Electrical Cable sizing



Comments



Description

STATE OF QATARNEW PORT PROJECT STEERING Committee NEW PORT PROJECT CONTAINER TERMINAL, INFRASTRUCTURE AND UTILITY BUILDINGS NPP/0026 Document Title : CONTAINER TERMINAL-1 LV CABLE SIZING CALCULATIONS Document No. DPCT-TCC-CAL-EL-00066 TEYSEER CONTRACTING COMPANY WLL/ CONSOLIDATED CONTRACTORS GROUP S.A.L. (OFFSHORE) (CCC) JV TCC/CCC JV 01 RE-ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash 00 ISSUED FOR APPROVAL Syed. GH C. Ranjit G. Kawash Rev Description Prepared by Reviewed by Approved by 14.08.2014 14.08.2014 14.08.2014 Signature: Date: NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS Page 2 of 45 DOC No.: DPCT-TCC-CAL-EL-00066 TABLE OF CONTENTS 1. SCOPE .................................................................................................................................................. 3 2. REFERENCE DOCUMENTS ................................................................................................................ 3 3. INITIAL DATA AND ASSUMPTIONS ................................................................................................... 3 4. CABLE SIZING CRITERIA ................................................................................................................... 4 4.1. VOLTAGE DROP .................................................................................................................................. 5 4.2. AMPACITY ............................................................................................................................................ 6 4.3. SHORT CIRCUIT ................................................................................................................................... 6 5. CABLE SIZING REQUIREMENTS ....................................................................................................... 7 5.1. VOLTAGE DROP .................................................................................................................................. 7 5.2. AMPACITY ............................................................................................................................................ 7 6. DE-RATING FACTORS FOR CABLES. ............................................................................................... 8 6.1. De-rating factors for cables installed in Ducts in the ground. ........................................................ 8 6.2. De-rating factors for cables Installed in Air. ..................................................................................... 9 6.3. THERMAL SHORT CIRCUIT CAPACITY........................................................................................... 10 7. APPENDICES...................................................................................................................................... 14 NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS Page 3 of 45 DOC No.: DPCT-TCC-CAL-EL-00066 1. SCOPE The objective of this calculation report is to establish the method to be used for the sizing of the Low Voltage power cables for the Low Voltage power distribution system and motors at Container Terminal-1 Utility Buildings and Infrastructure of New Doha Port Project. 2. REFERENCE DOCUMENTS The following documents have been taken into account for the cable sizing calculation: • • • • Specification Section 21: Electrical Works : Regulation for Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment-Dec 2010 : IEC Electrical Installation of Buildings : Selection and erection of Electrical Equipment – Wiring Systems “DOHA CABLES” Catalogue for XLPE Insulated Low Voltage Cables. 9224-05-EL-SPC-7001 QGEWC / KAHRAMAA IEC-60364-5-52-2001 3. INITIAL DATA AND ASSUMPTIONS The power cables have been sized taking into consideration the following data and cable type: • • • • Nominal voltage system: 240 / 415V Cable insulation level BS(IEC) kV: 0.6/1 kV (0.6/1 kV) Conductor material: Cu (Copper) Insulation material: XLPE o o • • Maximum conductor operating temperature: 90ºC Maximum short circuit temperature: 250ºC Thermal Resistivity values for direct buried cable installations: 2.0°C. m/W (KM standards section 3.3.12.1 and Specification Section 21: Electrical Works) Design conditions for electrical cables: o o Underground cable (buried) In air 40°C 50°C The LV cables for power distribution system and the loads shall be as follows: • Cable shall comprise of plain copper, stranded circular conductors insulated with an adequate thickness of extruded cross linked polyethylene (XLPE). NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No.: DPCT-TCC-CAL-EL-00066 • • • • • Page 4 of 45 Up to 10 Sqmm Cu/XPLE/PVC, unarmoured cable for indoor installations. 