Manual Ups

March 30, 2018 | Author: azaquy | Category: Power Inverter, Alternating Current, Rectifier, Switch, Direct Current


Comments



Description

μPS-SP Series 3:3 Phase, 10 – 60 kVA, 3 X 208 Vac, 60 Hz, 192 Vdc Gamatronic Electronic Industries Ltd. Har Hotzvim Industrial Park 14 Hartom St. PO Box 45029 Jerusalem 91450 Israel Tel: +972-2-588-8222 Fax: +972-2-582-8875 Email: [email protected] Website: www.gamatronic.com This UPS has been designed for commercial/industrial use only, and is not for use in any life support application. © Copyright 2008 by Gamatronic Electronic Industries Ltd. All rights reserved worldwide. The information contained in this document is proprietary and is subject to all relevant copyright, patent and other laws protecting intellectual property, as well as any specific agreement protecting Gamatronic Electronic Industries Ltd. rights in the aforesaid information. Neither this document nor the information contained herein may be published, or reproduced, in whole or in part, without the express, prior, written permission of Gamatronic Electronic Industries Ltd. In addition, any use of this document or the information contained herein for any purposes other than those for which it was disclosed is strictly forbidden. Gamatronic Electronic Industries Ltd. reserves the right, without prior notice or liability, to make changes in equipment design or specifications. Information supplied by Gamatronic Electronic Industries Ltd. is believed to be accurate and reliable. However, no responsibility is assumed by Gamatronic Electronic Industries Ltd. for the use thereof nor for the rights of third parties which may be affected in any way by the use thereof. Any representation(s) in this document concerning performance of Gamatronic Electronic Industries Ltd. product(s) are for informational purposes only and are not warranties of future performance, either express or implied. Gamatronic Electronic Industries Ltd. standard limited warranty, available upon request, stated in its sales contract or order confirmation form, is the only warranty offered by Gamatronic Electronic Industries Ltd. in relation thereto. This document may contain flaws, omissions or typesetting errors; no warranty is granted nor liability assumed in relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd. sales contract or order confirmation. Information contained herein is periodically updated and changes will be incorporated into subsequent editions. If you have encountered an error, please notify Gamatronic Electronic Industries Ltd. All specifications are subject to change without prior notice. ii μPS-SP Series 3:3 Phase, 10 – 60 kVA, 3 X 208 Vac, 60 Hz, 192 Vdc TABLE OF CONTENTS 1. SAFETY PRECAUTIONS ...................................................................................... 1 1.1 Do’s .............................................................................................................. 1 1.2 Don’ts........................................................................................................... 1 2. GENERAL FEATURES ......................................................................................... 2 2.1 Parallel Operation ....................................................................................... 3 2.1.1 Advantages of Parallel Operation ..................................................... 3 2.2 Major Subsystems ...................................................................................... 3 2.2.1 Rectifier................................................................................................ 3 2.2.2 Batteries............................................................................................... 4 2.2.3 Inverter................................................................................................. 4 2.2.4 Static Switch........................................................................................ 4 2.2.5 Bypass Isolation Transformer (option)............................................. 4 2.2.6 Control System ................................................................................... 4 2.3 Control Panel .............................................................................................. 5 2.4 Power-on Self Tests ................................................................................... 6 2.5 Measurement............................................................................................... 6 2.6 Real Time..................................................................................................... 6 2.7 Communications......................................................................................... 6 2.8 Event Logs .................................................................................................. 6 2.9 Ease of Use ................................................................................................. 6 2.10 Battery Check.............................................................................................. 6 2.11 Service Mode............................................................................................... 7 2.12 Emergency Power-Off (EPO) ..................................................................... 7 2.13 Connections ................................................................................................ 7 3. PARALLEL OPERATION (OPTION)..................................................................... 8 3.1.1 Centralized vs. Decentralized Static Switch..................................... 8 3.1.2 Decentralized Parallel Mode of Operation ........................................ 8 4. CONTROL PANEL & INDICATORS ................................................................... 11 4.1 The Control Panel on the Standard Cabinet........................................... 11 4.1.1 Function Buttons on the Standard Cabinet.................................... 12 4.1.2 Information Buttons on the Standard Cabinet ............................... 12 4.2 The Control Panel on the Larger Cabinet ............................................... 16 4.2.1 Function Buttons on the Larger Cabinet ........................................ 17 4.2.2 Information Buttons on the Larger Cabinet ................................... 17 4.3 The LOG, SET, and HELP Buttons for All Models ................................. 21 4.4 System Fault Diagnostics ........................................................................ 25 4.5 LED Indicators .......................................................................................... 27 5. OPERATING THE ΜPS SERIES UPS ................................................................ 29 5.1 Turning the UPS ON ................................................................................. 29 5.2 Turning the UPS OFF ............................................................................... 30 5.3 Activating Maintenance Bypass .............................................................. 31 5.4 Deactivating MAINTENANCE BYPASS ................................................... 32 5.5 After Use of the Emergency Power-Off Switch ...................................... 33 5.6 Setting the Real Time Clock .................................................................... 33 iii .......1 Accessibility............................. 10 – 60 kVA......................................... 10 Figure 6: Control panel on the standard cabinet (10kVA to 60kVA models) ............... 51 9................5.......... 41 8.......................... 52 9....................3................................................................. 44 Figure 18: Circuit breakers on the 10-20KVA models ...........3 Terminal Connections . TECHNICAL SPECIFICATIONS ....... 45 Figure 19: Circuit breakers on the 30-60 kVA models ...................................cable connections ..1 Wiring/Cabling Instructions ....... 38 8...2 Electrical Wiring....................3 Installation of Standalone UPS.........................................4 Installation of Decentralized Parallel Systems...................................................................................................................................... 11 Figure 7: Control panel on the larger cabinet (optional for 40–60KVA models)...5 Parallel Start-Up. 3 X 208 Vac......... 27 Figure 14: LED Indicators on the optional larger cabinet ............................................................................................................................... 26 Figure 12: Voltage Correction .... 22 Figure 11: Active Current Sharing ....................... 44 9................................ 47 9................................. 42 8............................. 9 Figure 5: Centralized Parallel µPS ............... 54 LIST OF FIGURES Figure 1: Schematic Diagram of the Operation of the UPS........................... COMMUNICATIONS........................................................................................................................... 41 8..........................3 Turning On the UPS for the First Time ................ 52 10........................................ 2 Figure 2: Control Panel on the 10 kVA to 60 kVA models....................................... 60 Hz............................................................... 192 Vdc 6....................................................................................................................... 45 9......2 External Battery Cabinet ............................................................................................ 42 Figure 17: Terminal Connections ..................................................... 48 iv ............................................................................................ 34 6..............................................................................................................................................................................3. 