insulation 15.5 32/25 36/27 41/32 286X575X575 17.0 Heat insulation Both liquid and gas pipes Note: * Anechoic chamber conversion value.Specifications Residential indoor units with connection to BP units Wall Mounted Type Ceiling Mounted Cassette (Compact Multi Flow) Type MODEL 600 x 600 FFQ25BV1B FFQ35BV1B Power supply Airflow rates (H) Sound levels (H/L)* Fan speed Machine weight 9.0 (424) 15.4 mm 9.7 18. 220 . 20) Both liquid and gas pipes Heat insulation Airflow rate (H) Silver Fan speed 9.7 Heat insulation Colour Panel (Option) Dimensions (HXWXD) Airflow rates (H) Fan speed 41 mm White Front panel colour 1-phase. Piping connections (Brazing) Liquid Gas 2 (connectable to 1-2 indoor units) W 10 A 0. 220 -240 V/220-230 V.7 Silver White Silver 8. BP-BP).4 (367) 11.7 (342) 16. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for CDXS-EA and 5 dB (A) for FDXS-C.4 (614) 9.05 180X294 (+356*)X350 mm kg Number of wiring connections Microcomputer control BPMKS967A2 1-phase.7 9.8 (381) Heating 10.9 18. 4 for interunit wiring (BP-indoor unit) 9.050X238 Both liquid and gas pipes Note: * For 220 V operation. 26/Internal Dia.4 (614) 21. BP Units for connection to residential indoor units MODEL Slim Ceiling Mounted Duct Type MODEL CDXS25EAVMA CDXS35EAVMA FDXS25CVMA FDXS35CVMA FDXS50CVMA FDXS60CVMA 1-phase. 300 88.9 (Flare) 19.93 4.0 16.345×900×320 1.700 kW 12.800 19.9 3.0 3. measured at a point 1 m in front of the unit at a height of 1.5 (Brazing) mm Piping connections Gas 15.0 26.5 100 125 150 200 215 130% 130 162.4 24.04 4.000 15.700 47. Outdoor temp. Level difference: 0 m.5 m.4 2.0 kcal/h 10.5 14.5 m.800 61.5 m.1 (Flare) 19.5/1) Casing colour Hermetically sealed swing type Type Hermetically sealed scroll type Compressor Motor output kW 1.14 5.230 V/220 V.25 6.8 9.1 (Brazing) 22. • Refrigerant charge is required.6 9.400 Btu/h 42.2 14.600 12.0 22. • Sound level: Anechoic chamber conversion value. Equivalent piping length: 7. Equivalent piping length: 7. During actual operation.430×940×320 138 kg 82 104 Sound level (Cooling/Heating) dB(A) 52/54 53/54 55/56 Cooling °CDB Operation range 4.5 106 140 990×940×320 1.500 21.800 54.5 (Flare) Liquid 5.5 195 260 280 6 8 9 13 14 Maximum number of connectable indoor units 20 to 100 Ivory white (5Y7.300 20.88 3.0 2. • Cooling: Indoor temp.0 22.60 3.92 3 m /min Airflow rate Dimensions (H×W×D) mm 3. 220. Outdoor temp.0 4 5 6 8 9 100 125 150 200 215 50% Combination 100% (%) 50 62.: 27°CDB.0 16.800 12.500 22.600 Btu/h 38.: 35°CDB.: 20°CDB. 45 46 .8 76 71 Machine weight 3.07 6. 6°CWB.94 6.900 kW 11.400 81.0 25. these values are normally somewhat higher as a result of ambient conditions.: 7°CDB.000 13.5 75 100 107.82 kW Heating Capacity control RXYMQ9AY1 3-phase. 50/60 Hz Cooling capacity RXYMQ8AY1 % 24 to 100 16 to 100 Total capacity index of connectable indoor units RXYMQ4AVE RXYMQ5AVE RXYMQ6AVE RXYMQ8AY1 RXYMQ9AY1 11. Level difference: 0 m.5 Type R-410A Refrigerant Charge kg 3. 380–415 V.200 47.400 85.8 57/58 58/59 -5 to 46 Heating °CWB -20 to 15.88 2.4 24.Specifications Outdoor Units S SERIES Heat Pump Outdoor unit combinations MODEL kW Class Capacity index RXYMQ4AVE MODEL Power supply RXYMQ5AVE RXYMQ6AVE Heating capacity Power consumption Cooling kcal/h 9.2 (Brazing) Note: Specifications are based on the following conditions.2 14.0 18. 50 Hz 1-phase.600 76. • Heating: Indoor temp. 19°CWB. FXKQ25MA Decoration panel Panel spacer Long life replacement filter Air discharge grille Air discharge blind panel Flexible duct (with shutter) FXZQ40M FXZQ50M No. 47 48 . 1 2 3 1 Type Item No. 1 KDJP55B160 KDTP55K160 Item Type FXDQ20PB Insulation kit for high humidity 4 5 6 7 8 BYCP125K-W1 KDBH55K160F KDBP55H160FA KAFP556B80 KAFP557B80 KAFP552B80 KAFP553B80 KDDFP55B160 KAFP551K160 KAFP55B160 KAFP55H160H KDDP55B160 KDDP55B160K KDDP55X160 KDJP55B80 KKSJ55KA160 KDTP55K80 KAFP556B160 KAFP557B160 KAFP552B160 KAFP553B160 1 2 3 4 5 Type Item FXZQ20M FXZQ25M Decoration panel Sealing material of air discharge outlet Panel spacer Replacement long-life filter Fresh air intake kit Direct installation type FXZQ32M FXDQ32PB FXDQ40NB FXDQ50NB KDT25N50 FXDQ63NB KDT25N63 1 Drain pump kit 2 High efficiency filter 3 4 5 Filter chamber Long life replacement filter Long life filter chamber kit 6 Service panel 7 Air discharge adaptor FXMQ20P FXMQ25P FXMQ32P FXMQ40P KAF372AA36 KAF373AA36 KDDF37AA36 KAF371AA36 KAF375AA36 KTBJ25K36W KTBJ25K36F KTBJ25K36T KDAJ25K36A KAF372AA56 KAF373AA56 KDDF37AA56 KAF371AA56 KAF375AA56 KTB25KA56W KTBJ25K56F KTBJ25K56T KDAJ25K56A FXMQ50P FXMQ63P FXMQ80P FXMQ100P FXMQ125P FXMQ140P FXMQ200MA FXMQ250MA — 65% 90% White Fresh white Brown KAF372AA80 KAF373AA80 KDDF37AA80 KAF371AA80 KAF375AA80 KTB25KA80W KTBJ25K80F KTBJ25K80T KDAJ25K71A KAF372AA160 KAF373AA160 KDDF37AA160 KAF371AA160 KAF375AA160 KTB25KA160W KTBJ25K160F KTBJ25K160T KDAJ25K140A KDU30L250VE KAFJ372L280 KAFJ373L280 KDJ3705L280 KAFJ371L280 — Ceiling Suspended Type KDJP55B160 KDTP55K160 Ceiling Mounted Cassette (Compact Multi Flow) Type No. Decoration panel Sealing material of air discharge outlet Panel spacer High efficiency filter unit 65% High efficiency filter unit 90% Replacement high efficiency filter 65% Replacement high efficiency filter 90% Filter related Filter chamber Long life replacement filter Ultra long-life filter Replacement ultra long-life filter Without T joint-pipe and fan Chamber type Fresh air intake kit With T joint-pipe without fan Direct installation type Branch duct chamber Chamber connection kit Insulation kit for high humidity FXKQ40MA BYK45FJW1 KPBJ52F56W KAFJ521F56 K-HV7AW KDBJ52F56W KFDJ52FA56 Item 1 2 3 FXKQ32MA Slim Ceiling Mounted Duct Type (Standard Series) Ceiling Mounted Cassette (Round Flow) Type No. FXDQ25PB Ceiling Mounted Duct Type Type Type FXFQ25LU FXFQ32LU FXFQ40LU FXFQ50LU FXFQ63LU FXFQ80LU FXFQ100LU FXFQ125LU Item FXKQ63MA BYK71FJW1 KPBJ52F80W KAFJ521F80 K-HV9AW KDBJ52F80W KFDJ52FA80 KDT25N32 No. Item Long life replacement filter FXCQ50M BYBC50G-W1 KAFJ532G56 KAFJ533G56 KDDFJ53G56 KAFJ531G56 FXCQ63M BYBC63G-W1 KAFJ532G80 KAFJ533G80 KDDFJ53G80 KAFJ531G80 FXCQ80M Item Long life replacement filter Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA KAFJ361K28 KAFJ361K45 KAFJ361K71 FXCQ125M BYBC125G-W1 KAFJ532G160 KAFJ533G160 KDDFJ53G160 KAFJ531G160 Note: 1 Filter chamber is required if installing high efficiency filter. FXUQ71A KDBHP49B140 KDBTP49B140 KAFP551K160 No. BYFQ60B3W1 KDBH44BA60 KDBQ44BA60A KAFQ441BA60 KDDQ44XA60 Item Drain pump kit Replacement long-life filter (Resin net) L-type piping kit (for upward direction) 1 Item Type FXAQ20P FXAQ25P Drain pump kit FXAQ32P FXAQ40P FXAQ50P FXAQ63P FXLQ50MA FXLQ63MA K-KDU572EVE Floor Standing Type 4-way Flow Ceiling Suspended Type No. Type Item 1 Panel related 2 Air inlet and air discharge outlet related No. 1 2 3 4 5 6 7 Ceiling Mounted Cassette Corner Type Type FXFQ25S FXFQ32S FXFQ40S FXFQ50S FXFQ63S FXFQ80S FXFQ100S FXFQ125S Item Decoration panel Sealing material of air discharge outlet Panel spacer High efficiency filter unit 65% High efficiency filter unit 90% Replacement high efficiency filter 65% Replacement high efficiency filter 90% Filter related Filter chamber Long life replacement filter Ultra long-life filter Replacement ultra long-life filter Without