16 Sqmm and above Cu/XLPE/SWA/PVC for armoured multicore cable for both indoor and outdoor installations. Cu/XLPE/SWA/LSHF armoured cable for the power supply to D & B (Manned) Buildings from the Utility Buildings. Armoured multicore cable shall have steel wire armouring and extruded sheath of black PVC. Armoured single core cable shall have aluminium wire armouring and extruded sheath of black PVC. The cable sizing will be performed considering multi-core cables up to 240 mm2 for distribution cables. For power, lighting and control cables the minimum cross section shall be 2.5 mm2. Maximum cross section for single-core cables shall be 630mm2. Single core cables may be used for practical and/or economic reasons, e.g., transformer secondary cables or in case of high current ratings where two parallel multicore cables of the largest cross section permitted would not suffice. All three single core cables shall be laid in trefoil formation. Sizing of motor feeders and power feeders will be performed taken into account the Full Load Ampacity (FLA) of the equipment (100% loaded). The system voltage is assumed to be at 100% nominal voltage. Standard power factors and efficiencies at 90% load will be used in this calculation, in case of absence of precise data. All LV Cables shall be installed in ducts throughout the Container Terminal-1 Area. The uPVC ducts are provided with the concrete encasement for LV Cables at road crossings only. The LV Cables shall be laid at a depth of 600mm as minimum. In the Container Terminal-1 Area, all the ducts shall be installed with minimum ground cover of 900mm otherwise it shall be concrete encased. All LV cables in Buildings shall be installed on cable trays/ Trunking/ Conduits as per Specification section 21: Electrical Works Doc. No.: 9224-05-EL-SPC-7001 clause 9.3.3. The correction factors / de-rating factors for the cables installed in Ducts and in Air are taken from “DOHA CABLES” Catalogue. 4. CABLE SIZING CRITERIA Sizing of LV cables will be based on the compliance of all of the following criteria: • • • Voltage Drop Continuous Current Carrying Capacity (Ampacity) Thermal Short Circuit Capacity 1. .L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS Page 5 of 45 DOC No. Voltage drop can also cause damage to electrical Equipment. VOLTAGE DROP A feeder shall be sized in such a way that the maximum voltage drop over the cable ensures the proper operation of the associated equipment in normal service. Excessive voltage drop will result in unsatisfactory operation of electrical equipment. (For Rc and Xc Values see Appendix 14). Note: The voltage drops are related to the terminals of the end equipment.: DPCT-TCC-CAL-EL-00066 4.A.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. The following formula will determine the voltage drop: • For feeders and motors under running conditions (three phases and single phase): Vd = • For motors under starting conditions (three phases and single phase): Vd = • k·I N · l·(Rc·cosϕ + Xc·sin ϕ )·100 n·V k·I starting · l·(Rc·cosϕ s + Xc·sin ϕ s )·100 n·V DC voltage drop can be computed using the formula: Vd = Where: Vd 2·I N · l ·Rdc·100 n·V Voltage drop in percentage Rated current (FLA for motors) in Amps IN Istarting Starting rated current in Amps V System voltage in volts n Number of parallel runs l Length (km) Rc AC conductor resistance at rated conductor temperature at 90 Degree C in (Ω/km) Xc Reactance of the cable (Ω/km) at 50Hz. and represents energy wasted in the cabling system. cos ϕ Power factor cos ϕs Starting power factor k √3 for three-phase consumers and 2 for single phase consumers. and assumes that the associated main switchboard from which the equipment is fed will normally be operated at a voltage of not less than 100% of system voltage. The following de-rating factors will be applied depending on the type of installation. De-rating or correction factors are applied where the installation conditions differ from those for which values of current carrying capacity are defined.A.: DPCT-TCC-CAL-EL-00066 4.2.3. S≥ 1 × K I× t θf + β ln θi + β mm 2 .g.150m direct buried) De-rating temperature factor (e. AMPACITY The current carrying capacity of a cable corresponds to the maximum current that it can carry under specified conditions without the conductor exceeding the permissible limit of steady state temperature for the type of insulation concerned.