External alarm implementation

March 24, 2018 | Author: Farid Abbasi | Category: Rectifier, Relay, Electric Power, Electrical Equipment, Equipment


Comments



Description

内部公开 Internal Use Only▲New Site External alarm implementation guide For new site External we have two scenario: 1. ZTE ODU External Alarm Configuration (With Sceco) 2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset) ZTE ODU External Alarm Configuration (With Sceco) Alarm Designation No. 1 Door Cabinet Open(WHITE / DDF SLOT 1 BLUE) 2 High Temperature(WHITE / Tower Light Failure 2 Rectifier Alarm (WHITE / 3 AC Power Fail(WHITE / GRAY) Connected directly to Sensor - DDF 2 - BBU SA Connected directly to Sensor - DDF 3 - BBU SA BBU SA Card 4 BROWN) 5 Sensor - DDF 1 - BBU SA BBU SA Card Alarm(WHITE / GREEN) 4 Connected directly to Connection BBU SA Card ORANGE) 3 Remarks From B201 SIB Board X15 - DDF 4 - BBU SA (Power Unit) - X15 port 5 From B201 SIB Board X16 - DDF 5 - BBU SA (Power Unit) - X16 port 6 Environmental Over 6 Humidity(RED / BLUE) 7 DC Low Voltage alarm(RED / SMOKE Alarm(RED / Green) X16 - DDF 6 - BBU SA (Power Unit) - X16 port 7 ORANGE) 8 From B201 SIB Board From B201 SIB Board X17 - DDF 7 - BBU SA (Power Unit) - X17 port 8 From B201 SIB Board X17 - DDF 8 - BBU SA (Power Unit) - X17 port <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved, No Spreading abroad without Permission of ZTE 第1页 内部公开 Internal Use Only▲ ZTE ODU External Alarm Drawing (With Sceco) ODU Cabinet Door 1 sensor Door open alarm DDF Port 1 Door 2 sensor AC1(1500W) alarm cable High tep.it very important for test external alarm. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved.all external alarm sensor should be connect to SA card through DDF terminal.before connect sensor. No Spreading abroad without Permission of ZTE 第2页 .please make loop back test from DDF to OMC. Alarm DDF Port 2 AC2(1500W) alarm cable AC3(500W) alarm cable Smoke alarm DDF Port 8 SA card (BS8800) D D F B201 Module B201 X17 Port(NC/COM) B201 X24 Port Rectifier alarm DDF Port 4 B201 X15 Port(NC/COM) AC power fail alarm DDF Port 5 B201 X16 Port(NC/COM) Environmental over humidity alarm DDF Port 6 B201 X16 Port(NC/COM) DC Low voltage alarm DDF Port 7 virtual Actual Smoke sensor B201 X17 Port(NC/COM) Tower Medium light alarm cable Tower Light Failre Alarm DDF Port 3 Control box Junction box Low light alarm cable Low light alarm cable NodeB(BS8800) part: SA card (BS8800) D D F For New site External alarm we through BS8800 SA card report to EMS/OMC. External alarm connection : SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor 1.make sure 8channel no any cross. 内部公开 Internal Use Only▲ 2. No Spreading abroad without Permission of ZTE 第3页 .SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable We used core color(new) <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. 内部公开 Internal Use Only▲ 3. No Spreading abroad without Permission of ZTE 第4页 .connection picture: <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. No Spreading abroad without Permission of ZTE 第5页 . Door Cabinet Open(WHITE / BLUE)(in DOU cabinet) ODU Cabinet SA card (BS8800) Door open alarm DDF Port 1 Door 1 sensor Door 2 sensor D D F Door1 and Door2 Sensor cable need parallel connect to DDF port1 Door 1 Sensor : Door2 Sensor Door 1&Door 2 Sensor cable : <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved.内部公开 Internal Use Only▲ No1. AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM) <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. Alarm DDF Port 2 AC1(1500W) alarm cable AC2(1500W) alarm cable AC3(500W) alarm cable SA card (BS8800) D D F AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2 1. No Spreading abroad without Permission of ZTE 第6页 .内部公开 Internal Use Only▲ No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet) ODU Cabinet High tep. AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM) 4.