T joint-pipe and fan Chamber type Fresh air intake kit With T joint-pipe without fan Direct installation type Branch duct chamber Insulation kit for high humidity BYCQ125B-W1 KDBHQ55B140 KDBP55H160FA KAFP556B80 KAFP557B80 KAFP552B80 KAFP553B80 KDDFP55B160 KAFP551K160 KAFP55B160 KAFP55H160H KDDQ55B140 KDDP55B160K KDDP55X160 KDJP55B80 KDTP55K80 KAFP556B160 KAFP557B160 KAFP552B160 KAFP553B160 No.Option List VRV Indoor Units Ceiling Mounted Cassette (Round Flow with Sensing) Type No. Item 1 2 Decoration panel Filter related High efficiency filter 65% 1 High efficiency filter 90% 1 Filter chamber bottom suction Long life replacement filter FXCQ20M FXCQ25M FXCQ32M BYBC32G-W1 KAFJ532G36 KAFJ533G36 KDDFJ53G36 KAFJ531G36 1 FXCQ40M FXLQ25MA KAFJ361K28 FXLQ32MA FXLQ40MA KAFJ361K45 KAFJ361K71 Concealed Floor Standing Type Ceiling Mounted Cassette (Double Flow) Type Type Type FXLQ20MA FXUQ100A Sealing material of air discharge outlet Decoration panel for air discharge Replacement long-life filter No. 1 2 3 Type FXHQ32MA KDU50N60VE KAF501DA56 KHFP5MA63 FXHQ63MA FXHQ100MA KDU50N125VE KAF501DA80 KAF501DA112 KHFP5MA160 Wall Mounted Type No. 1 Item Type CDXS25EAVMA CDXS35EAVMA FDXS25CVMA Insulation kit for high humidity KDT25N32 FDXS35CVMA FDXS50CVMA KDT25N50 FDXS60CVMA KDT25N63 Wall Mounted Type Residential Indoor Units with connection to BP units No. 2 Plenum chamber *4 Pulley for plenum chamber *4 Fresh air intake kit Rear suction kit Discharge grille for plenum side Wood base Vibration isolating frame KAFJ261L140 KAFJ261L224 – KD-9A200 KDGF-9A200 KAF-91A200 KAF-92A200 KAF-93A200 KDDF-9A200 KPC5J KPP9JA KD106D10 KDFJ905A200 KD101A10 KWF1G5P K-ABSG1407A KAFJ261L280 3 Item Discharge and Suction 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 KD-9A140 KDGF-9A140 KAF-91A140 KAF-92A140 KAF-93A140 KDDF-9A140 KPCJ140A KPP8JA KDFJ905A140 KKWJ9A140 K-ABSG1406A KD-9A280 KDGF-9A280 KAF-91A280 KAF-92A280 KAF-93A280 KDDF-9A280 KPC8J KPP10JA 4 5 6 7 8 9 10 KDFJ905A280 11 KWF1G8P K-ABSG1408A 12 13 14 Item Decoration panel Service access panel High-efficiency filter Type (Colourimetric method 65%) (Colourimetric method 90%) Replacement long-life filter Resin net Filter chamber for bottom suction Filter chamber for rear suction Canvas duct ø150 Discharge grille ø200 ø150 Discharge chamber ø200 Branch duct ø150 ø200 ø150 Flexible duct ø200 Blind board Adaptor for discharge Flange for suction FBQ60BV1 FBQ71BV1 BYBS71DJW1 KTB25KA80W KAF252LA80 KAF253LA80 KAFJ251K80 KAJ25LA80D KAJ25LA80B KSA-25KA80 K-DG5DW K-DG9DW K-DGC5D K-DGC9D K-DDV20B15 K-FDS151D(1m)/K-FDS152D(2m)/K-FDS153D(3m)/K-FDS154D(4m)/K-FDS155D(5m)/K-FDS156D(6m) K-FDS201D(1m)/K-FDS202D(2m)/K-FDS203D(3m)/K-FDS204D(4m)/K-FDS205D(5m)/K-FDS206D(6m) KBBJ25KA80 KDAJ25K71A KDJ2507K80 *1 When ordering a filter chamber for high efficiency filter (65%). Item 1 Type CTXG25PVMAW CTXG35PVMAW CTXG50PVMAW CTXG25PVMAS CTXG35PVMAS CTXG50PVMAS FTXS20DVMA FTXS25EVMA FTXS35EVMA KAF970A46 Titanium apatite photocatalytic air-purifying filter FTXS50FVMA FTXS60FVMA FTXS71FVMA KAF952B42 Note: Filter is a standard accessory. KHRP26A33T KKPJ5G280 KKPJ5F180 KKPJ5G280 KKTP5B112 KPT-60B160 KKTP5B112 — K-KYZP15C 50 . It should be replaced approximately 3 years. and 3 BP units require only 2 REFNET joints. Fresh air intake is directly from a hole on the main unit. 3 for high Replacement high 65% *1. Fresh air intake is from 2 holes on the sides of the connection chamber. Item 1 1-1 Cool/Heat selector Fixing box 2 REFNET header 3 4 5 6 REFNET joint Central drain plug Fixture for preventing overturning Wire fixture for preventing overturning Type RXYMQ4AVE RXYMQ5AVE RXYMQ6AVE RXYMQ8AY1 RXYMQ9AY1 KRC19-26A — KJB111A — KHRP26M22H (Max. 4 branch) KHRP26M33H (Max. Without a suction chamber. 1 BPMKS967A2 BPMKS967A3 KHRP26A22T *1. *2 When ordering a filter chamber for high efficiency filter (90%). please order with all the respective parts. Outdoor Units Ceiling Mounted Cassette (Compact Multi Flow) Type 1 2 3 4 5 Item REFNET joint Item Decoration panel Replacement long-life filter Fresh air intake kit Direct installation type Sealing material for air discharge outlet Panel spacer Type FFQ25BV1B FFQ35BV1B FFQ50BV1B BYFQ60B3W1 KAFQ441BA60 KDDQ44XA60 KDBH44BA60 KDBQ44BA60A FFQ60BV1B No. Without a suction chamber. 1 2 Type FCQ35BVE FCQ50BVE 4 5 6 7 8 FCQ60BVE FCQ71BVE BP Units for connection to residential indoor units BYC125K-W1 KDBP55H160WA KDD55DA160 KDD55DA160K KDDJ55XA160 KAF556DA80 KAF557DA80 KAFP552B80 KAFP553B80 KDDF55DA160 KAF551KA160 KDJ55K80 Chamber Without T-shaped pipe and fan*1 Fresh air intake kit type With T-shaped pipe. 3 filter *1. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. please order the replacement filters with the corresponding filter model name.) *3. Type FXVQ125N FXVQ200N FXVQ250N Replacement long life filter Ultra long-life filter Front suction base flange Front suction Suction grille filter chamber Filter chamber Replacement long-life filter *1. Ceiling Mounted Cassette Type No. 2 BP units require only 1 REFNET joint. please order with all the respective parts. without fan*2 Direct installation type*3 (Colourimetric method 65%) High-efficiency filter (Colourimetric method 90%) Replacement (Colourimetric method 65%) high-efficiency filter (Colourimetric method 90%) High-efficiency filter chamber Replacement long-life filter Branch duct chamber 3 Notes: Item Decoration panel Panel spacer No. 8 branch) KHRP26A22T KHRP26A22T. (This method should be selected if a wireless remote controller is used. Slim Ceiling Mounted Duct Type No. 2. *3 When replacing with a new filter. 3 for high efficiency filter efficiency efficiency filter 90% *2. No. (A wireless remote controller cannot be used in this case. 2 Filter chamber *1. Floor Standing Duct Type No.) *2.Option List VRV Indoor Units Ceiling Mounted Built-in Type No. With a suction chamber. *4 Use the plenum chamber and pulley for plenum chamber in combination. 49 Type Note: A single BP unit does not require a REFNET joint. 6 KRP1B61 KRP2A61 KRP4AA51 BRC4C65 Note 4. 6 — FXMQ-MA FXHQ-MA FXAQ-P BRC4C65 BRC4C62 BRC7EA63W BRC1C62 BRC1E62 Note 7 BRC7EA618 BRC4C62 BRC2C51 BRC3A61 KRP1C64 KRP2A61 KRP4AA51 KRCS01-4B BRC2C51 BRC3A61 KRP1B61 KRP2A61 KRP4AA51 KRP1BA54 KRP2A62 KRP4AA52 — Note 3 Note 1 KRP1CA93 KRP4AA93 DTA104A62 DTA104A61 Remote controller 8 Installation box for adaptor PCB Note 1 9 External control adaptor for outdoor unit DTA104A61 DTA104A61 10 11 12 Adaptor for multi tenant External control adaptor for cooling / heating Remote controller with key DTA114A61 — KRP4A96 — — FXVQ-N — BRC1C62 Note 8 BRC1E62 Note 9 — — KRP1C67 KRP2A62 — BRC2C51 BRC3A61 KRP1B61 KRP2A61 KRP4AA51 — KRP2A61 KRP4AA51 KRCS01-1B — DTA104A53 FXMQ-P 1 Residential central remote controller 2 Central remote controller 3 3-1 3-2 Unified ON/OFF controller Electrical box with earth terminal (2 blocks) Noise filter (for electromagnetic interface use only) 4 Schedule timer 5 5-room centralised For C(F)DXS. 7 No. Type DCS302CA61 • Up to 64 groups of indoor units(128 units) can be connected. 