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS NEW PORT PROJECT Page 6 of 45 DOC No.g.2 below) Load Current Global de-rating factor (FG= Fg ·Ft ·Fd ·Fs) De-rating grouping factor (e. soil temperature 40ºC instead of 15ºC) De-rating factor for depths of laying of cables De-rating factor for thermal resistivity of soil Design factor 4. see Clause 5.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. 5 cables spaced 0. • Installation Trenches and Duct Banks (Below ground) o o o o • Thermal resistivity of soil : Fs Depth of laying : Fd Ground temperature : Ft Grouping factor : Fg Above ground installation (In Air – Indoor / Outdoor) o o Ambient air temperature : Ft Grouping factor : Fg The current carrying capacity required under given conditions can be calculated as follows: I cable _ amp ≥ I N ⋅ FD FG Where: Icable_amp IN FG Fg Ft Fd Fs FD Cable ampacity (current rating of the cable for the conditions defined in the manufacturer’s catalogue. SHORT CIRCUIT The minimum conductor sizes suitable to withstand the applicable short circuit conditions are calculated based on the maximum permissible conductor temperature of 250ºC as follows (valid where t ≤ 5sec). The allowable cable ampacities for this project are determined following the application of the appropriate correction/de-rating factors which are applied where the installation and environmental conditions differ from those for which the values of current carrying capacity are defined.A. at end of short circuit (XLPE insulation:250 ºC) It is the reciprocal of the resistance variation of the conductor at 0º C.08) 5.2. (Copper β=234. The Voltage drop is measured from the LV terminal of the Transformer to the final load in a LV Circuit.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. allowable conductor temp. The following factors (de-rating and over-sizing factors) will be used in the calculation depending on the type of installation: . (XLPE insulation: 90ºC) Max. 5.5) Constant. permissible continuous conductor temperature ºC. Depends on material of the conductor (Copper K =143. VOLTAGE DROP As per BS 7671: 4% As per QGEWC: 2.: DPCT-TCC-CAL-EL-00066 Page 7 of 45 Where: S I t θi θf β K Minimum cross-section area of the cable (mm2) Short circuit current Short circuit time rating (seconds) Max.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No.5% (From utility LV Connection Point) The maximum permissible voltage drop for three phase 415V system shall be 4%. AMPACITY Cable size will be selected in order to comply with ampacity criterion. CABLE SIZING REQUIREMENTS 5.1. De-rating factors for cables.88 0.88 0.95 Depth of laying @ 2m – Multi Core : Fd Depth of laying @ 2m – Single Core : Fd Soil thermal resistivity @ 2.45 Single-core cables 0.64 Appendix-7 Multicore cables 0.0 K·m/W – Three Core and Single Core Cables : Fs Cable grouping factor – Multicore Cables : Fg Cable grouping factor – Single Core Cables : Fg (Trefoil formation) 0.85 0. Total de-rating factors will be as follows: De-Rating Factors Value Ground temperature @ 40ºC : Ft 0.95 0.41 Global de-rating factors will be as follows: De-Rating Factors Ground temperature : Ft Depth of laying @ 2m : Fd Soil thermal resistivity @ 2.A.67 Reference “DOHA CABLES” Catalogue Appendix-3 Appendix-5 Appendix-5 Appendix-6 Appendix-8 0.: DPCT-TCC-CAL-EL-00066 6. The data is based upon normal conditions which are: • • • • Ground temperature: Ambient Air temperature: Depth of laying: Soil Thermal resistivity: 35ºC 40ºC 0.85 0.64 0.80 0.0 : Fs Grouping factor : Fg Global De-rating : FG .67 0.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS NEW PORT PROJECT Page 8 of 45 DOC No. De-rating factors for cables installed in Ducts in the ground.1.5m 1.2 K·m/W In order to update them to the project conditions the following correction factors from “DOHA CABLES” Catalogue will be used: 6.80 0. Ampacities data were taken from “DOHA CABLES” Catalogue (Appendix 1).80 0.95 0.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. In order to update them to the project conditions the following correction factors from “DOHA CABLES” Catalogue will be used: De-rating factors Value Ambient temperature @ 50ºC – Installed Outdoor / Non Air-conditioned Area : Ft Ambient temperature @ 35ºC – Installed Indoor / Airconditioned Area : Ft Cable grouping factor for Multicore cables : Fg Cable grouping factor for Single core cables : Fg Design Factor 0.05 0.A.89 Ref.93 0.90 0.97 Single-core cables 1.2. . “DOHA CABLES” Catalogue Appendix 4 1.89 0. Temperature factor : Ft Grouping factor : Fg Global De-rating : FG Multicore cables 0.05 0. Ampacities data were taken from “DOHA CABLES” Catalogue (Appendix 1).90 125% Appendix 9 Appendix 10 Note: De-rating grouping factor corresponds to a single layer installation in a ladder type cable tray with a maximum grouping of 3 three-phase circuits for single core cables (up to 6 circuits for multi-core cables) and up to 3 levels of cable trays (300mm spacing between trays).80 The design factor of 25% will be employed to oversize incoming cables to LV switchgears to allow 25% spare capacity for the future loads on all the incoming cables.