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM) 3.内部公开 Internal Use Only▲ 2. No Spreading abroad without Permission of ZTE 第7页 .alarm cable in ODU location <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. For detail connection please reference installation and operation manual in the box. From Control box alarm output connect to DDF port3 terminal.内部公开 Internal Use Only▲ No 3. From Junction box connect to Control box alarm input terminal. No Spreading abroad without Permission of ZTE 第8页 .Tower Light Failure Alarm(WHITE / GREEN)-on tower SA card (BS8800) D D F Tower Medium light alarm cable Tower Light Failre Alarm DDF Port 3 Control box Junction box Low light alarm cable Low light alarm cable Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3 Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal. <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. No Spreading abroad without Permission of ZTE 第9页 . <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. AC Power Fail(WHITE / GRAY) No 6. Rectifier Alarm (WHITE / BROWN) No 5.DC Low Voltage alarm(RED / ORANGE) SA card (BS8800) D D F Rectifier alarm DDF Port 4 B201 X15 Port(NC/COM) AC power fail alarm DDF Port 5 B201 X16 Port(NC/COM) Environmental over humidity alarm DDF Port 6 DC Low voltage alarm DDF Port 7 B201 X16 Port(NC/COM) B201 X17 Port(NC/COM) Rectifier Alarm From X15 NC/COM connect to DDF port4 AC Power Fail From X16 NC/COM connect to DDF port5 Environmental Over Humidity From X16 NC/COM connect to DDF port6 DC Low Voltage alarm From X17 NC/COM connect to DDF port7 Below description detail how to setting external alarm in ZXDU68 B201 system.内部公开 Internal Use Only▲ No 4. Figure as below: shown the board layout.Environmental Over Humidity(RED / BLUE) No 7. About the relay alarm of the ZXDU68B201 power supply system The boards of the zxdu68 B201system is integrated in the signal transfer box. 6 Then the relays alarm function need to three interface: X15、X16、X17.4 X26 Intrusion alarm X17 Out relays 5. Modem power board(MPB). Figure signal board: Table signal interface name Interface Interface name X4 Battery 1 temperature Interface Interface name X21 RS485 interface X5 Battery 2 temperature X22 Rs232 interface X12 Temperature control X23 Flood alarm X14 Input relays 1. Network interface board(IP/SNMP).内部公开 Internal Use Only▲ 1. Signal interface board(SIB) And the signal interface board provides external communication interfaces and monitoring unit signal interfaces. 3.2 1 2NO Relay output 2-NO(normally open) A3 2 2COM Relay output 2-Common end A3 3 2NC Relay output 2-NC(normally closed) A3 <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. No Spreading abroad without Permission of ZTE 第 10 页 .2 X25 Ambient temperature X16 Out relays 3.4 X24 Smoke alarm X15 Out relays 1.3. The signal board is shown in figure as below. 2. So the relays alarm function of the signal interface definition as belowTable-1: Interface Pin Signal definition Signal description Relay alarm definition (monitor parameters) X15 Output relays 1.2. Refer to table for the signal board interfaces description. <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. another terminal connect with the BTS interface. until it finished. So need to know the BTS interface alarm definition which it is NO or NC.6 4 1NO Relay output 1-NO -- 5 1COM Relay output 1-Common end -- 6 1NC Relay output 1-NC -- 1 4NO Relay output 4-NO A5 2 4COM Relay output 4-Common end A5 3 4NC Relay output 4-NC A5 4 3NO Relay output 3-NO A2 5 3COM Relay output 3-Common end A2 6 3NC Relay output 3-NC A2 1 6NO Relay output 6-NO A4 2 6COM Relay output 6-Common end A4 3 6NC Relay output 6-NC A4 4 5NO Relay output 5-NO A5 5 5COM Relay output 5-Common end A5 6 5NC Relay output 5-NC A5 