46 Figure 20: Connecting the external battery cabinet .........1 Installation Considerations................................................ 45 9..... 36 Figure 16: External circuit breakers ..............2 Circuit Breakers .................................................................................................... 21 Figure 9: Accessing the Log on the standard cabinet ....................................... 16 Figure 8: LOG Messages Structure ........................................................3 Remote Monitor Box (Optional)................. 26 Figure 13: LED Indicators on the standard cabinet ... 27 Figure 15: Remote Monitor Box .. 47 9........ 35 6.............3......................................................................................................................................................................................................................μPS-SP Series 3:3 Phase.. SITE PREPARATION ..................................................1 Decentralized (2 UPSs only) ..1 Connecting the Monitor Box to the UPS........ 21 Figure 10: Accessing the Log on the large cabinet .............................................................2 The Alarm Interface ........ 5 Figure 3: Control Panel on the 40 – 60 kVA model with optional larger cabinet ................................. 45 9............................................................................................................................................................... TROUBLESHOOTING..............3.............cable connections ............1 RS232 Interface.......... 36 6.............................. 37 7................... 48 9.................................................................................. 5 Figure 4: Decentralized Parallel µPS .... 49 9........................................ INSTALLATION .................. 34 6............................ ............................................................................................................................. Unless otherwise indicated............... 34 Table 4: LED Indicators on Remote Monitor Panel..... the readings on the display screen in the diagrams are representational only... 43 Table 9: Wiring requirements ................................ User Guide and Instruction Manual v ...... 37 Table 6: Trouble Shooting and Problem Solving .... 43 Table 10: Technical Specifications.................................................................................................................. 60 Hz..............................................μPS-SP Series 3:3 Phase................... 38 Table 7: PC Board Check Points & Voltage Ranges.. and are not intended to match the readings on any specific system in a particular environment.................... 10 – 60 kVA........................ 3 X 208 Vac......... 54 STANDARDS AND CONVENTIONS This manual contains diagrams that include an image of the UPS’s LCD display screen.................................... Gamatronic Electronic Industries Ltd........................................ 28 Table 3: RS232 Connector Pin Assignment ................................................................................................................... 40 Table 8: External circuit breakers – required minimum ratings ............... 23 Table 2: LED Indicators........................................... 192 Vdc LIST OF TABLES Table 1: Log Variables ................ 36 Table 5: Control Buttons on Remote Monitor Panel.............................................................. 3 X 208 Vac. vi . 10 – 60 kVA.μPS-SP Series 3:3 Phase. 60 Hz. 192 Vdc This page left blank deliberately. WARNING Do not touch the battery terminals of external batteries with bare hands. (The battery’s cabinet body must be connected with the grounding screw located on the electronic cabinet or directly to the grounding circuit. Install the UPS in a clean and well-ventilated location. 3x220 in.2 • • • • • • • Don’ts Do not open the cover under any circumstances. The UPS must be well grounded to the building’s grounding system with a conductor that has a current carrying capacity that matches the rating of the UPS. there is a risk of lethal electric shock. µPS-SP 3:3. Do not try to repair it yourself! • • • WARNING Appropriate precautions should be taken during inspection and servicing. 1. Do not move the UPS while it is operating. If the unit contains an external battery cabinet. Allow only qualified technicians to service the UPS.Gamatronic Electronic Industries Ltd. Do not turn the UPS upside down during transportation. Review the safety precautions described below to avoid damaging users or equipment. User Guide 1.) Use the UPS only for its intended purpose. There are no userserviceable components. Do not put objects on the UPS. periodically check the grounding connection between the external cabinet and the main UPS cabinet.1 • • • • • Do’s Read this manual carefully before operating the UPS. SAFETY PRECAUTIONS 1. Do not connect or disconnect the cable to the battery cabinet before the battery circuit breaker is turned off Do not turn on the battery circuit breaker when the battery cabinet is disconnected from the UPS. The battery cabinet contains 12-Volt batteries that provide high voltage even when the UPS is not connected to the mains. Do not insert any objects through the ventilation holes. Leave at least 20 cm of clearance space between the ventilation holes of the UPS and other objects or walls. 3x208 60 Hz out Safety Precautions 1 . the UPS provides backup power for a specific period of time. Its operation is simple and requires no previous technical knowledge. sophisticated protection for every type of line fluctuation. 3x220 in. 2. for any reason. The system informs the operator. 3x208 60 Hz out . The unit consists of two major subsystems: 1 Reduced Instruction Set Computing 2 General Features µPS-SP 3:3. current operational status of the UPS. An LCD display on the UPS front panel provides real time. the UPS is powered by batteries and maintains a constant output voltage supply. When backup service is provided (when there is a power breakdown in the mains).User Guide Gamatronic Electronic Industries Ltd. Figure 1: Schematic Diagram of the Operation of the UPS In the event of a power failure. including interruption of the AC input . GENERAL FEATURES The μPS Series 3/3 Phase Uninterruptible Power Supply (UPS) employs Pulse Width Modulation (PWM) and is controlled by a high performance RISC 1 micro-controller. the unit provides a voltage of 3 × 208VAC at a stabilized 60 Hz frequency to any practical load. The system is user friendly. The system can also be connected to the service center via a modem and a telephone line. or to a computer network via an SNMP/WEB agent. The UPS operates on-line and once activated. such as during power surges. Similar status information may be viewed on a computer monitor via an RS232 communications port. to provide reliable. when a power failure occurs. or in case of inverter failure. providing the user with complete up-to-date information. The UPS is equipped with a Static Switch that enables the load(s) device(s) to continue normal operation when the inverter is unable to supply exceptionally heavy loads. by means of LED indicators and audible signals. etc. The parallel UPS system is the most reliable energy source for any critical load. 3x208 60 Hz out General Features 3 . µPS-SP 3:3. microprocessor board. 3x220 in. the output voltage is not interrupted even if more than one UPS unit is faulty.Gamatronic Electronic Industries Ltd. the output voltage is not interrupted even if one of units is faulty. User Guide • Electronic Cabinet that contains all electronic components: charger. two to ten UPS units may be connected in parallel. the static switch is external instead of inside each UPS.1 Advantages of Parallel Operation Redundancy Parallel operation of the UPS provides redundancy in the event of a UPS failure. If the system uses N+1 UPS units (the redundant parallel system). Two topologies are supported: centralized and decentralized. The microcontroller also ensures synchronization of the phase and frequency of the output of all of the UPSs. Up to 10 units can be connected in parallel to feed and backup the same load.2. In this case. Load Sharing The μPS SP UPS includes a high-speed microcontroller to manage the process of load sharing between the units connected in parallel. the load is shared between the units. With a decentralized parallel system.1. inverter. See “Parallel Operation” beginning on page 8. to provide full redundancy. Parallel operation is appropriate where the devices supported by the UPS are of critical importance and higher MTBF is required. 2. In this configuration. If the parallel system is equipped with a Gamatronic Static Switch unit.1 Parallel Operation The μPS-SP UPS can be operated in parallel with similar UPSs. each UPS has its own static switch in which case two systems can be connected in parallel. panel.1 Rectifier The rectifier supplies a stabilized DC voltage to the device at 216V ± 2V. 2. 2. static switch. • Battery Cabinets that contain batteries and circuit breaker.2 Major Subsystems The μPS SP UPS consists of the following modules: 2. With a centralized parallel system. The unit can operate in parallel with similar Gamatronic UPS units. bypassing the inverter. During normal operation. together with the Inverter isolation transformer. output current. current transformer. input/output signal frequency. PC906 board.2. AC voltage (power).).6 • • • • Control System Tests input.5 Bypass Isolation Transformer (option) For customers requesting this option.3 Inverter The inverter receives a DC voltage from the charger or batteries and supplies a regulated. isolated output transformer circuit.2.SW automatically switches the load back to the inverter when inverter's output voltage returns to normal. The control system performs the following functions: 4 General Features µPS-SP 3:3. Reads the panel keyboard and sends messages to the front panel LCD display.SW/Bypass automatically transfers the load from the inverter to the mains without voltage interruption or disturbance. 