9. and operation and malfunction can be displayed. installed on DMS502B51. A wiring adaptor (KRP413AB1S) is also required for each indoor unit. DCS303A51 Electrical box with earth terminal (3 blocks) Note 10 — — — Model No. 1 2 3 4 5 6-1 6-2 7 Type Item Installation box for adaptor PCB External control adaptor for outdoor unit Adaptor for multi tenant 2 3 4 5 6-1 6-2 7 BRC7E530W FXDQ-PB FXCQ-M FXKQ-MA FXDQ-NB FXDQ-SP BRC7CB58 BRC4C62 BRC1C62 BRC1E62 Note 7 — — KRP1BA57 — — KRP2A62 KRP4AA53 KRP4AA53 KRCS01-1B KRCS01-4B KRP1C63 KRP2A62 KRP4AA53 KRCS01-4B Note 4. 3 9 10 1 FXFQ-LU BRC7F634F Wireless Wired Navigation remote controller (Wired remote controller) Simplified remote controller (Exposed type) Remote controller for hotel use (Concealed type) Adaptor for wiring Wiring adaptor for electrical appendices (1) Wiring adaptor for electrical appendices (2) Remote sensor (for indoor temperature) Remote controller 8 No. 8. 6 Contact/ Unification adaptor for computerised analogue signal control DCS302A52 • Interface between the central monitoring board and central control units.000m. number of branches: 16) apply to each adaptor. 3. Installation box for adaptor must be obtained locally. Individual airflow direction. Refrigerating and Air-Conditioning Engineers (ASHRAE). • Air-Conditioning management system that can be controlled by a compact all-in-one unit. to provide 16 more wattmeter pulse input points. Up to 2 adaptors can be fixed for each installation box. Installation box for adaptor PCB (KRP1BA101) is necessary.F 1 1-1 1-2 2 Item 2-2 Model No.Option List Control Systems Operation Control System Optional Accessories System Configuration No. 7 iTM plus adaptors can be connected to intelligent Touch Manager. 10. Wiring for wired remote controller should be obtained locally. Installation box for adaptor must be obtained locally. Note 3 KRC72A Building Management System — Notes: 1. Only one installation box can be installed for each indoor unit. Operation and monitoring of air-conditioning systems through LonWorks® communication. Installation box is necessary for second adaptor. Installation box for adaptor PCB (KRP1B98) is necessary. Up to 2 installation boxes can be installed for each indoor unit. • Fixing plate for DTA109A51 Note: 1. Remove the group control adaptor which is a standard equipment before mounting KRP6A1 and DTA104A62. • Air-conditioning management system that can be controlled by touch screen. 4. 5. DTA104A62 For residential indoor unit use No. 5 Home Automation Interface Adaptor DTA116A51 • Use of the Modbus protocol enables the connection of the VRV system with a variety of home automation systems from other manufacturers. 3. controller for residential FTXS indoor units 6 Interface adaptor for residential indoor units DTA104A61 Wired type Note 1 Wireless type 1 Remote controller 2 Adaptor for wiring 3 Wiring adaptor for electrical appendices 4 5 Installation box for adaptor PCB Remote sensor (for indoor temperature) 6 Wiring adaptor for time clock/remote controller Note 5 (Normal open pulse contact/normal open contact Remote controller loss prevention chain Interface adaptor for DIII-NET use 7 8 FCQ-B FFQ-B BRC7C612W BRC1C61 BRC7E530W Note 3 Note 4 KRP1BA57 KRP1BA57 Note 3 Note 4 KRP4AA53 KRP4AA53 KRP1B98 — KRP1BA101 KRCS01-1B — DTA114A61 KRP6A1 Note 10 KRCB37-1 CDXS-EA FDXS-C — DTA112BA51 KRP928BB2S • Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System. Cannot be used with other centralised control equipment. Time clock and other devices should be obtained locally. *3.000m. FXFQ-S Type Item Notes: *1. Can turn units ON/OFF twice per day. Note 2 2-1 — KRP1BA101 DTA104A61 DTA104A61 — FXLQ-MA FXNQ-MA Item — — — — — BRC2C51 BRC3A61 KRP1B61 KRP1B56 KRP2A61 KRP2A53 KRP4A54 KRP4AA51 KRCS01-1B KRP1B96 — DTA104A62 BRC4C61 Note 2. Note 4 DTA112BA51 Interface adaptor for SkyAir-series Central control adaptor kit For UAT(Y)-K(A). 51 FBQ-B Item • Up to 5 indoor units can be controlled. 3 KRP1BA97 KRP1BA101 KRP1H98 DTA104A62 DTA114A61 Type Wireless Wired Navigation remote controller (Wired remote controller) Simplified remote controller (Exposed type) Remote controller for hotel use (Concealed type) Adaptor for wiring Wiring adaptor for electrical appendices (1) Wiring adaptor for electrical appendices (2) Remote sensor (for indoor temperature) FXUQ-A FXZQ-M Note 2. • Additional 64 groups (10 outdoor units) is possible. DCM009A51 • BACnet equipment can be managed by intelligent Touch Manager. A wireless remote controller is a standard accessory for C(F)DXS. 5. Since the control panel is equipped as standard. please place it separately. DCM601A51 Hardware iTM plus adaptor DCM601A52 intelligent Touch Manager iTM power proportional distribution Option 2-4 iTM energy navigator BACnet client 2-5 HTTP Interface Software 2-3 KJB411A DCM002A51 • Power consumption of indoor units are calculated based on operation status of the indoor unit and outdoor unit power consumption measured by kWh metre. length: 1. DCM008A51 • Building energy consumption is visualised. Installation box is necessary for each adaptor. total wiring length: 2. — KRP1BA54 — 3-1 KRP4AA51 — 3-2 Note 2 Communication Optional Di board interface 4 *2 Interface for use in LONWORKS® DMS504B51 • Interface unit to allow communications between VRV and BMS. temperature settings and scheduling can be controlled individually for indoor units. Not usable independently. This is a low cost system which can only control ON/OFF. use the option for 2 remote control system. BACnet® is a registered trademark of American Society of Heating. installed on DMS502B51. temperature setting and monitoring can be accomplished individually or KJB311AA simultaneously. Not usable independently. DCS301BA61 • Up to 16 groups of indoor units(128 units) can be turned. 2. auto airflow rate and sensing sensor control can be set only via wired remote controller BRC1E62.FD-K Wiring adaptor for other air-conditioner 10 DIII-NET Expander Adaptor DTA109A51 Mounting plate KRP4A92 DTA107A55 DTA103A51 * To use any of the above optional controllers.E. Can be used in combination with up to 8 controllers. KEK26-1A • Programmed time weekly schedule can be controlled by unified control for up to DST301BA61 64 groups of indoor units (128 units). ® *2. ON/OFF individually or KJB212AA simultaneously. an appropriate adaptor must be installed on the product unit to be controlled. 2. Optional DIII board DAM411B51 • Expansion kit. 7. 3 — — Function DCS601C51 intelligent Touch Hardware Controller intelligent Touch Controller Option Hardware DIII-NET plus adaptor Electrical box with earth terminal (4 blocks) Basic Hardware intelligent Touch Manager Basic 2-1 — — — Notes: 1. DCM007A51 • Interface for intelligent Touch Manager by HTTP DEC101A51 • 8 pairs based on a pair of ON/OFF input and abnormality input. 2. • Up to 1024 units can be centrally controlled in 64 different groups. For residential use only. *1 Interface for use in BACnet® DMS502B51 • Interface unit to allow communications between VRV and BMS. KRP6A1 and DTA104A62 cannot be mounted to the same indoor unit at the same time. 3. 8 9 10-1 Function • Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. • Wiring restrictions (max. 6. Max. Connectable up to 2 controllers in one system. max. 52 . When using BRC1E62. 