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.: DPCT-TCC-CAL-EL-00066 6.90 0.93 0.89 0. • Global De-rating factors will be as follows: De-rating factors for cables Installed in Air (Installed Indoor / Air-conditioned Area).93 0. The different circuits for single core cables must be installed spaced at least two (2) external diameters of the single-core cable. Temperature factor : Ft Grouping factor : Fg Global De-rating : FG Multicore cables 1. De-rating factors for cables Installed in Air.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS Page 9 of 45 DOC No.82 Single-core cables 0.94 De-rating factors for cables Installed in Air (Installed Outdoor / Non Air-conditioned Area).05 Appendix 4 0. The following formulae will be used: 2 S ≥ I ×t k2 mm 2 Where: I2·t = Specific circuit breaker let-through energy k = Constant (k = 143. the minimum conductor sizes shall be calculated.08 for copper cables and XLPE insulation) .NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. According to the equation under paragraph 4. THERMAL SHORT CIRCUIT CAPACITY For incomer cables to all the switchgears the short circuit rating of the switchgear shall be used for the value of short circuit current. The minimum calculated Short Circuit Ratings of conductor from “DOHA CABLES” manufacturer are provided in the Appendix-11: For switchgear outgoings (feeders and motor starters) the current limiting characteristic of the circuit breaker has been taken into account in order to size the minimum cable sizes.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS Page 10 of 45 DOC No.3 and taking into account the above clearance times.: DPCT-TCC-CAL-EL-00066 6.A. let-through energy curves of circuit breakers to be installed in the switchgear have been analysed. For that purpose. The value for t has been taken as 1 sec for incomer circuit breakers.3. : DPCT-TCC-CAL-EL-00066 • Circuit breakers ≤ 63A (ABB Tmax T2 160A) Irms = 80Ka I2·t = 0.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.22 106 S > 3.A. which means minimum cable size 4mm2.28 mm2. Page 11 of 45 .L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. Page 12 of 45 .NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.: DPCT-TCC-CAL-EL-00066 • Circuit breakers ≤ 160A (ABB Tmax T2 160A) Irms = 80Ka I2·t = 0.39 106 S > 4.36 mm2. which means minimum cable size 6mm2.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. Page 13 of 45 .46 mm2.: DPCT-TCC-CAL-EL-00066 • Circuit breakers > 160A & ≤ 800A (ABB T6 800A) Irms = 80Ka I2·t = 19 106 S > 30.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. which means minimum cable size 35mm2.A. Rating Factors for Trefoil Formation for Three Single Core Cables Laid Direct in Ground. AC resistance (R) and reactance (X) for Single and multi-core Cables. • Appendix 14 Cable selection chart for 415V-3 Phase. Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable (From LV Switch Board to Final Loads). reference from “DOHA CABLES” catalogue. • Appendix 11 Short Circuit Ratings of Conductors for 1 Sec in kA. Rating Factors for groups of more than one multi-core cable in air To be applied to the current-carrying capacity for one multi-core cable in free air. Reference from “DOHA CABLES” Catalogue. • Appendix 8. • Appendix 4. Current ratings for single and multi-core cables (“DOHA CABLES” Catalogue). Reference from “DOHA CABLES” Catalogue. . Reference from “DOHA CABLES” Catalogue. • Appendix 12 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (Power Distribution Feeders . Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution Feeders .). • Appendix 9. Rating Factors for Air Temperature. Rating Factors for Variation in Thermal Resistivity of Soil (average values). • Appendix 13 Cable selection chart for 415V-3 Phase. • Appendix 7.A. • Appendix 6. Reference from “DOHA CABLES” Catalogue. Rating Factors for Ground Temperature. Rating Factors for Depth of Laying. Reference from “DOHA CABLES” Catalogue.From LV Switch Board to Distribution Panels). Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads.NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. • Appendix 3. Reference from “DOHA CABLES” Catalogue.