2. 2. frequency-stabilized. 3x208 60 Hz out . 2. The ST. The inverter incorporates an IGBT transistorized bridge.2. (PC968 board). and temperature. inrush current on connecting the load. Controls the inverter and the bypass changeover contactor—RA101— and manages the static switch and charger voltage during battery tests. The static switch includes the PC690 board and the RA101 . an L-C filter circuit.2. inverter malfunction. The function of this transformer. battery voltage. When the UPS is in BYPASS mode.2 Batteries The batteries are always connected to the rectifier output and they supply voltage to the inverter during power failures. 3x220 in. The batteries for all models are housed in separate battery cabinets. The inverter is synchronized with the mains in both frequency and phase to ensure correct operation of the static switch. the batteries are in standby mode.2. 2. bypass. etc.4 Static Switch In case the inverter cannot supply the load with the correct voltage (for example: because of overload. is to create a condition of complete galvanic isolation between the input and output of the UPS. inverter. 2.RA103 contactors. Controls the Alarm interface. the ST. driver. the UPS includes an isolation transformer connected to the Bypass AC input.User Guide Gamatronic Electronic Industries Ltd. the load draws power directly from the mains. and a PC801 control board. User Guide • Communicates with devices via the RS232 interface.3 Control Panel The UPS is equipped with an LCD display and touch pad control panel that enables the user to effectively manage the UPS. Messages. 2. 3x220 in.Gamatronic Electronic Industries Ltd. warnings and error conditions are relayed to the user through the control panel’s LCD display and through audible alarms. PC075/PC085 panel board. and temperature sensors. current. The control system includes the PC801 control board. Figure 2: Control Panel on the 10 kVA to 60 kVA models Figure 3: Control Panel on the 40 – 60 kVA model with optional larger cabinet µPS-SP 3:3. 3x208 60 Hz out General Features 5 . the control panel serves as the user’s primary interface with the system. Once the UPS is installed. PC873 power supply. Measured voltages and currents are connected to the control board via the PC800 interface board. 6 Real Time The system includes a real time clock and calendar that sequentially manage the log file and provide historical data to the user.5 Measurement The user can receive real time information regarding the unit’s operation and condition simply by pressing the appropriate status button. Memory (setup. All LEDs are lit individually for the operator to monitor. 2.9 Ease of Use The UPS includes an on-line help feature that explains the system’s features and describes each of the LCD control buttons. proprietary SNMP agents. This information is very useful for maintenance and analyzing performance statistics. 2.4 Power-on Self Tests The UPS automatically performs the following series of diagnostic tests when initially powered on: • • • LED test. 2. 2. 3x208 60 Hz out . 6 General Features µPS-SP 3:3. using a modem connected to a telephone line. 2.8 Event Logs The system compiles a listing of up to 256 extraordinary events of the mains. 2. unit and load during operation.10 Battery Check The unit automatically and continuously checks the battery status and the battery cabinet connection with the UPS. calibration and events log) is tested. The real time results are displayed on the front panel. Real-time clock EEPROM. 3x220 in. for network access. through the RS232 communications port. 2.User Guide Gamatronic Electronic Industries Ltd. This information is accessible via the LCD display or.7 Communications The UPS relays all the measured data and events of the log file through an RS232 communications port to a host computer or. or via GMAC or GMACi. optionally. to a remote location. This data is written to the log file and can be accessed easily at any time through the display panel or computer (optional). )” The Emergency Power-Off terminals should be connected by a normally closed.5. 48V 0. 3x208 60 Hz out General Features 7 . User Guide 2. and batteries—are accessed via the lower portion of the front of the UPS. For the 10-20 kVA models: All connections are made on the rear panel of the UPS. These terminals are labeled “EMERG. input.13 Connections For the 30-60 kVA models: All connections—connection panel. 2.12 Emergency Power-Off (EPO) The system includes a pair of wires linking two Emergency Power-Off terminals. µPS-SP 3:3. “After Use of the Emergency Power-Off Switch” on page 33. Power to the load is cut.11 Service Mode The UPS has a technician’s SERVICE MODE that is password protected.C. located together with the other terminals.1A mushroom-type pushbutton. Access to the service mode is only permitted after the technician successfully enters an assigned password. 2. output. 3x220 in. OFF” or “EPO (N. See also section 5. The user must unlock the door with a flathead screwdriver to access these areas. Pressing the pushbutton opens the contact and shuts down the unit.Gamatronic Electronic Industries Ltd. an active current sharing circuit changes the output voltage of each UPS to provide proportional load sharing between the units. In addition. Up to ten units can be connected in parallel.2 Decentralized Parallel Mode of Operation The μPS SP UPS uses a simple “master/slave” hierarchy. where one unit at any given time is designated as the Master UPS and the remaining parallel units are considered Slave UPSs.1 Centralized vs. In decentralized mode each UPS includes its own Static Switch which works independently. because the output voltage is constant even if both UPSs are disconnected. the Static Switch would instantly be triggered and supply the load directly from the mains. 3x208 60 Hz out . Two or more units would then be connected in parallel. The other units are Slaves and follow the Master. and is now responsible for transmitting phase and frequency information to the Slave UPSs. Figure 4 on page 9 shows a cabling diagram for parallel decentralized operation of multiple UPSs. the Static Switches are synchronized using a 3-wire cable. which synchronize themselves accordingly. For additional security.1. 3. This would connect the inverter of the other UPS directly to the mains which could potentially damage the other UPS. Local static switches are inhibited. to avoid such a hazard in decentralized mode. Decentralized Static Switch The UPS employs a Static Switch for functional override. Therefore. PARALLEL OPERATION (OPTION) Each UPS can optionally operate in parallel with similar units as part of a modular UPS system. The function of Master is not dedicated to one of the units. the next UPS in line becomes the Master. One of the system's units takes on the function of Master. to prevent circulation of energy between the UPS units and to isolate the faulty unit from the common power bus. and transmits the phase and frequency information to the Slave UPSs. Special technical solutions are used to synchronize all the units of the system.This method significanly increases system reliability. As illustrated in Figure 5 on page 10. This unit is synchronized to the mains power. When the Master UPS fails. Up to ten units can be connected in parallel. centralized and decentralized.1. In parallel mode there are two possible options of Static Switch operation. However. 3. 3x220 in. 3.User Guide Gamatronic Electronic Industries Ltd. 8 Parallel Operation (option) µPS-SP 3:3. if one UPS were to fail. in centralized parallel operatoin there is only one Static Switch (in a separate housing) for the entire system. Any normally functioning UPS can be the Master. a second option is available as a centralized Static Switch. The Master unit synchronizes its output voltage with the bypass phase and frequency. cable connections µPS-SP 3:3. Bus AC Output To Load UPS 2 Static Switch Output AC Input DC link Battery Control Figure 4: Decentralized Parallel µPS . It is a 15-pin cable that includes • • • Master/Slave logic path A path for the phase and frequency syncronization pulses Buses for active current sharing UPS 1 Bypass AC Input Static Switch Output DC link AC Input Battery Control AC Output Power Bus Parallel ST.Gamatronic Electronic Industries Ltd.SW. User Guide Special Cable for Parallel Operation Gamatronic provides a special cable for connecting the μPS SP units in parallel. 3x208 60 Hz out Parallel Operation (option) 9 . Bus Parallel Comm. 3x220 in. 3x208 60 Hz out . Bypass AC Input UPS 1 DC link AC Input Output Contactor Static Switch AC Output To Load Output Battery Bypass Reference .cable connections 10 Parallel Operation (option) µPS-SP 3:3.. 3x220 in.- Control AC Output Power Bus Parallel Comm.User Guide Gamatronic Electronic Industries Ltd. Bus UPS 2 DC link AC Input Output Contactor Output Battery Bypass Reference Control UPS N+1 DC link AC Input Output Contactor Output Battery Bypass Reference Control Figure 5: Centralized Parallel µPS . Figure 6: Control panel on the standard cabinet (10kVA to 60kVA models) µPS-SP 3:3. The description of the standard 10-60 kVA control panel begins in section 4. 3x208 60 Hz out Control Panel & Indicators 11 . according to cabinet type.1 on this page. 4. Textual information is presented on the LCD display. we discuss two control panels separately. 