4. Cannot be set via other remote controllers. KRP413AB1S KKF917A4 KKF910A4 KRP928BB2S KKF917A4 • Wall embedded switch box. DAM412B51 • Expansion kit. Installation box is necessary for each adaptor marked . to provide 2 more DIII-NET communication ports. ON/OFF. DCS601A52 • Additional 64 groups (10 outdoor units) is possible. be sure to remove the control panel and since BRC1E62 cannot be stored inside the indoor unit. CTXG. Operation and monitoring of air-conditioning systems through BACnet® communication. CTXG and FTXS models. For VRV indoor unit use No. LonWorks is a trademark of Echelon Corporation registered in the United States and other countries. CTXG-P FTXS-D. No adaptor is required for some indoor units. 2-6 Di unit 2-7 Dio unit DEC102A51 • 4 pairs based on a pair of ON/OFF input and abnormality input. Wasted air-conditioning energy can be found out. 4. and ON/OFF. Backlight display Weekly schedule Backlight display helps operating in dark rooms. 5 actions per day can be scheduled for each day of the week. and with the fan operation. it returns to the preset temperature after a preset period of time. ON ON 4) 15:00 When the third period starts. but now the new remote controller (BRC1E62) allows the setting of both Cooling and Heating. This function is convenient when the remote controller is installed at a place where any number of people may operate it. Even if the set temperature is changed. (e. Period can be preset from 30 to 180 minutes in 10-minute increments. and max. set temperature. the air conditioner starts operating in Cooling automatically. Avoids excessive cooling or heating. 3 independent schedules can be set. For other settings just select the function from the menu list. When room temperature reaches 33ºC. OFF 3) 13:00 In the second period. Energy saving Auto operation mode Comfort Until now only the temperature for one point could be set. Dot matrix display BRC1E62 Setback temperature Cooling 33 37ºC -2 -8ºC Heating 10 15ºC +2 +8ºC A combination of fine dots enables various icons. 54 . 60.) 1 2 3 4 2 Setpoint range set Setpoint auto reset Saves energy by limiting the min. ON 2) 10:00 The first period starts and the air conditioner starts the cooling operation. the classroom is unoccupied and the air conditioner stops.g. and 120 minutes. Outlet mark 1 3 Restaurant sample Restaurant opened Temperature is set to 27ºC 27 °C Full tables at lunchtime Then is lowered to 24ºC for crowded room 24 °C After 30 minutes* Automatically returns to preset temperature (27ºC) Returns to 27°C Off timer Turns off the air conditioner after a preset period of time. Period selectable from 30 min/60 min/90 min/120 min. *1 Only available for VRV 4-Way Flow Ceiling Suspended type FXUQ-A series and Ceiling Mounted Cassette (Round Flow with Sensing) type FXFQ-S series. *Setting possible for after 30. winter. operation starts again. Ex) Setback temperature Cooling : 35ºC Recovery differential Cooling : -2ºC When the room temperature goes above 35ºC. summer. (Positions 0 to 4. The holiday function will disable schedule timer for the days that have been set as holiday. Basic setting such as fan speed and temperature can be intuitively operated. ON OFF Guide on display The display gives an explanation of each setting for easy operation. 53 4 automatically Auto airflow rate (*1) Airflow rate is automatically controlled in accordance with the difference between room temperature and set temperature.Control Systems Individual Control Systems for VRV Indoor Units Convenience Navigation remote controller (Wired remote controller) (Option) Setback (default:OFF) Clear display Maintains the room temperature in a specific range during unoccupied period by temporarily starting air conditioner that was turned OFF. Large text display is easy to see. the air conditioner returns OFF. and No individual setting are selectable. mid-season) Simple operation Recovery differential College classroom sample (a summer Monday case) Large buttons and arrow keys 1) 8:30 Large buttons and arrow keys enable easy operation. OFF OFF After the third period. 90. mid-range temperatures are comfortable and operation is more energy efficient. the classroom becomes vacant again and the air conditioner stops. Swing. Individual airflow direction (*1) Airflow direction of each of the four air outlets can be controlled individually. which can control the operation of indoor unit freely. 55 56 . operation mode. the remote controller can display the time to clean the filter. 3 Control for the combined operation The operation of Heat Reclaim Ventilator can be controlled by the remote controller of the indoor unit. Forced OFF input and etc. swing. Of course. auto airflow rate and sensing sensor control can be set only via wired remote controller BRC1E62. Ceiling Suspended type and Wall Mounted type is mounted into the indoor unit. * Individual airflow direction. the group control by two remote controller is also possible. temperature setting and airflow volume). * Refer to page 51 for the name of each model. The exposed type remote controller is fitted with a thermostat sensor. Double Flow) type. ● Displays current airflow.16 indoor units at the same time. 2 Remote control The wiring of remote controller can be extended to max. Remote controller Forced OFF input Wide variation of remote controllers for VRV indoor units FXFQ-S FXFQ-LU FXZQ Heat Reclaim Ventilator Remote controller Remote controller Remote controller Remote controller FXCQ FXUQ FXKQ FXDQFXDQ-SP PB/NB FXMQ FXHQ FXAQ FXL(N)Q FXVQ Navigation remote controller (Wired remote controller) (BRC1E62) Remote controller Wired remote controller (BRC1C62) 1 2 3 4 Wireless remote controller* (Installed type signal receiver unit) 1 Control by two remote controller The indoor unit can be connected by the two remote controller. (The last command has a priority. 4 Expansion of system control The system can be expanded to add several controllers. temperature. 500 m and it is possible to install the remote controllers for the different indoor units in one place. auto airflow rate and sensing sensor control can be set only via wired remote controller BRC1E62. Simplified remote controller (Option) ● Outdoor unit Group control One remote controller can control the operation of max. Signal receiver unit (Installed type) The wired remote controller supports a wide range of control functions Control of Cool/Heat changeover In all the series of VRV. operating mode and timer settings.) Of course. A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is included. Equipment related to the central control Concealed type (For hotel use) (BRC3A61) Indoor unit Remote controller Remote controller Exposed type (BRC2C51) ● The remote controller has centralised its frequently used operation selectors and switches (on/off. making itself suitable for use in hotel rooms or conference rooms. Signal receiver unit can be installed on the panel Signal receiver unit (Separate type) BRC1C62 ex. such as BMS. Wireless remote controller* (Separate type signal receiver unit) Simplified remote controller (Exposed type) (BRC2C51) Simplified remote controller (Concealed type: for Hotel use) (BRC3A61) *Refer to page 51 for the name of each model. * Individual airflow direction. ・A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow. Cannot be set via other remote controllers. Cannot be set via other remote