The relays alarm function has two options on the signal board. NO COMMON DDF 2、 Other relays alarm as above the connection step. and one terminal connect with relay out –ON and relay output –common end on the signal board interface. one relay output-NO(normal open) and one relay output-NC(normal close).4 X17 Output relays 5. If it is ‘NO’. and set parameters in the monitor. After finished to connect the signal cables . No Spreading abroad without Permission of ZTE 第 11 页 . find the CTRL menu. and connect relay alarm cables step: 1、 One group relay out need two signal cables .内部公开 Internal Use Only▲ X16 Output relays3. Step: 1、check the monitor screen. Set Relay to Enter 7、 And find the relays alarm parameter. find the 1. press the Enter button. 4、 Enter the setup parameter system: 1.内部公开 Internal Use Only▲ 2、press the button ENTER of the monitor. Setup Para. 3、 Entering the password: 0000. No Spreading abroad without Permission of ZTE 第 12 页 . 5、 Find the Alarm Para in the Setup Para. set the relay <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. According to the relays alarm requirements. 6、 Enter the Alarm Para menu. it mean what it is SMR Alarm.2) of the signal board.内部公开 Internal Use Only▲ alarm. Refer to above the Table-1. SMOKE Alarm(RED / Green) ODU Cabinet Smoke alarm DDF Port 8 SA card (BS8800) B201 X17 Port(NC/COM) B201 X24 Port Smoke sensor D D F Smoke alarm From Smoke sensor first connect to X24,then X17 NC/COM connect to DDF port8 <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. So the relay alarm parameter set A2. Setup procedures: If the relay alarm connected the X15(1. Figure (set parameter: No 8. No Spreading abroad without Permission of ZTE 第 13 页 . DDF 5 .X16 port Environmental Over Humidity(WHITE / 5 From B201 SIB Board 5 GRAY) X16 .DDF 1 .X16 port From B201 SIB Board 6 DC Low Voltage alarm(RED / BLUE) 6 X17 .BBU SA (Power Unit) .BBU SA Card From B201 SIB Board 3 Rectifier Alarm (WHITE / GREEN) 3 X15 .BBU SA (Power Unit) .BBU SA connected directly to SA Card From the Storage Tank 8 Generator Low Fuel(RED / GREEN) 8 Storage Tank Sensor .BBU SA Card Connected directly to BBU SA 2 High Temperature(WHITE / ORANGE) 2 Sensor .DDF 7 .DDF 3 .DDF 2 .DDF 6 . Connected directly to BBU SA 1 Door Cabinet Open(WHITE / BLUE) 1 Sensor .BBU SA (Power Unit) .X15 port From B201 SIB Board 4 AC Power Fail(WHITE / BROWN) 4 X16 .X17 port From Generator Control Port 7 Generator Fault(RED / ORANGE) 7 Generator Control .内部公开 Internal Use Only▲ ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset) Alarm DDF DRY Contact Alarm SLOT Connection Designation Connection No.BBU SA Connected directly to SA Card ZTE ODU External Alarm Drawing (With Genset) ODU Cabinet Door open alarm DDF Port 1 High tep.DDF 4 . No Spreading abroad without Permission of ZTE 第 14 页 .BBU SA (Power Unit) .DDF 8 . Alarm DDF Port 2 Door 1 sensor Door 2 sensor AC1(1500W) alarm cable AC2(1500W) alarm cable AC3(500W) alarm cable B201 Module SA card (BS8800) D D F Rectifier alarm DDF Port 3 B201 X15 Port(NC/COM) AC power fail alarm DDF Port 4 B201 X16 Port(NC/COM) Environmental over humidity alarm DDF Port 5 DC Low voltage alarm DDF Port 6 B201 X16 Port(NC/COM) B201 X17 Port(NC/COM) virtual Generator Actual Generator Fault DDF Port 7 Generator Generator Low Fuel DDF Port 8 Genterator tank <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved. 内部公开 Internal Use Only▲ For alarm No.1—No. No Spreading abroad without Permission of ZTE 第 15 页 . No7.please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Sceco) installation. Generator Fault(RED / ORANGE) No8 Generator Low Fuel(RED / GREEN) SA card (BS8800) D D F Generator Generator Fault DDF Port 7 Generator Generator Low Fuel DDF Port 8 Genterator tank <以上所有信息均为中兴通讯股份有限公司所有,不得外传> All Rights reserved.6.
Copyright © 2024 DOKUMEN.SITE Inc.