3x220 in. Because the control panel of the standard cabinet (used for the 10-60KVA models) differs in appearance from the console of the larger cabinet (an option for the 40-60 kVA models). These messages are often reinforced with audible alerts to alert the user of extraordinary circumstances.Gamatronic Electronic Industries Ltd. the control panel on the larger cabinet (option for 40-60 kVA models) is described beginning in section 4.1 The Control Panel on the Standard Cabinet The control panel has 6 round function buttons for controlling the unit and 12 square information buttons for reporting the status of the UPS. User Guide 4. Real time information is displayed visually and audibly. CONTROL PANEL & INDICATORS The control panel serves as an interface between the UPS and the user.2 on page 16. after which the LCD display reverts to the default STATUS display. putting the unit into BYPASS mode. the alarm returns to active mode. 4. alternatively. or from a remote location via a modem.User Guide Gamatronic Electronic Industries Ltd. manually taking the UPS out of BYPASS mode. Battery checks are automatically performed at the following times: Upon start-up Every 200 hours of accumulated operating time After battery cabinet reconnection (following a disconnection) INV INV Pressing the INV button connects the inverter to the output.1. The UPS maintains an event history in its log. 3x220 in. BATTERY TEST BATTERY TEST Pressing the BATTERY TEST button manually initiates a battery test. by a computer using the optional RS232 connection. and confirm the selection by pressing the B/P button a second time. 4. Note: The ALARM LED remains lit until the problem is resolved to notify users about the continued existence of a system fault. If another fault occurs.2 Information Buttons on the Standard Cabinet The UPS continually monitors its operational status. Note: There is no display associated with this action. 3x208 60 Hz out . If an alarm is triggered. Confirmation of this action is required. Wait approximately 2 seconds. B/P B/P Pressing the B/P button connects the mains to the output. The unit requires confirmation of this action. Wait 2 seconds. The user can display real-time information about this status by pressing the appropriate information button.1 BUTTON Function Buttons on the Standard Cabinet DESCRIPTION UPS OFF UPS OFF Pressing the UPS OFF button turns off the UPS. The unit also continuously checks the battery cabinet connection with the UPS. 12 Control Panel & Indicators µPS-SP 3:3. UPS ON UPS ON Pressing the UPS ON button turns on the UPS and sequentially displays the results of the start-up diagnostic tests ALARM OFF ALARM OFF Pressing the ALARM OFF button silences the alarm that sounds when there is a system fault. The log can be accessed by pressing the LOG button or. the information buttons (except for LOG and “?”) display information for approximately 10 seconds.1. and confirm it by pressing UPS OFF again. 3x208 60 Hz out Control Panel & Indicators 13 . 232 230 231 45 45 45 INV (Inverter) Press the INV button to display the unit's Inverter Voltage and Current. Sample LCD displays are presented below.Gamatronic Electronic Industries Ltd. the LCD display provides information for the R. S. User Guide Where appropriate. IN. NOTE: Input current current display is available as an option. IN (Input) Press the IN button to display the unit’s Input Voltage. and T phases and for voltage and current. BYP. 3x220 in. INV 230 231 230 45 46 45 µPS-SP 3:3. 230 230 231 B/P (Bypass) Press the B/P button to display the unit’s Bypass Voltage and Current. Otherwise. 3x220 in. OUT. BYP. OUT (Output) Press the OUT button to display the unit’s Output Voltage and Current. Note: Battery current display is also available as an option BATTERY 230V 14 Control Panel & Indicators µPS-SP 3:3. 3x208 60 Hz out .9Hz 49.User Guide Gamatronic Electronic Industries Ltd. INV. the inverter frequency is determined by the quartz oscillator and should be set at 50/60 Hz.9Hz The operating inverter frequency is determined by the bypass frequency when operating normally. 230 230 230 45 45 45 FREQ (Frequency) Press the FREQ button to display the unit’s Bypass and Inverter Frequency. BATT (Battery) Press the BATT button to display the battery voltage.FREQ.FREQ. 49. For status and fault analysis. and current time (HH:MM:SS). and HELP buttons are described in section 4. TEMPERATURE NORMAL LOG The LOG. UPS OK TIME 00548:05:40 Note: This is the default display. which begins on page 21. described on page 23. User Guide TIME Press the TIME button to display the unit’s current day/month (DD/MM). To set the proper time or date use the SET button.Gamatronic Electronic Industries Ltd. 3x208 60 Hz out Control Panel & Indicators 15 . see System Fault Diagnostics on page 25.3. SET. TEMP (Temperature) Press the TEMP button to display the status of the unit's thermosensors. 0 UPS OK 18/12 12:35:40 STAT (Status) Press the STAT button to display the unit’s status and accumulated working time (HHHHH:MM:SS). µPS-SP 3:3. 3x220 in. User Guide Gamatronic Electronic Industries Ltd.2 The Control Panel on the Larger Cabinet The control panel has 6 function buttons for controlling the unit and 12 information buttons for reporting the status of the UPS. 3x208 60 Hz out . 3x220 in. 4. Figure 7: Control panel on the larger cabinet (optional for 40–60KVA models) 16 Control Panel & Indicators µPS-SP 3:3. Confirmation of this action is required. Note: The ALARM LED remains lit until the problem is resolved to notify users about the continued existence of a system fault. µPS-SP 3:3. The unit also continuously checks the battery cabinet connection with the UPS.2 Information Buttons on the Larger Cabinet The UPS continually monitors its operational status. Wait approximately 2 seconds. Where appropriate. pressing the UPS ON/OFF button turns on the UPS and sequentially displays the results of the start-up diagnostic tests When the UPS is ON. When the UPS is in Bypass mode.2. after which the LCD display reverts to the default STATUS display.1 BUTTON Function Buttons on the Larger Cabinet DESCRIPTION UPS ON/OFF When the UPS is OFF. pressing the B/P INV button connects the inverter to the output. User Guide 4. 3x208 60 Hz out Control Panel & Indicators 17 . The log can be accessed by pressing the LOG button or. 3x220 in. putting the unit into Bypass mode. the information buttons (except for LOG and “?”) display information for approximately 10 seconds. S. or from a remote location via a modem. ALARM OFF Pressing the ALARM OFF button silences the alarm that sounds when there is a system fault. If an alarm is triggered. the LCD display provides information for the R. manually taking the UPS out of Bypass mode.2. If another fault occurs. pressing the UPS ON/OFF button turns off the UPS. Battery checks are automatically performed at the following times: Upon start-up Every 200 hours of accumulated operating time After battery cabinet reconnection (following a disconnection) B/P INV B/P INV When the UPS is in Inverter mode. The user can display real-time information about this status by pressing the appropriate information button. and T phases and for voltage and current. and confirm the selection by pressing the B/P INVbutton a second time. Note: There is no display associated with this action. The unit requires confirmation of this action. Wait 2 seconds. BATTERY TEST BATT TEST Pressing the BATTERY TEST button manually initiates a battery test. 4. pressing the B/P INV button connects the mains to the output. and confirm it by pressing UPS OFF again. the alarm returns to active mode.Gamatronic Electronic Industries Ltd. The UPS maintains an event history in its log. by a computer using the optional RS232 connection. alternatively. IN. 230 230 231 45 45 45 18 Control Panel & Indicators µPS-SP 3:3. 3x220 in.User Guide Gamatronic Electronic Industries Ltd. B/P (Bypass) Press the B/P button to display the unit’s Bypass Voltage and Current. INV. IN (Input) Press the IN button to display the unit’s Input Voltage. 230 230 231 45 45 45 INV (Inverter) Press the INV button to display the unit's Inverter Voltage and Current. 230 230 231 NOTE: Input current current display is available as an option. Sample LCD displays are presented below. BYP. 3x208 60 Hz out . the inverter frequency is determined by the quartz oscillator and should be set at 50/60 Hz.9Hz The operating inverter frequency is determined by the bypass frequency when operating normally. BATTERY 192V Note: Battery current display is also available as an option µPS-SP 3:3.Gamatronic Electronic Industries Ltd. FREQ. 3x220 in.9Hz INV. OUT. BYP. 49. BATT (Battery) Press the BATT button to display the battery voltage. User Guide OUT (Output) Press the OUT button to display the unit’s Output Voltage and Current. Otherwise. 230 230 231 45 45 45 FREQ (Frequency) Press the FREQ button to display the unit’s Bypass and Inverter Frequency.FREQ. 49. 3x208 60 Hz out Control Panel & Indicators 19 . TIME Press the TIME button to display the unit’s current day/month (DD/MM). UPS OK 0 01/11 14:23:01 STAT (Status) Press the STAT button to display the unit’s status and accumulated working time (HHHHH:MM:SS). described on page 23. see System Fault Diagnostics on page 25. For status and fault analysis. TEMPERATURE NORMAL 20 Control Panel & Indicators µPS-SP 3:3. 3x208 60 Hz out .User Guide Gamatronic Electronic Industries Ltd. and current time (HH:MM:SS). To set the proper time or date use the SET button. UPS OK TIME 00611:01:59 Note: This is the default display. TEMP (Temperature) Press the TEMP button to display the status of the unit's thermosensors. 3x220 in. which contains a history of the last 256 important events to occur to the UPS. To view the 1st window of a previous event. The display cycle is illustrated in Figure 8. and HELP Buttons for All Models This section describes use of the LOG. while the UPS was operating. Figure 9: Accessing the Log on the standard cabinet µPS-SP 3:3.3 The LOG. The first window to appear is the first part of the most recent fault. User Guide 4. To view the contents of the log: Press the LOG button to enter LOG mode. Press the arrow buttons to scroll through the information recorded in the log. from 10KVA to 60KVA. or to the input AC power or the load. The down arrow will show the second window. 1. Each log entry is two screens long. and HELP information buttons. 2. 