controllers. Cool/Heat changeover in the same refrigerant circuit can be changed by the remote controller of the indoor unit. The concealed type remote controller smartly fits into a night table or console panel in a hotel room. for example one in the room and the other one in the control room. Ceiling Mounted Cassette (Round Flow) type Wireless remote controller * Wireless remote controller and signal receiver unit are sold as a set. Compact Multi Flow.Control Systems Individual Control Systems for VRV Indoor Units Wireless remote controller (Option) Wired remote controller (Option) ● The same operation modes and settings as with wired remote controllers are possible. • Different control equipment flexibly joined in the system for hierarchical risk diversification.) (Optional Maintenance Service) Unification adaptor for computerised control (DCS302A52) Home Automation Master Controller BMS * No adaptor is required for some indoor units. links air conditioners and various other building equipment—in accordance with applications.Control Systems Integrated Building Monitoring System DIII-NET Line BACnet®/Ethernet or LONWORKS® Network Communication Line The high speed transmission of DIII-NET enables more advanced control of the VRV system. providing you with enhanced comfort. • Saving the in-building cabling using non-polar. scale and conditions—and transmits vast amounts of information between them. Consultation is necessary before employing this control system. 58 . Daikin’s unique high speed multiple transmission system. therefore please consult us separately for details. Central Control Adaptor Kit (DTA107A55) Interface Adaptor for DIII-NET use (KRP928BB2S) Packaged Air-conditioner Residential Air-conditioner (Obtain locally) Di unit (DEC101A51) Dio unit (DEC102A51) Interface for use in BACnet® (DMS502B51) Interface for use in LONWORKS® (DMS504B51) VRV Wiring adaptor for electrical appendices (KRP2A61/62/53) 57 Building services equipment • Electrical equipment • Supply water and drainage equipment • Automatic fire alarm • Parking equipment • Lift • Ventilation equipment • Lighting • Crime and fire prevention equipment Caution: Limitation may apply to some models and functions. two-wire cables. Note: BACnet® is a registered trademark of American Society of Heating. Control /Connection Interface ACC Centre Home Automation Interface Adaptor (DTA116A51) SkyAir DIII-NET. Please contact your local sales office before making a purchase. Easier wiring work with tremendously fewer wiring errors. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries. Refrigerating and Air-Conditioning Engineers (ASHRAE). Please contact your local sales office for details. Contact Signal Line RS485 Modbus Line Building Control System The DIII-NET system provides for: • Close control and monitoring by integrating a wide variety of air-conditioners in the entire building. • Daikin's total heat exchangers and other devices under integral control. An extendable cabling up to 2 km in total. Controllers for Centralised Control VRV (DCS601C51) Heat Reclaim Ventilator (DCM601A51) Central Remote Controller (DCS302CA61) Via internet Unified ON/OFF Controller (DCS301BA61) Schedule Timer (DST301BA61) D -NET (High Speed Multiple Transmission) Interface Adaptor for SkyAir Series (DTA112BA51) Via internet Air Conditioning Network Service System (There are restrictions in applicable areas and release times. • Additional setups readily up and running. 64 indoor unit groups KRP928BB2S Web Access via LAN Air Conditioning Network Service System modem for connections Up to 7 Adaptors Fire alarm kWh meter RS-232C WAGO I/O up to 30 nodes D -NET Via internet D -NET Plus Adaptor DCS601A52 (Option) Indoor Unit Heat Reclaim Ventilator BACnet / IP Air Handling Unit 3rd party BACnet controller Lighting Pump Fan Sensor System Components ACC centre Keycard switch Number of indoor units expanded from 64 to 128. • WAGO Ao and Pi are newly supported and connectable WAGO modules are added. Automatic control • VRV systems are controlled automatically throughout the year by the schedule function. Enhanced history function Connectivity • BACnet connection with a wide range of building equipment. • Air Conditioning Network Service System (Optional Maintenance Service) Central control • Handy area settings simplify detailed management of VRV system. French. • E-mails are sent automatically to alert of malfunctions and potential trouble. Remote access • Remote access with a PC allows total air conditioning management using the same type of screens as those displayed in the intelligent Touch Manager. Troubleshooting • Contact information of maintenance contractors can be registered and displayed. 64 indoor unit groups Di/Pi Line Web Access via Internet Max. 64 indoor unit groups USB 2. German. • The intelligent Touch Manager can link to the Air Conditioning Network Service System for 24-hour monitoring of operating conditions and status. • Operation history shows manner of control and origin in past operations of air conditioning units.0 Flash drive Di/Pi port Max. 64 indoor unit groups (128 indoor units) iTM Plus Adaptor 100Mbps Ethernet DCS601C51 Max. Italian. • Display of floor plans enables a quick search of desired air conditioning units. Spanish. Portuguese. Dutch. • Setback adjusts temperature settings even when rooms are unoccupied. Energy management • The Energy Navigator feature simplifies energy management by tracking energy consumption data and identifying inefficient operation.Control Systems Advanced Control Systems for VRV Indoor Units Communication functions in the user-friendly icon-based multilingual controller simplify centralised control of the VRV system. • Interlocking VRV system and other equipment enables easy automation of building facilities operation. 59 Features Colour LCD touch panel icon display Small manageable size Simplified engineering Multi language (English. Chinese and Korean) Yearly schedule Auto heat/cool change-over Temperature limitation Scalability • A single intelligent Touch Manager can manage a small building or be expanded to handle medium.to large-sized buildings. • Authorised users can centrally control individual air conditioning units from their own computers. intelligent Touch Manager maximises the advantages of VRV features intelligent Touch Manager System Overview Up to 512 groups (1024 indoor units) Up to 650 management points Air Conditioning Network Service System DCM601A51 One D -NET system Max. Built-in modem for connecting to Air Conditioning Network Service System (Option) Simple Interlock Function Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option) 60 . Heating. Heating. one of the following can be selected: Local Controller. Connectable up to 10 outdoor units and 64 indoor unit groups. or intelligent Touch Manager. Refer to the Options page for the name of each model. *5. DMS502B51 Interface for use in BACnet® RS485 Modbus Protocol Television Wire length is up to 500m VRV Outdoor unit Simple installation Up to 2 units can be connected DTA116A51* One Adaptor requires for a house The VRV outdoor unit and Compatible with home automation system can be connected simply by an existing unit. H (depend on indoor unit capability) Reset