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. Reference from “DOHA CABLES” Catalogue. Reference from “DOHA CABLES” Catalogue. • Appendix 15 Cable selection chart for 415V-3 Phase. APPENDICES • Appendix 1. Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in Ground.From LV Switch Board to Distribution Panels). • Appendix 2. Reference from “DOHA CABLES” Catalogue.: DPCT-TCC-CAL-EL-00066 Page 14 of 45 7. • Appendix 5. • Appendix 10 Rating Factors for groups of more than one circuit of single-core cables To be applied to the current-carrying capacity for one circuit of single-core cables in free air. • Appendix 21 Cable selection chart for 415V-3 Phase.From LV Switch Board to LV Motors).: DPCT-TCC-CAL-EL-00066 Page 15 of 45 • Appendix 16 Cable selection chart for 415V-3 Phase. • Appendix 29 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (For 3 Phase LV Motor Feeders – At Run . Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (Outdoor). Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (From LV Switch Board to Final Loads). Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (Indoor/Outdoor) on cable trays (From LV Switch Board to Final Loads). (Power Distribution Feeders .From LV Switch Board to LV Motors). • Appendix 24 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders – At Starting . • Appendix 20 Cable selection chart for 230V-1 Phase. • Appendix 23 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders – At Run . Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (Outdoor). (From LV Switch Board to Final Loads). • Appendix 25 Cable selection chart for 415V Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (For 3 Phase LV Motor Feeders – Selection Sheet From LV Switch Board to LV Motors).From LV Switch Board to LV Motors). . Single Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (Outdoor). Single Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (Power Distribution Feeders .From LV Switch Board to LV Motors).L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. (Power Distribution Feeders .NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.From LV Switch Board to Distribution Panels). • Appendix 22 Cable selection chart for 415V-3 Phase. • Appendix 17 Cable selection chart for 415V-3 Phase. • Appendix 26 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders –At Run From LV Switch Board to LV Motors).A. • Appendix 27 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders – At Starting . Multi Core Cu/XLPE/PVC cables – Laid in Air (Indoor) on cable trays (From LV Switch Board to Final Loads). • Appendix 19 Cable selection chart for 230V-1 Phase.From LV Switch Board to Distribution Panels). • Appendix 28 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Air (Indoor/Outdoor) on cable trays (For 3 Phase LV Motor Feeders – Selection Sheet .From LV Switch Board to Distribution Panels). • Appendix 18 Cable selection chart for 230V-1 Phase.From LV Switch Board to LV Motors). A.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. • Appendix 31 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (For 3 Phase LV Motor Feeders – Selection Sheet .From LV Switch Board to LV Motors).From LV Switch Board to LV Motors).NEW PORT PROJECT TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. .: DPCT-TCC-CAL-EL-00066 Page 16 of 45 • Appendix 30 Cable selection chart for 415V Multi Core Cu/XLPE/SWA/PVC cables – Laid in Ducts (For 3 Phase LV Motor Feeders – At Starting . reference from “DOHA CABLES” catalogue. Note: The Current Carrying Capacities. Current ratings and AC resistance (R) & reactance (X) for Single and multi-core Cables.: DPCT-TCC-CAL-EL-00066 Page 17 of 44 Appendix 1 & 2.A. . Cable Resistances & Reactances and Cable overall diameter is typical for the LSHF cables (Low Smoke Halogen Free).TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. : DPCT-TCC-CAL-EL-00066 Page 18 of 44 Note: The Current Carrying Capacities.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No.A. Cable Resistances & Reactances and Cable overall diameter is typical for the LSHF cables (Low Smoke Halogen Free). . L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No.A. Rating Factors for Ground Temperature.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. Appendix 5. Reference from “DOHA CABLES” Catalogue. Rating Factors for Depth of Laying. Rating Factors for Air Temperature. Appendix 4. Reference from “DOHA CABLES” Catalogue. .: DPCT-TCC-CAL-EL-00066 Page 19 of 44 Appendix 3. Reference from “DOHA CABLES” Catalogue. L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No.: DPCT-TCC-CAL-EL-00066 Page 20 of 44 Appendix 6. Rating Factors for Variation in Thermal Resistivity of Soil (average values).A. Reference from “DOHA CABLES” Catalogue. Rating Factors for Trefoil Formation for Three Single Core Cables Laid Direct in Ground. Appendix 7. Reference from “DOHA CABLES” Catalogue. .TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. Rating Factors for Trefoil Formation for Multi-Core Cables Laid Direct in Ground.