3x220 in. Press the down arrow to view the second window of the event. Examples of logged events include machine startup and shutdown. 3x208 60 Hz out Control Panel & Indicators 21 . press the up arrow . which operate identically on all models of the UPS. SET TIME. SET. pressing the up arrow once again will show the 1st window of the event previous to that. AC input restore. Figure 8: LOG Messages Structure LOG Pressing the LOG button displays the unit’s event log.. a swich to Bypass or Battery mode.Gamatronic Electronic Industries Ltd. or a return to Normal mode. AC input failure. 3. The second screen shows the log number. 22 Control Panel & Indicators µPS-SP 3:3. 3x220 in. The first screen provides a description of the event with date and time. BATTERY LOW 0 01/11 14:23:01 Figure 10: Accessing the Log on the large cabinet Each log entry requires 2 screens that can be navigated using the up and down arrows. The log variables include typical UPS parameters for the event. listed in Table 1. 3x208 60 Hz out . variable values and fault results.User Guide Gamatronic Electronic Industries Ltd. fault 0009H = 0000000000001001 binary which translates as overload and battery test failure. SET (Time) Pressing this button sets the unit’s real-time clock (see “Setting the Real Time Clock” on page 33.Gamatronic Electronic Industries Ltd. battery low Other fault Faults are represented as a hexadecimal word comprising 16 bits: Bit 0: 1 = Overload Bit 1: Inverter Bit 2: Bypass Bit 3: Rectifier Bit 4: Input Bit 5: Phase sequence Bit 6: Temperature Bit 7: Battery test failure Bit 8: Output Bit 9: Load on bypass Bit 10: Circulation (for parallel) Bit 11: Slave receive failure (parallel only) For example. µPS-SP 3:3. 3x220 in. 3x208 60 Hz out Control Panel & Indicators 23 . User Guide Table 1: Log Variables Event Overload Inverter fault Bypass fault LOG Variable Sum of currents in all phases Vinv (average inverter voltage) in all phases Vbyp (average bypass voltage) in all phases where there is a bypass voltage fault or Hz (Frequency) where there is a bypass frequency fault Average Vin on all phases Temperature °C DC voltage Average Vout for all phases Input fault High temperature Rectifier fault. Single for one integral bar Input current meter: YES for specified option. To quit the help. 3x208 60 Hz out . "?" (Help Button) Pressing this button provides on-line configuration data for display purposes. 24 Control Panel & Indicators µPS-SP 3:3. 3x220 in. Note: Configuration can be modified in service mode only 1. NO as standard Date of manufacture: Format DD/MM/YY Date of last battery installation: Format DD/MM/YY Software version number 2. NO for stand-alone UPS Load LED bar: Triple for panel with 3 LED bars.) Serial number Nominal power Number of phases in and out Nominal input and output voltage between phase and neutral Voltage range of input and bypass Nominal output current per phase Nominal output frequency Frequency tracking range when the inverter is synchronized to the bypass Number of batteries connected in series Nominal capacity of each battery (for use in calculating backup duration where the battery current meter option is installed) DC shutdown voltage in battery discharge mode Bypass: YES for option with bypass. NO if shutdown is inhibited Par. Operation: YES for parallel UPS. model name etc. The following messages are presented: • • • • • • • • • • • • • • • • • • • • • • Model type: True on-line UPS. Use the UP and DOWN arrows to scroll through the information. NO as standard Battery current meter: YES for specified option.User Guide Gamatronic Electronic Industries Ltd. NO for DC/AC inverter Distance shutdown: YES if EPO and shutdown via interface alarm and RS232 are supported. NO for option without bypass Rectifier: YES for UPS. press the “?” button once again. The STATE byte indications are as follows: Bit 0: Bit 1: Bit 3: Bit 4: Bit 5: UPS power 1 = ON. press the down arrow . Byte 3 shows result of inverter symptoms analysis. Indications are as follows: Bit 0: Bit 1: Bit 3: Bit 7: 1 = Fault is in phase R 1 = Fault is in phase S 1 = Fault is in phase T 1 = Fault exists Byte 2 shows the result of bypass symptoms analysis. and 9 bytes are displayed on the panel: Byte 1 shows input diagnostics. Indications are as follows: Bit 0: 1 = Shutdown limit exceeded Bit 1: 1 = Alarm limit exceeded µPS-SP 3:3. 3x208 60 Hz out Control Panel & Indicators 25 . 0 = Enabled Load transfer 1 = In progress. Indications are as follows: Bit 0: Bit 1: Bit 2: Bit 3: Bit 4: Bit 6: Bit 7: 1 = Battery is currently discharging 1 = Battery is discharged 1 = Battery is disconnected 1 = Battery check failed 1 = Excessive current difference in battery sets. 0 = OFF Bit 1: Load supply 1 = On bypass. Indications are as per byte 1. 0 = OFF Load supply 1 = On bypass.4 System Fault Diagnostics Select the STAT button and press the down arrow .Gamatronic Electronic Industries Ltd. User Guide 4. each representing the STATE and the INSTRUCTION. Byte 4 shows output voltage diagnostics. 0 = Pending The INSTRUCTION byte indications are as follows: Bit 0: UPS power 1 = ON. Byte 5 shows DC voltage diagnostics. 0 = Pending Battery check 1 = In progress. make a note of the bit representations. 0 = On inverter Bit 5: Battery check 1 = In progress. 3x220 in. The display will show 2 bytes representing the FAULT (see LOG on page 21) followed by two bytes (each of 8 bits) are now on display. 0 = Pending To view fault condition details. 0 = On inverter Audible alarm 1 = Disabled. (Option) 1 = Rectifier failure 1 = Fault exists Byte 6 shows measured temperature diagnostics. To use the hexadecimal indicators. S and T using a half-scale offset. To view the active current sharing status. 3x208 60 Hz out . 3x220 in.User Guide Gamatronic Electronic Industries Ltd. Zero current is presented as 128. To view the register used for inverter voltage correction. press the down arrow . DC votage abd active current sharing conditions. depending on the load. With positive current this value increases. 26 Control Panel & Indicators µPS-SP 3:3. press the down arrow Iact Iavr IaR IavR IaS IavS IaT IavT Figure 11: Active Current Sharing I and Ia in Figure 14 show the results of active average current measurements on phases R. this value decreases. Indications are as follows: Bit 0: Bit 1: Bit 2: Bit 3: Bit 4: Bit 5: Bit 6: 1 = Transferring started 1 = Inverter is OFF 1 = Inverter restarting 1 = Inverter under diagnosis 1 = Switching to inverter – SRSW SCR is ON 1 = Switching to inverter – SRSW SCR is OFF 1 = System in wait state . Bit 2: 1 = Fault detected by bi-metal temperature sensor Bit 7: 1 = Fault exists Byte 7 shows bypass frequency diagnostics: Bit 0: 1 = Bypass frequency incorrect Byte 8 shows over-current diagnostics. Initial value of the correction registers is zero. Indications are as follows: Bit 0: Bit 1: Bit 2: Bit 7: 1 = Over-current detected in phase R 1 = Over-current detected in phase S 1 = Over-current detected in phase T 1 = Fault exists Byte 9 shows load transferring diagnostics. CORR RR RS RT Figure 12: Voltage Correction R in Figure 12 shows the contents of the correction register. with negative current. 3x208 60 Hz out Control Panel & Indicators 27 . They are color coded so that the user can easily and quickly identify areas for concern. and green indicates normal status and operation. Figure 13: LED Indicators on the standard cabinet Figure 14: LED Indicators on the optional larger cabinet The meaning of each of the LEDs is explained in Table 2. 3x220 in. µPS-SP 3:3. User Guide 4. Red indicates a fault or abnormal status (usually associated with an audible alarm).5 LED Indicators LED indicators provide at-a-glance information regarding the status or operation of the UPS.Gamatronic Electronic Industries Ltd. User Guide Gamatronic Electronic Industries Ltd. Table 2: LED Indicators LED BYPASS B/P OVERLOAD BATTERY SYNC CHARGER INVERTER INV LOAD LEVEL LOAD LEVEL MEANING Bypass Normal Output Connected to the Bypass Overload Battery Not Normal Synchronized Inverter Charger Operating Inverter Normal Output Connected to the Inverter Load Level Load Greater Than 100% COLOR Green Red Red Red Green Green Green Green Green Red 28 Control Panel & Indicators µPS-SP 3:3. 3x208 60 Hz out . 3x220 in. Wait 20 seconds. The UPS performs a self-test that takes approximately one minute. and 20KVA models the Battery circuit breaker is located on the UPS. OPERATING THE μPS SERIES UPS 5. 2. Verify that both the Output circuit breaker and the Maintenance Bypass circuit breaker are turned off 6. On the 10. Wait 1 minute and then turn on the BATTERY circuit breaker. If the Bypass voltage is acceptable the UPS connects the Bypass voltage to the output terminal. User Guide 5. While you are waiting. The unit then begins to construct the Inverter voltage. ''UPS OFF'' µPS-SP 3:3. On the 30– 60 kVA models. 5.1 Turning the UPS ON To turn the UPS ON: 1. Verify that the UPS OFF message is displayed on the LCD display after the test is completed. then turn on the Rectifier CB. Turn on the Static Switch Bypass circuit breaker. 3x208 60 Hz out Operating the μPS Series UPS 29 . 3x220 in. 15. 3. Press the UPS ON button on the front panel and wait approximately 40 seconds. 4. The message UPS ON PLEASE WAIT appears as the unit turns on. after which time it transfers to Inverter mode. then checks the Bypass voltage.Gamatronic Electronic Industries Ltd. the UPS turns on the Inverter. the Battery circuit breaker is found on the battery cabinet. The UPS is ready for use and begins charging the batteries. Connect the equipment to be protected by the UPS and verify that it is functioning correctly. and that "UPS OK" NO RED LED is lit. Turn OFF all the circuit breakers. Turn ON the UPS Output circuit breaker. 3x208 60 Hz out . Turn off all the loads connected to the UPS. press twice on the UPS ON/OFF button) 3. Verify that the message “UPS OK” appears on the LCD display. 3x220 in. “B/P” LED ”INV” LED is is OFF GREEN 8. 11. 