filter sign of indoor units Retrieve system information Connected indoor units Indoor unit capabilities 61 D -NET address of connected indoor units can be retrieved. *2. Fan. M.etc DMS502B51 DMS504B51 ® ® (Interface for use in BACnet ) (Interface for use in LONWORKS ) Fire alarm Security Power supply facility VRV System Heat Reclaim Ventilator Local Controller Use of Modbus protocol Other Home Appliances Home Automation Master Controller Compatibility with BMS enhanced by utilising the international communication standards. Model name varies upon the system size. *3. M. *4. H (depend on indoor unit capability) Forced off status of indoor units Malfunction. Fan.3 protocol for BACnet®) Up to 40 outdoor units and 256 indoor unit groups on one gateway (optional adaptor) On/Off status of indoor units Cooling.Control Systems Advanced Control Systems for VRV Indoor Units Home Automation Interface Adaptor Interface for The VRV system can be operated from the home automation system. Air Conditioning Network Service System Maintenance services that boost profits and customer satisfaction Functions Monitor On/Off Operation mode Setpoint Room temperature Fan direction Fan volume Forced off status Error Filter sign Communication status Electric curtains Support for Heat Reclaim Ventilator VAM series Selectable temperature unit BTL Certification PPD data (Optional Di board is required. Flap direction (depend on indoor unit capability) L. setpoint HV can be retrieved. LonWorks® is a trademark of Echelon Corporation registered in the United States and other countries. It may not be installed inside some outdoor unit models. Dry. using this dedicated adaptor. *A separate power supply for Home Automation Interfere Adaptor is necessary. Auto (depend on indoor unit capability) Setpoint of indoor units Suction temperature of indoor units Swing. 62 .) ISO 16484-5 (Does not support IEEE 802. BACnet® or LONWORKS®. intelligent Touch Controller. Integrated control systems that recognise the trend of open control systems BACnet ® and LONWORKS® Image to use Home Automation Interface Adaptor DTA116A51 Ethernet Up to 16 indoor units can be individually controlled. Auto (depend on indoor unit capability) Cooling/Heating setpoint Swing. Lighting equipment DMS504B51 Interface for use in LONWORKS® XIF file for confirming of specifications of the units. Warning with Error code Filter sign of indoor units Communication normal/error of indoor units Automatic data transfer *4 I/F unit INTERNET ACC centre Malfunction report by E-mail Local dealers Control On/Off Operation mode Setpoint Fan direction Fan volume Filter sign reset On/Off control of indoor units Cooling. For an I/F unit. Stop. 24 hour on-line diagnostic system Energy saving and extension of aircon operating life Maintenance management via A /C network service system reports Reliable service at shortest lead time *1. Dry. Flap direction (depend on indoor unit capability) L. BACnet® is a registered trademark of American Society of Heating. Refrigerating and Air-Conditioning Engineers (ASHRAE). Please contact Daikin for compatibility with BMS system BMS VRV Indoor unit Lift Pump Lighting. Indoor unit capabilities such as operation mode. fan control. Schedule timer and BMS system Unification adaptor for computerised control (DCS302A52) 1. a maximum of 8 weekly schedule patterns can be set. and adapts easily to large-scale system expansion. DST301BA61 63 Max. Refer to page 51 for the total number of indoor units that can be connected to the outdoor unit.Control Systems Centralised Control Systems for VRV Indoor Units Residential central remote controller* (Option) Up to 64 groups of indoor units (128 units) can be centrally controlled. 8 weekly schedule control patterns possible 7 cores max. temperature settings and scheduling can be controlled individually for indoor units. wiring length 1. 16 groups of indoor units can be easily controlled with the large LCD panel.000 m (Total: 2. Unified ON/OFF controller (Option) Outdoor-air processing unit can be connected. Address setting of central control can be performed from the remote controller. Optional controllers for centralised control can be combined freely. Schedule timer (Option) • Certain indoor units limit the functions of some control systems. wiring length 1. while the central controller can be used to select desired zones. schedule timer and BMS system Airflow volume and direction can be controlled individually for indoor units in each group operation.000 m (Total: 2. 128 indoor units can be operated as programmed schedule. Max. Max. Each group has a dedicated button for convenience. 16 groups of indoor units can be operated simultaneously/individually. Ventilation volume and mode can be controlled for Heat Reclaim Ventilator. Connectable number of centralised control equipment Central remote 2 units controller Unified on /off controller Group control of up to 16 units is possible*1 (group control via automatic address setting) DCS302CA61 8 units Schedule timer 1 unit System without remote control is also available. Max.000 m) Connectable with Unified ON/OFF controller. Max. Zone control Malfunction code display Max. Cannot be used with other centralised control equipment. 128 indoor units controllable When used in combination with a central remote controller. which can control from 2 different places. Alarm) Centralised control indication Max. Interface adaptor for SkyAir series (DTA102A52) Up to 2 units connectable 6 cores Schedule timer (DST301BA61) 1 unit connection possible. Forced shut-down input Central remote controller (DCS302CA61) Wiring adaptor for other airconditioners (DTA103A51) Central control adaptor kit (DTA107A55). Max.000 m) Compact size casing (Thickness: 16 mm) Connectable with Central Remote controller.000 m (Total: 2. All indoor units can be turned on or off at once with “ALL” button. Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer. For more details. Central remote controller (Option) Max. Operating status indication (Normal operation. Unified on/off controller (DCS301BA61) Connection of up to 8 units possible Independent and centralised control of Heat Reclaim Ventilator is possible. System integration with various air-conditioning peripheral equipment such as Heat Reclaim Ventilator is easy. Outside temperature display DCS303A51 * For residential use only. Unified ON/OFF controller and BMS system 64 . 64 groups (128 indoor units) controllable Max. 16 groups (128 indoor units) controllable 2 remote controllers can be used to control from 2 different places. Up to 2 ON/OFF pairs can be set per day. 48 hours back up power supply Max. Max.000 m) Compact size casing (Thickness: 16 mm) Connectable with Central Remote controller. please refer to the Engineering Data. wiring length 1. Interlink Building Management System (host computer monitor panel) also possible DCS301BA61 Max. and system can be designed in accordance with building scale and purpose. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller. 16 groups (128 indoor units) controllable Backlight and large LCD panel for easy readability ON/OFF. Wiring can be run up to a total length of 2 km. 128 groups (128 indoor units) are controllable by using 2 central remote controllers. Air conditioning load reduced by approximately 31%! *1 This function can be operated only when interlocked with air conditioners. • The air conditioning load reduction values are based on the following conditions. (Return air from room) (Fresh air from outdoors) SA (Supply air to room) Indoor unit • ON/OFF signal • Cooling/Heating mode signal • Set temperature signal • Ventilation signal Interlocking Reduces air conditioning load by not running the Heat Reclaim Ventilator while air is still clean soon after the air conditioner is turned ON. VAM650GJVE. Thickness of resulting in increased effective area that supply and the partition sheet exhaust air can be exposed to. such as above ceilings. miscellaneous gas barrier properties are maintained by decreasing the porosity in the moisture-absorption materials. cooling load when air conditioners are turned on in the This reduces the air conditioning load the next day thereby increasing efficiency. Pre-heat Control Sheet structure Outdoor Air conditioning load reduction (%) EA Indoor -10 0 10 20 30 40 50 CO2 sensor optional kit connection Prevent energy losses from over-ventilation while maintaining indoor air quality with optional CO2 sensor. VAM350GJVE. VAM1000GJVE.Air Treatment Equipment Lineup Heat Reclaim Ventilator — VAM series The Heat Reclaim Ventilator Creates a High-Quality Environment by Interlocking with the Air Conditioner Air conditioning load reduced by approximately 23% Total heat exchange ventilation Model Names 31%! VAM150GJVE. Furthermore. Application: Tokyo office building Building form: 6 floors above ground. By ventilating rooms containing office equipment that raises the room approx. nighttime free cooling operation reduces the The indoor accumulated heat is discharged at night. Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating status of the air conditioner. 25 days per month) Calculation method: simulation based on "MICRO-HASP/1982" of the Japan Building Mechanical and Electrical Engineers Association. RA OA • Operating mode signal • Filter cleaning signal • Failure detection signal High-humidity air SA (Exhaust air to outdoors) For models: VAM150/250/350/650/800/1000/2000GJVE 2 For models: VAM150/350/500GJVE 1 Exhaust air Exhaust air 2% Pre-cool. VAM250GJVE. •Realises more space for extra layers in the element. temperature. improved external static pressure 2 offers more flexibility for installation. 66 . winter 22℃ 40% RH Operating time: 2745 hours (9 hours per day. Furthermore. *Interlocked operation with an air conditioner Standard operation at temperatures down to -15℃. the nighttime free cooling operation contributes to energy conservation and more comfortable space. approx. floor area 2. Cold Climate Compatible 306 mm Exhaust heat Generated heat Heat is discharged. *2 Value is based on the following conditions: • Cooling operation performed from April to October. 10%! This VAM series provides higher enthalpy efficiency 1. the unit easily fits in limited spaces. VAM1500GJVE. request your dealer to turn it on. morning. thereby conserving energy and reducing the load on the air conditioning system. so if you wish to use it. thin-film material RA (unclean indoor air) Outdoor air (fresh air) Supply air Low-humidity air Moisture exchange efficiency is greatly improved by using optimised thinner films and moisture-absorption materials in the element. VAM500GJVE. intermediate seasons 24℃ 50% RH.100 m2 Personnel density: 0. Comfortable! The load is small so the temperature is rapidly reduced to a comfortable level. Cold air Indoor unit Indoor unit Exhaust heat With a height of just 306 mm. • The air conditioning load reduction values may vary according to weather and other environmental conditions at the location of the machine's installation. VAM800GJVE.25 person/m2 Ventilation volume: 25 m3/h Indoor air conditioning level: summer 25℃ 50% RH. due to the greatly enhanced performance of the thin film element. 5% ! Heat Reclaim Ventilator Energy Conservation •Nighttime free cooling operation only works to cool and if connected to Building Multi or VRV systems. Enthalpy efficiency drastically improved by employing thin film element! (VAM-GJ model) Due to the thinner film… •Decreases the moisture resistance of the partition sheets drastically. Along with these three outstanding improvements. It also alleviates feelings of discomfort in the morning caused by heat accumulated during the night. 2 floors underground. etc. VAM2000GJVE Heat Reclaim Ventilator remote controller* BRC301B61 (Option) 1 Improved Enthalpy Efficiency 2 Higher External Static Pressure Enhanced Energy Saving Functions * This remote controller is used in case of independent operation of Heat Reclaim Ventilator. •Nighttime free cooling operation is set to “off” in the factory settings. • Calculated for air conditioning sensible heat load only (latent heat load not included). Daikin air conditioner 20% 0% Normal ventilation fan VAM-GJ Individual operation VAM-GJ Interlocked operation with air conditioner Air conditioning sensible heat load reduced by Nighttime free cooling operation is an energy-conserving function that works at night when air *2 conditioners are off. 6% Auto-ventilation Mode Changeover Switching This unit recovers heat energy lost through ventilation and curbs room temperature changes caused by ventilation. Moisture absorption increased by approx. -15˚CDB 50˚CDB * For VAM500GJVE -20 65 31% Air Conditioning Load Reduced by Approximately Nighttime free cooling operation*1 LCD remote controller for indoor unit Compact Equipment Molecule of water Miscellaneous gas CO2 molecule. Precise. 5-40.5-41.5 30-31. with the value converted for an anechoic chamber. 3.5 27-29 31. Use a non-inflammable connecting duct to the electric heater. 3 Notes 4.5-43.5 34.289 111 120 182 225 300 517 567 991 1.5-30.5-29 31.5-41.5 36-38. flexible duct and sound-muffling air supply/discharge grilles •Decentralised installation of discharge grilles 11. In conformance with JIS standards (JIS B 8628).5 65 70 65 72 76 74 77 74 71.000 High m3/h 150 250 350 500 650 800 1. 8. Up to 2 adaptors can be fixed for each installation box. The specifications.5 27. and this will result in a marked increase in noise. 5.289 111 120 182 225 300 517 567 991 1.5-28. 3 Notes 2.090X2 150 0.5 40. etc.5 39-43 20. When connected with a Heat Reclaim Ventilator (VAM).720 Ultra-High 120 70 169 105 85 133 168 112 116 106 54 141 66 53 92 110 73 58 56 24 67 32 35 72 85 56 Airflow Rate External Static Pressure High Pa Low Motor Output kW Connection Duct Diameter mm Unit Ambient Condition 0.145 1. Type VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE — KDDM24B50 KDDM24B100 KDDM24B100X2 Silencer Nominal pipe diameter mm — 200 250 High efficiency filter KAF242H65M KAF242H80M KAF242H100M KAF242H80MX2 KAF242H100MX2 KAF242H25M KAF242H50M Air filter for replacement KAF241G50M KAF241G65M KAF241G80M KAF241G100M KAF241G80MX2 KAF241G100MX2 KAF241G25M Flexible duct (1 m) K-FDS101D K-FDS151D K-FDS201D K-FDS251D Flexible duct (2 m) K-FDS102D K-FDS152D K-FDS202D K-FDS252D — YDFA25A1 Duct adaptor Nominal pipe diameter mm — 250 CO2 sensor — BRYMA65 BRYMA100 BRYMA65 BRYMA100 Item PC board adaptor for heater control kit (BRP4A50) When the installation of an electric heater is required in a cold region. outdoor side to indoor side = 7 to 1.214 785X1.214 RA Additional function Bypass Mode 79 Low For Cooling High Sound Level 75 Ultra-High For Heating High Power Consumption % 79 Controlling device Temp. Up to 2 installation boxes can be installed for each indoor unit.5 67.5-39.5 22. 