10. The UPS executes an automatic "TIME XXXXXXXX" battery test for 1 minute. (On the large-cabinet model. 7.2 Turning the UPS OFF To turn the UPS OFF: 1. 9. 30 Operating the μPS Series UPS µPS-SP 3:3. 2. 5. Check the LED indicators to verify that the UPS is now in Inverter mode.User Guide Gamatronic Electronic Industries Ltd. Press twice on the UPS OFF button on the display panel. For UPSs with the optional Bypass Isolation Transformer. On the standard cabinet: press the B/P function button twice (see section 4.1 on page 17). 4.1 on page12. DO NOT turn off the Static Switch Bypass circuit breaker when using the Maintenance Bypass switch. 3x220 in. 2. To put the UPS into regular Bypass mode: • • 3. The Maintenance Bypass switch is locked in the OFF position with a small padlock or a protective cover. Turn on the MAINTENANCE BYPASS circuit breaker.) On the large cabinet (option for the 40 – 60 kVA models): press the B/P INV function button twice (see section 4. User Guide 5.3 Activating Maintenance Bypass The UPS includes a Maintenance Bypass switch which allows the UPS to be shut down for servicing without interrupting the loads. Verify that the SYNC and BYPASS LEDs are lit. To avoid accidental short-circuiting of the UPS output to the mains when entering or leaving Maintenance Bypass mode. 5. 6.Gamatronic Electronic Industries Ltd. For units WITHOUT the optional Bypass Isolation Transformer: turn off the Static Switch Bypass circuit breaker. The UPS must first be transferred to regular Bypass mode. 3x208 60 Hz out Operating the μPS Series UPS 31 . Turn off the OUTPUT circuit breaker. 8. be sure to follow these instructions in the order given! To avoid accidental disconnection of the load devices from AC power. Turn off the RECTIFIER and BATTERY circuit breakers. If they are not lit. !! !! !! To activate the MAINTENANCE BYPASS mode: 1. be sure to follow these instructions in the order given! NEVER lift the MAINTENANCE BYPASS circuit breaker without first putting the UPS in BYPASS mode (the red B/P light must be lit). WARNINGS !! !! The Maintenance Bypass switch should be operated by authorized personnel only. Press twice on the UPS OFF button on the display panel. the UPS cannot go into Bypass mode. µPS-SP 3:3. 7.1.2. Verify that the B/P LED is lit. 6. 5. 7. Press the UPS ON button (on the large-cabinet models. 32 Operating the μPS Series UPS µPS-SP 3:3. Verify that the B/P LED is lit. Turn on the RECTIFIER . STATIC SWITCH BYPASS. 3x220 in. 4. To avoid accidental short-circuiting of the UPS output to the mains when entering or leaving Maintenance Bypass mode. Verify that there are no LEDs lit on the display panel. Press twice on the B/P button to put the UPS into BYPASS mode.4 !! !! Deactivating MAINTENANCE BYPASS WARNINGS The Maintenance Bypass switch should be operated by authorized personnel only. 3. 5. Turn on the OUTPUT circuit breaker. DO NOT turn off the Static Switch Bypass circuit breaker when using the Maintenance Bypass switch. be sure to follow these instructions in the order given! To avoid accidental disconnection of the load devices from AC power.User Guide Gamatronic Electronic Industries Ltd. Verify that the message SELF-CHECK OK appears on the LCD. 10. 9. It is automatically followed by the message UPS OFF. The UPS can now be serviced. Verify that the OUTPUT circuit breaker is turned off. For UPSs with the optional Bypass Isolation Transformer. !! !! !! To deactivate MAINTENANCE BYPASS and restart the UPS: 1. The loads are now supplied by the UPS. be sure to follow these instructions in the order given! NEVER lift the MAINTENANCE BYPASS circuit breaker without first putting the UPS in BYPASS mode (the red BYPASS light must be lit). Turn off the MAINTENANCE BYPASS circuit breaker. Press on the INV button on the display panel to put the UPS in INVERTER mode. and BATTERY circuit breakers. the UPS ON/OFF button) and wait 40 seconds (approximately) until the UPS OK message appears on the LCD. 8. Verify that the green INV light is lit on the display panel. 2. 3x208 60 Hz out . Gamatronic Electronic Industries Ltd. User Guide 5.5 After Use of the Emergency Power-Off Switch After use of the optional Emergency Power-Off switch, the UPS must be restarted as follows: 1. Return the Emergency Power-Off switch to its normal position (N.C.). 2. Turn off all of the ciruit breakers: • • • • Output CB Static Switch CB Battery CB Charger CB. 3. After turning off the circuit breakers, wait for 30 to 60 seconds. The UPS can now be turned on as described in Section 5.1, “Turning the UPS ON”, on page 29. 5.6 Setting the Real Time Clock The real time clock is composed of the date and time fields and may be set by the user. The date field contains three subfields (DD/MM/YY) and the time field contains two subfields (HH:MM). To set the real time clock: 1. Press the TIME button to enter the time mode. The normal TIME display is shown on the LCD panel. 2. Press the SET button to initiate setting mode. The year is presented as 2 digits. 3. Press the SET button to increase the value. 4. Press the up arrow to continue with the settings, setting month [1-12], day [1-31], hour [0-23] and minutes [0-59]. µPS-SP 3:3, 3x220 in, 3x208 60 Hz out Operating the μPS Series UPS 33 User Guide Gamatronic Electronic Industries Ltd. 6. COMMUNICATIONS The UPS is connected to a computer or a modem using a shielded cable, with an RS232-type 9-pin female connector. Maximum allowed cable length is 15 meters. There are two types of UPS connections: • • Directly to a host computer with dedicated software. Remote monitor through a SNMP/WEB management programs for communication with a computer network (optional). LOCAL DIRECT CONNECTION 6.1 RS232 Interface The UPS supports standard UPS protocol. Full information about the status of the UPS, the value of its parameters, and the memory events log is displayed on a userfriendly graphic interface. The graphic interface also allows you to use the host computer to execute a set of instructions for the UPS that includes shutdown, restart, battery check, etc. Communication parameters: COM RS232 Tx Rx • • • • 2400 Baud rate No parity 1 stop bit No flow control 9 6 5 1 SIGNAL RD TD GND UPS 2 3 5 Table 3: RS232 Connector Pin Assignment 34 Communications µPS-SP 3:3, 3x220 in, 3x208 60 Hz out Gamatronic Electronic Industries Ltd. User Guide 6.2 The Alarm Interface The following diagram describes the Alarm Interface µPS-SP 3:3, 3x220 in, 3x208 60 Hz out Communications 35 Its LEDs are color coded.User Guide Gamatronic Electronic Industries Ltd. 6. Figure 15: Remote Monitor Box The monitor panel on the front of the monitor box displays audio and visual information about the condition of the UPS. and the load. 3x220 in. 3x208 60 Hz out . the mains.3 Remote Monitor Box (Optional) The remote monitor box can be located a maximum distance of 50m from the UPS. It is directly connected to the UPS with a 4-wire cable connected to the REMOTE MONITOR interface of the UPS. The meaning of each of the LEDs is explained in the following table: LED BYPASS BYPASS B/P OVERLOAD BATTERY BATTERY CHARGER CHARGER INVERTER INVERTER INV LOAD LEVEL LOAD LEVEL UPS ON ALARM OFF SYNC MEANING Bypass Normal Fault in Bypass Output Connected to the Bypass Overload (Load more than 100%) Battery Faulty Battery Normal Input voltage is OK Input voltage is not OK Inverter is OK Inverter is faulty Output Connected to the Inverter Load Level Load Greater Than 100% UPS is activated Fault in the system Bypass voltage is synchronized with Table 4: LED Indicators on Remote Monitor Panel COLOR Green Red Red Red Red Green Green Red Green Red Green Green Red Green Red 36 Communications µPS-SP 3:3. Attach the back of the monitor box to the wall. height -135 mm. 3x220 in.200mm.Gamatronic Electronic Industries Ltd. The cable is attached to the side of the monitor box with two screws. µPS-SP 3:3. 2. DB9 Row of Terminals The measurements of the Monitor box are: Length . User Guide The monitor panel also contains buttons for controlling the UPS which are described in the following table: BUTTON UPS ON UPS OFF INV B/P BATTERY TEST ALARM OFF PURPOSE Not in use Not in Use Manually switches the load from the bypass to the inverter Manually switches the load from the inverter to the bypass Manually starts a battery test Silences the audible alarm Table 5: Control Buttons on Remote Monitor Panel 6. The UPS PC908 board in the monitor box is connected to the PC021 board on the rear panel of the UPS with a 4-wire cable connected to the appropriate 1-4 Pin male or female DB9 connector terminal in the UPS’ row of terminals. 3. and distance between the screws on the back of the box .3.265mm.1 Connecting the Monitor Box to the UPS 1. 3x208 60 Hz out Communications 37 . Corrects itself automatically when the input voltage stabilizes or returns. BYPASS FREQ. 7. The load transfers from bypass to inverter when the load is corrected. and one of the following emergency messages appears on the LCD: MESSAGE BATTERY LOW INPUT FAULT STATE Battery is low Input voltage is too low. the technician should perform the following: 38 Troubleshooting µPS-SP 3:3. B/P FAULT Bypass voltage is too high.User Guide Gamatronic Electronic Industries Ltd. Self-test has a negative result DC voltage is faulty Table 6: Trouble Shooting and Problem Solving Note: The following procedures are relevant in cases where the unit is not operating normally and there are no LCD display panel messages. Make up to 7 attempts to reconnect to the inverter. NOT CONNECT Malfunctioning inverter Over temperature Battery is not connected BATTERY UNDER LOAD Power failure. No input voltage Bypass voltage is too low. 3x208 60 Hz out . Over 90° paralyzes the inverter’s action and transfers the load to bypass. COMMENTS INVERTER FAULT OVER TEMPERATURE BATT. Call service technician Call service technician Corrects itself automatically when the bypass voltage stabilizes or returns. No bypass voltage OVERLOAD Overload The unit goes to bypass and stays that way as long as there is an overload. In the event that the unit has stopped operating in a normal manner. Works on an independent frequency of the inverter and will synchronize back when the frequency will return to normal. 3x220 in. FAULT FAULT CONDITION SERVICE REQUIRED RECTIFIER FAULT The frequency bypass exceeds the allowable limits. A slow beep indicates that the battery is starting to discharge. Input voltage is too high. a warning beep sounds. and the display panel is not functioning. TROUBLESHOOTING If unit stops operating normally. These procedures are to be performed ONLY BY A TRAINED TECHNICIAN. Check the status of the battery switch and the connections to the batteries. Inverter operating on batteries. A fast beep and a TEST BATT light indicates that the battery has almost finished discharging. a red alarm light (ALARM) flashes. It returns automatically to normal operation only after the temperature goes below 55°. User Guide START A 1 Turn ALL UPS switches OFF 10 Check all board connectors are secure 2 Wait 5 minutes and restart the UPS 11 Check IC2 on PC901 is securely seated in socket 3 UPS operating properly? 12 YES Correct the problem Problems? NO 4 YES END Turn all UPS and battery cabinet switches OFF NO Disconnect UPS from the AC input (mains) 13 Connect UPS to AC input and turn charger switch ON 5 14 Check voltages between UPS chassis and points on voltage chart 6 Wait 5 minutes and make sure no control panel indicators are lit 15 YES Replace PC901 Voltages within specifications? NO Replace PC921 or PC971 7 Remove UPS cabinet right and left panels 8 Connnect DC voltmeter across C101 and wait for discharge to 5V 16 YES Is there a display on the LCD? NO Replace PC950 LCD 9 Check for burned or damaged components END A µPS-SP 3:3.Gamatronic Electronic Industries Ltd. 3x220 in. 3x208 60 Hz out Troubleshooting 39 . Table 7: PC Board Check Points & Voltage Ranges BOARD PC 801 PC 800 PC 800 CHASSIS CHECK POINT TP10 P13/1 P13/2 VOLTAGE 5V ± 5% 12V ± 5% 12V ± 20% 40 Troubleshooting µPS-SP 3:3. 3x208 60 Hz out . 3x220 in.User Guide Gamatronic Electronic Industries Ltd. Battery life can be extended by ensuring a cool operating site. 3x220 in. In altitudes above 2000 m. in which case 20 cm of free space at the sides of the unit is adequate. Humidity must be less than 95% non-condensing. For the 80K cabinet. note of the following: 1) 2) 3) 4) Select a well ventilated and dust-free site that is conveniently located to both the electrical closet and the desired load. Note: These instructions make reference to two types of UPS cabinets. There must be a minimum of 1 meter of free space in front of the UPS for service accessibility. 5) 6) Make sure that the air vents are not obstructed. for ventilation and to allow connection of required cables. consistent with logical equipment arrangements and in compliance with NEC and local electrical codes. 20cm of free space is required at the sides of the UPS. the UPS rating is reduced. it bears no relationship to UPS capacity) is shown on the right side of the cover illustration of this book.Gamatronic Electronic Industries Ltd. The recommended ambient temperature for operation is 15-25°C (59–77°F). Use the shortest possible output distribution cable runs at the installation site. the “20B” cabinet is shown on the left side of the cover. computer monitor. Allow space for future equipment additions. There must be sufficient free space at the sides of the UPS. Make sure that the room temperature does not exceed 40ºC. 60 to 70 cm of free space is required unless the cabinet is equipped with wheels. To ensure long-term trouble-free operation. for service accessibility. The “80K” cabinet (this is just the cabinet name. 3x208 60 Hz out Site Preparation 41 . SITE PREPARATION Electrical codes may vary according to location. 8. and Federal electrical codes for acceptable external wiring practices. For the 20B cabinet.) at least 1 meter from the UPS. The permitted ambient temperature range for operating the UPS is 0–40°C (32–104°F). etc. You must maintain at least 40 cm of free space at the rear of the UPS. Both UPS operation and battery charging generate heat. state. (6560 ft). 7) 8) 9) 10) The route and foundation to the installation site must be capable of supporting the weight of cabinets and moving equipment. Observe all local.1 Installation Considerations The UPS is designed to operate under varied environmental conditions. Place electrical equipment (load. Plan the route to ensure that the µPS-SP 3:3. User Guide 8. 8. For minimum conductor size. separate conduit or cable tray. Verify that control wiring is run in an individual. 3) 4) Figure 16: External circuit breakers 42 Site Preparation µPS-SP 3:3.User Guide Gamatronic Electronic Industries Ltd. 3x208 60 Hz out . See Figure 16 on page 42 and Table 8 on page 43 for the proper circuit breaker ratings. 3x220 in. (Please check your local electrical codes to verify compliance with the given grades. and doorways without damage. corners. which has been prepared in accordance with NEC requirements. Refer to Table 10 on page 54 for specific information about cabinet size and weight. separate conduit. Use of appropriately rated external circuit breakers on the lines from the electrical supply board to the UPS and from the UPS to the distribution board is critically important. Use of appropriately rated cables between the electrical supply board and the UPS and between the UPS and the distribution board is critically important. unit will pass through all elevators. 11) Heat output of UPS equipment is significant. Make sure that environmental conditioning systems can accommodate this heat load. even during utility outages. refer to Table 9 on page 43.2 1) 2) Electrical Wiring Verify that power wiring is run in an individual.) Be sure to observe proper phase sequence when connecting the electrical supply board to the UPS. µPS-SP 3:3. 3x208 60 Hz out Site Preparation 43 .Gamatronic Electronic Industries Ltd.12 on page 7). 2. S1. S3 are 3-phase ac circuit breakers. S2. This applies for all UPS models described in this book. use 2 wires of 1 mm2 cross-section each. User Guide Table 8: External circuit breakers – required minimum ratings UPS Model 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Notes: CB S1: Input to Rectifier 3 x 50 A 3 x 80 A 3 x 100 A 3 x 160 A 3 x 200 A 3 x 250 A 3 x 250 A CB S2: Bypass Input 3 x 40 A 3 x 63 A 3 x 80 A 3 x 120 A 3 x 160 A 3 x 200 A 3 x 250 A CB S2: Output from UPS 3 x 32 A 3 x 50 A 3 x 63 A 3 x 100 A 3 x 120 A 3 x 160 A 3 x 200 A CB S4: Battery Cabinet 63 A 80 A 120 A 160 A 250 A 300 A 300 A 1. 3x220 in. S4 is a dc circuit breaker rated at 250 Vdc Table 9: Wiring requirements UPS Model 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Rectifier Input 3 x 10 mm2 3 x 16 mm2 3 x 25 mm2 3 x 50 mm2 3 x 70 mm2 3 x 70 mm2 3 x 70 mm2 Bypass Input 3 x 6 mm2 3 x 10 mm2 3 x 16 mm2 3 x 25 mm2 3 x 30 mm2 3 x 50 mm2 3 x 50 mm2 UPS Output 3 x 6 mm2 3 x 10 mm2 3 x 16 mm2 3 x 25 mm2 3 x 30 mm2 3 x 50 mm2 3 x 50 mm2 Battery 16 mm2 16 mm2 35 mm2 50 mm2 70 mm2 70 mm2 70 mm2 For the Emergency Power-Off switch (see section 2. 3x220 in.User Guide Gamatronic Electronic Industries Ltd.3 Terminal Connections TERMINALS FOR 10-20KVA MODELS (WITH INTERNAL BATTERIES) TERMINAL FOR 30-60KVA MODELS Figure 17: Terminal Connections 44 Site Preparation µPS-SP 3:3. 8. 3x208 60 Hz out . input.3 and 5. 9. 3x208 60 Hz out Installation 45 . 3x220 in. output. Installation of a parallel UPS system is done by qualified technical personal authorized by Gamatronic.Gamatronic Electronic Industries Ltd. • • • Rectifier CB Static Switch Bypass CB Output CB The UPS also has a Maintenance Bypass switch.4. All connections—connection panel. Cables should be introduced from the bottom of the UPS. A signal cable and software EPROM chip are required for this installation (Contact Gamatronic for details). INSTALLATION 9. Figure 18: Circuit breakers on the 10-20KVA models µPS-SP 3:3. User Guide 9. This switch must only be operated by qualified technical personnel and according to the special procedures described in 5.1 Accessibility All access to the UPS is through the front of the unit. and static switches—are accessed by opening the front door of the UPS and removing the lower protective panel to reveal the terminal block.2 Circuit Breakers The UPS has three automatic circuit breakers that are accessible via the front of the unit. 3x220 in.User Guide Gamatronic Electronic Industries Ltd. 3x208 60 Hz out . Figure 19: Circuit breakers on the 30-60 kVA models 46 Installation µPS-SP 3:3. 6.Gamatronic Electronic Industries Ltd. Connect the Emergency Power-Off switch to the Emergency Power-Off terminals using a 2-wire cable with each wire having a cross-section of 1 mm2. Use of a large. Connect one electrical supply cables to the Rectifier AC Input. Turn off ALL the circuit breaker switches: Rectifier CB Static Switch Bypass CB Output CB Battery CB Maintenance Bypass CB (should already be off) 4. 3x220 in.3. 3x208 60 Hz out Installation 47 . Connect the other end of the cable to the distribution board or to a load device or a dummy load. mushroom-type NC (normally closed) pushbutton rated at 25VCD. 5. Connect a cable to the UPS’s AC Output terminal. Be sure correct phase sequence is followed. according to your location’s requirements. µPS-SP 3:3.3 9. An Emergency Power-Off switch can be installed to enable immediate shutdown of the UPS. User Guide 9. external. 2. Connect a separate electrical supply cable and Bypass AC Input terminals of the UPS. is recommended. Ensure that the circuit breakers for all lines from the electrical supply board are OFF. • • • • • Note: It is critically important that the Rectifier AC Input and Bypass AC Input are fed from different points of the electrical supply board. Check for zero voltage on all lines before continuing. Remove the lower access panel or protection cover. Use the proper wire grades. 3.1A minimum. 