3 — — — Note 3 — — KRP1H98 KRP1BA101 KRP1B96 KRP1BA101 KRP4A96 KRP1CA93 KRP4AA93 Installation box is necessary for each adaptor marked . Sound level is measured in an anechoic chamber.5 27. 50 Hz/60 Hz Ultra-High PC Board Adaptor Power Supply Enthalpy Exchange Efficiency Air suction/discharge grille (Obtain locally) VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE Heater (Obtain locally) OA Thermostat (Obtain locally) (ON when the temperature is at or below -10℃) Power supply (Obtain locally) Relay box Notes when installing Examine fully an installation place and specification for using the electric heater based on the standard and regulation of each country. Indoor Outdoor EA RA Heat Reclaim Ventilator SA BRP4A50 Thermostat (Obtain locally) (OFF when the temperature is at or more than 5℃) 67 EA Option List Installation box for adaptor PCB Sirocco fan Silencer (Option) Duct (Obtain locally) SA 157 Multidirectional fibrous fleeces Type Round hood (Obtain locally) Branch duct (Obtain locally) Specially processed nonflammable paper Air Filter High efficient filter (Option) SA Air to air cross flow total heat (Sensible heat + latent heat) exchange Heat Exchange Element Material Fan 387X1.5-33 33-35. 6 Notes 2.5-42. The sound level at the air discharge port is about 8 dB(A) higher than the unit's sound level.500 2.000 1.5 31. Sound level is measured at 1. 6 Notes 2.5 33-34. 2. this adaptor with an internal timer function eliminates the complicated timer connecting work that was necessary with conventional heaters.5-34 33-34. designs and information given here are subject to change without notice.5 39.5-33 33-34. 7.5 39. 5.500 2. 9.5 26-27.5 64 66 Ultra-High 125 137 200 248 342 599 635 1. if peripheral effects are included (such as reverberation of the floor and walls.5 High dB(A) 27.5-26.5-29. When installing in a location with particularly low background noise such as a classroom. 7.5 25.5-28. 6. Supply the electric heater and safety production devices such as a relay and a thermostat.5-23 24. Exchange Efficiency Heat Exchange Mode Flexible duct (Option) 1-phase.619X1. Temperature Exchange Efficiency is the mean value between cooling and heating. In such cases.151 High W Low 57 60 122 128 196 435 476 835 966 Ultra-High 125 137 200 248 342 599 635 1. If the equipment and discharge grille are near each other.5 38. Please consider noise countermeasures when installing the unit. 4. reflected sound. 220-240 V/220 V.5 33-35.5-40 38. Installation box is necessary for each adaptor. BRC301B61 DCS303A51 *1 DCS302CA61 DCS301BA61 DST301BA61 KRP2A61 KRP50-2 KRP50-2A90 (Mounted electric component assy of Heat Reclaim Ventilator) BRP4A50 FXFQ-S FXDQ-PB FXLQ-MA Type For wiring (indoor unit of VRV ) FXFQ-LU FXZQ-M FXUQ-A FXCQ-M FXKQ-MA FXDQ-NB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-P FXNQ-MA FXVQ-N — KRP1C63 KRP1BA57 KRP1C67 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 KRP1B61 KRP1C67 Notes 2. 3 Note 4.280X4 350 -15℃–50℃DB.5 35-37.5 36. combination with other equipment.5 35-37. 6.5-41 40. *1 For residential use only.5 27. 3. With large models in particular (1500 and 2000 m3/h models).5-29. please consider countermeasures such as the following: •Use a sound-muffling box. operating sound level is based on the value when one unit is operated.5 41. Efficiency is measured under the following conditions: Ratio of rated external static pressure has been maintained as follows.5-23. for example.5 39. Cannot be used with other centralised control equipment.Air Treatment Equipment Lineup Specifications MODEL Options High 74 75 72 78 72 77 79 75 79 74 75 72 78 72 77 84 79 82 80 77 74 80. please consider the following measures to avoid transmission sound from the main unit: •Use of ceiling materials with high sound insulating properties (high transmission loss) •Methods of blocking sound transmission. please provide as much separation as possible between the main unit and the discharge grille.111X1.111X832 387X1.5 36-38. Thus it is normal for the sound to be louder than the indicated value when the unit is actually installed.5-39.5 37.145 1. consider supplementary methods such as installing the equipment in a different location (corridor.5 36-39 28.619X832 785X1. 10. use a different power supply from that of the electric heater and install a circuit breaker for each. Sound level generally becomes greater than this value depending on the operating conditions.5 28. Alternatively.140X2 200 0.5 37.5 67 75 66 63 66 55 61 61 64 61 62 66 63 66 55 61 61 64 61 62 % Low Ultra-High % Low 70 66 70 59 64 64 68.5-39.5 65 70 65 72 72 71 70 67 67.320 1.5 21-22 23-25 25-28. and peripheral noise.5 Bypass Mode High W Low Ultra-High Heat Exchange High dB(A) Mode Low Ultra-High Casing Galvanised steel plate Insulation Material Self-extinguishable polyurethane foam Dimensions (HXWXD) Machine Weigh mm 278X810X551 kg 24 Heat Exchange System 306X879X800 338X973X832 32 45 55 67 129 Thermal insulation material (Obtain locally) OA Ultra-High 150 250 350 500 650 800 1.5-30. you can only switch the power ON/OFF. 68 .5 34-36 39-40. When installing a large model. 4. sound level may be as much as 15 dB(A) higher than the indicated value.5 26-27. Sound level from the discharge port causes the value to be approximately 8 dB(A) (models with the airflow rate of less than 150 to 500 m3/h) to approximately 11 dB(A) (models with the airflow rate of 650 m3/h or more) greater than the indicated value. Furthermore. Only one installation box can be installed for each indoor unit.5 37-39.000 Low 100 155 230 320 500 700 860 1.5 79 72 71 70 67 67. Installation box is necessary for second adaptor.5-38 37. fan rotation and noise from the discharge grille may increase depending on the on-site duct resistance conditions.5 35-37. For the Heat Reclaim Ventilator.5-21.151 57 60 122 128 196 435 476 835 966 27-28. 2.5 41-43 43-45. and does not include sound from the discharge grille. the noise of the main unit may be heard from the discharge grille via the duct.030X2 100 0.000 1. Be sure to allow 2 m or more between the electric heater and the Heat Reclaim Ventilator for safety. This is transmission sound from the main unit.5-45 Low 22. Airflow rate can be changed over to Low mode or High mode.) Type Item Heat Reclaim Ventilator remote controller Residential central remote controller Centralised Central remote controller controlling Unified ON/OFF controller device Schedule timer Wiring adaptor for electrical appendices For humidifier Installation box for adaptor PCB For heater control kit Notes: 1. by adding sound insulating materials around the bottom of the sound source. 80%RH or less Notes: 1.5 m below the centre of the body.5-42 40. if the supply air (SA) grille is installed near the main unit.5 72.5-36 35-37.280X2 250 45 0.5 75. etc of which qualities satisfy the standard and regulation of each country at site. and background noise). Memo 69 70 .