7. Connect a ground cable to the UPS ground terminal or ground bus 8. see Table 8 on page 43. as listed in Table 9 on page 43.1 Installation of Standalone UPS Wiring/Cabling Instructions 1. 0. For required circuit breaker capacities. each with its own separate circuit breaker. Open the front access door using a flathead screwdriver to turn the lock. 3x208 60 Hz out . Connect the battery cabinet to the UPS with a 3-wire cable (plus. Connect the battery cabinet to the appropriate terminals of the UPS as shown in Figure 17. The UPS batteries supply a nominal voltage of 192VDC.2 External Battery Cabinet This section is relevant for all models of the UPS. a Battery Test results in a Battery Low alarm. on page 44. The Battery Test function can be used to monitor the status of the battery circuit breaker. 2.3. 3. EXTERNAL BATTERY CABINET UPS + 192VDC Battery Terminals UPS GROUND BUS Battery Test Terminals Battery Test Terminals Figure 20: Connecting the external battery cabinet 48 Installation µPS-SP 3:3. Be sure to use the proper grade of wire as listed in Table 8 on page 43. 4. 9. See Figure xx. The circuit breaker should be a 2-pole type. ground). An external circuit breaker should be installed between the battery cabinet and the UPS. 3x220 in. using a 2-wire cable with each wire having a cross-section of 1 mm2. minus. The battery cabinet houses 16 batteries of 12V each. The battery circuit breaker should be connected between the Auxiliary terminal of the battery cabinet and the Battery Test terminal of the UPS. When the circuit breaker is open. rated at 250VDC or better. and according to the schematic in Figure 20. 1.User Guide Gamatronic Electronic Industries Ltd. Measure to insure that you have the indicated voltage at the UPS’s Bypass Input terminals: Between R and N Between S and N Between T and N Between N and Gnd Between R and S Between S and T Between T and R Between N and Gnd 208V ± 10%. Turn ON the UPS’s STATIC SWITCH BYPASS circuit breaker. Verify that all the circuit breakers on the UPS are turned OFF 2. 160Hz 1V maximum! 5. Measure to insure that you have the indicated voltage at the UPS’s Rectifier and AC Input terminals: Between R and S Between S and T Between T and R 220V ± 10%. then turn on the UPS’s RECTIFIER circuit breaker. 3. Verify that both the Output CB and the Maintenance Bypass CB are turned off.3 Turning On the UPS for the First Time 1. The UPS performs a self-test (that takes approximately one minute). 8. then turn on the UPS’s BATTERY circuit breaker. 60Hz 4. User Guide 9. 6. Wait twenty seconds. WAIT one minute. 60Hz 1V maximum! 208V ± 10%. 3x220 in. Verify that the self-test takes place and that the UPS OFF ''UPS OFF'' message is displayed on the LCD screen when the self-test is completed. µPS-SP 3:3.Gamatronic Electronic Industries Ltd. Turn ON the circuit breakers on the electrical supply board.3. 3x208 60 Hz out Installation 49 . 7. The UPS is ready for use and begins charging the batteries. then checks the Bypass voltage. 3x220 in. 3x208 60 Hz out . Connect the equipment to be protected by the UPS and verify that it is functioning correctly. Check the LED indicators to verify that the “B/P” LED is OFF ”INV” LED is GREEN UPS is now in Inverter mode. 12. Turn ON the UPS Output circuit breaker. and wait 60 seconds before proceeding to the next step. 9. after which time it transfers to Inverter mode. 10. 50 Installation µPS-SP 3:3. The unit then begins to construct the Inverter voltage. and that NO RED LED is lit 13. Verify that the message “UPS OK” appears on the LCD display.User Guide Gamatronic Electronic Industries Ltd. Measure to insure that the following voltages are present at the UPS output terminal: BETWEEN R and S S and T T and R 208V ±2% VOLTAGE 15. Press UPS ON. The UPS executes an automatic battery test for 1 minute. While you are waiting. 11. 14. the UPS turns on the Inverter. If the Bypass voltage is acceptable the UPS connects the Bypass voltage to the output terminal. User Guide 9.4 Installation of Decentralized Parallel Systems The installation of two or more μPS-SP UPSs in Decentralized Parallel mode starts with the individual installation of each of the UPSs. The rectifier source can be different for each unit. with the same phase order. The UPSs are installed as for Standalone mode (see section 9. The units are connected with the Gamatronic-supplied parallel communication cable. When in operation. 3x208 60 Hz out Installation 51 . µPS-SP 3:3. The output cables are connected to a common bus with the identical phase order.Gamatronic Electronic Industries Ltd. • • • • • The same bypass source is used for each unit. if desired.3 beginning on page 47) with the following differences. the other UPSs do the same. 3x220 in. if any of the UPSs decides to transfer to bypass mode. Leave the output circuit breakers of each UPS OFF. Verify that the “SLAVE MODE” message appears on the LCD screen of the Slave UPS when you press the STAT button. 2.SW terminals are located on the bottom of the UPS adjacent to the other terminals. Start up one of the UPSs using the procedure described in “Turning On the UPS for the First Time” on page 49. 12. 13.SW input. Turn ON the Output circuit breaker of the Master UPS. 10.5. Verify that both UPSs are connected to the same bypass source and with the same phase sequence. and connecting the cables to the rectifier input. On the Master UPS.1 on page 8. 3x220 in. 2 to 2 and 3 to 3). 14. 9. Check the status LEDs to verify that both UPSs have transferred to bypass mode.5 Parallel Start-Up This section describes the start-up procedure for parallel UPSs. 52 Installation µPS-SP 3:3. maintenance bypass output and batteries. on both UPSs. 3.COM.1. 8. Verify that all circuit breakers are turned off in both UPSs. transfer the load to BYPASS by pressing the B/P button twice. Verify that the following voltage differences exist between the Bypass AC Input terminals of the two units: V(R-R) V(S-S) V(T-T) V(N-N) ≤500 mvAC ≤500 mvAC ≤500 mvAC ≤500 mvAC 9. Verify that the parallel communication cable is securely connected to the D15 female connector labeled as PAR. 11. perform the following steps: 1. Start up the second UPS using the procedure described in “Turning On the UPS for the First Time” on page 49. Transfer the Master UPS back to INVERTER mode by pressing the INV button once. 4. ST. 3x208 60 Hz out . 9. 7. after successfully completing the installation procedure. please refer to section 3. Verify that the “MASTER MODE” message appears on the LCD screen of the Master UPS when you press the STAT button. The PAR. 5.User Guide Gamatronic Electronic Industries Ltd. Make sure that the three PAR ST. For a technical description of the parallel scenario. the “INV” LED should be off. 6.1 Decentralized (2 UPSs only) To start-up both UPSs. The “B/P” LED should be red. ST.SW bus terminals in both UPSs are connected to each other in the correct order (1 to 1. UPS Model Inom 10 kVA 3A 15 kVA 4A 20 kVA 5A 30 kVA 8A 40 kVA 10 A 50 kVA 12 A 60 kVA 16 A 17. 3x208 60 Hz out Installation 53 .T) should be less than 10% Inom.Gamatronic Electronic Industries Ltd. 16. as shown in the table. 3x220 in. Measure to insure that the following voltages are present at the UPS output terminal: BETWEEN R and S S and T T and R 208V ±2% VOLTAGE 18.S. µPS-SP 3:3. Start to connect loads and verify that both UPSs are automatically sharing the load equally. The current for each phase (R. Measure the output current of the Master UPS. Turn ON the Output circuit breaker of the Slave UPS. User Guide 15. ± 1.F. 1000 % 1 cycle 0. 3x220 in. TECHNICAL SPECIFICATIONS Table 10: Technical Specifications MODEL INPUT 3 Phase X Voltage range Frequency Power walk-in Power factor (PF) OUTPUT Voltage (V) Free-running freq. 150 % 30 sec.5 15 12 90 1333 92.9 with optional filter 40 32 90. 0. 10. 125 % 10 min.User Guide Gamatronic Electronic Industries Ltd. Balanced load ±1 o 10 K 15 K 20 K 30 K 3 x 220 Vac ±20 % 57-63 Hz 12 sec. sealed lead-acid.5. (Hz) Power (kVA) (KW) Efficiency ac-ac (%) Dissipation (W) at full load (1W = 3.8 sinusoidal 3:1 Less than 2 % (at linear load) Overload and short circuit 2% Less than 0. tracking range Slew rate Overload Load P. maintenance-free Approximately 6-8 hours 54 Technical Specifications µPS-SP 3:3. ± 4 Hz (selectable) 1 Hz/sec.5 msec. Waveform Crest factor Total harmonic distortion Protection Dynamic response to 100% load change Transition time: to and from line 10 8 90 888 92.1 % 30 24 90.8 standard. 40 K 50 K 60 K 0..4 BTU) Inverter efficiency at 100% load (%) Regulation Freq. ± 3.5 3360 94 50 40 91 3956 94 60 48 91 4750 94 Phase deviation Rejection ratio BACKUP OPERATION Backup time Floating dc voltage Nominal dc voltage Batteries (12 Vdc each) Battery recharge time More than 100 dB As per customer specifications 216 Vdc 192 Vdc External. ± 2.5 2520 94 ± 1% ± 0.. 3x208 60 Hz out .5 20 16 90 1580 93 3 X 208 Vac 60 ±0. 000 hours. non-condensing 1500 m w/o derating EN50091-1 EN50091-2 ENV50091-3 100. larger cabinet available. User Guide MODEL COMMUNICATION OPTIONS RS232 Alarm Remote indication panel SNMP LCD DATA Input Output & Inverter Bypass Batteries Temperature Log (events memory) ENVIRONMENT & OTHER Ambient temperature: Operating permitted optimum Storage Relative humidity Altitude UPS Standard General & Safety EMC Design MTBF Audible noise (dB) at 1.. 250. current. monitor Shutdown software Optional Optional Voltage Voltage. 50. 3x208 60 Hz out Technical Specifications 55 . and 60 kVA models have an optional. µPS-SP 3:3.5* 111* 650 750 * The 40.Gamatronic Electronic Industries Ltd.000 hours with static switch 60 62 65 67 o o 95 45 85 250 300 350 450 500 130* 55. frequency Voltage & frequency Voltage Heatsink Last 256 events 0 to 40 C (32 to 104 F) o o 15 to 25 C (59 to 77 F) o o -20 to 60 C (-4 to 140 F) 95 % max. measuring 190 cm (h) x 70 cm (w) x 80 cm (d).5 m DIMENSIONS * Height (cm) Width (cm) Depth (cm) Weight (kg) w/o batteries 10 K 15 K 20 K 30 K 40 K 50 K 60 K Shutdown. 3x220 in.
Copyright © 2024 DOKUMEN.SITE Inc.