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.: DPCT-TCC-CAL-EL-00066 Page 21 of 44 Appendix 8.A. . Reference from “DOHA CABLES” Catalogue. Reference from “DOHA CABLES” Catalogue.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. .A.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.: DPCT-TCC-CAL-EL-00066 Page 22 of 44 Appendix 9. Rating Factors for groups of more than one multi-core cable in air To be applied to the current-carrying capacity for one multi-core cable in free air. : DPCT-TCC-CAL-EL-00066 Page 23 of 44 Appendix 10. Reference from “DOHA CABLES” Catalogue. Rating Factors for groups of more than one circuit of single-core cables To be applied to the current-carrying capacity for one circuit of single-core cables in free air.A. .TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. A.: DPCT-TCC-CAL-EL-00066 Page 24 of 44 Appendix 11.L (OFFSHORE) (CCC) JV LV CABLE SIZING CALCULATIONS DOC No. . Short Circuit Ratings of Conductors for 1 Sec in kA. Reference from “DOHA CABLES” Catalogue.TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S. 53 18.85 0.53 25.00 18.05 0.53 30.85 0.85 0.00 122.74 38.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.53 185.19 783.85 0.02 96.36 386.ccc.A.68 - * SITE CABLE RATING = CCC x DERATING FACTOR 1728.50 9.53 132.85 0.37 0.00 4.00 60.85 0.41 0.85 0.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 50 Hz 1 0.72 1168.02 0.37 19.36 116.85 0.90 0.85 0.53 150.85 0.85 0.00 0.53 1.00 40.53 0.L.85 0.04 78.08 0.81 289.85 0.85 0.85 0.00 245.55 0.50 2.18 39.53 7.gr APPENDIX : 12 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 415 V Document No.00 49.53 110.85 0.85 0.91 527.23 0.67 26.53 0.0933 % AT F.85 0.00 327.53 75.62 39.50 12.53 5.55 0.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.2 2.ON CABLE LADDER (INDOOR) Power Distribution Feeders .97 CABLE C.85 28.78 576.85 0.51 52.92 5.64 17.09 0.85 0.24 288.00 0.83 1953.00 360.00 6.51 0.00 90.00 458.29 28.68 131.70 48.85 0.85 0.00 73.53 3.84 0.00 36.NEW PORT PROJECT STEERING COMMITTEE Page 25 of 44 REV.53 11.09 - - - - - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.58 57.79 0.75 0.01 0.00 24.28 0.81 23.00 261.: DPCT-TCC-CAL-EL-00066 3.50 4.85 0.10 0.34 0.06 108.C 4X6 44 42.04 0.46 0. 01 3-PH POWER FEEDER 0.00 180.29 - 2890.55 0.53 61.85 0.87 144.56 0.61 481.61 0.28 0.87 0.53 37.91 24.53 200. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.75 1.6/1 kV.53 45. CU/XLPE/PVC (FOUR CORES CABLE .50 30.08 240.27 1314.53 4.F xVOLT) - - ***L = - - - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) - - - .90 180.36 19.91 0.92 0.12 172.85 0.53 250.65 0.25 0.8800 0.9300 0.00 99.00 302.PH LV POWER FEEDER LAID IN AIR .68 72.73 193.S.L.02 963.3300 0.36 65.53 220. No.85 0.34 15.0888 4 X 10 60 58.18 0.C AMPS** 0.00 409.53 280.53 15.05 785.53 160.85 0.L.40 96.00 216.28 0.53 22.07 32.85 0.0856 - - - - - - - - - - - - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 1160.85 0.53 55.From LV Switch Board to Distribution Panels CLIENT: STATE OF QATAR .53 0.68 3.53 2.85 0.53 4X4 36 34. 5 0.53 110.50 12.15 270.53 11.00 40.53 30.02 0.45 1440.6/1 kV.23 0.ccc.45 97.25 0.85 0.85 0.00 4.18 0.92 5.00 360.85 0.53 220.85 0.37 0.53 3. CU/XLPE/PVC (FOUR CORES CABLE .41 290.0933 % AT F.00 302.68 65.23 - - - - - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.84 96.00 0.80 2920.71 181.00 0.53 200.: DPCT-TCC-CAL-EL-00066 3.00 90.61 0. 01 3-PH POWER FEEDER 0.8800 0.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 50 Hz 2.50 240.08 4883.00 49.53 150.55 0.51 722.78 1318.65 0.84 0.04 2409.30 432.gr APPENDIX : 13 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 415 V Document No.53 1.85 0.13 72.66 82.85 0.79 0.85 0.55 0.85 0.85 0.53 0.85 0.53 37.01 0.53 61.45 144.56 0.53 45. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.85 0.27 60.3300 0.53 55.00 36.40 49.C AMPS** 0.S.50 9.85 0.60 720.53 5.0856 - - - - - - - - - - - - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2900.51 0.L.F xVOLT) - - ***L = - - - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) - - - .28 0.90 0.53 185.50 4.75 0.55 0.85 0.85 0.11 196.53 15.28 0.L.85 0.20 - * SITE CABLE RATING = CCC x DERATING FACTOR 4321.97 CABLE C.40 966.00 60.85 0.18 360.53 4.50 2.71 602.75 1.NEW PORT PROJECT STEERING COMMITTEE Page 26 of 44 REV.00 24.28 131.00 261.22 72.53 160.53 132.53 4X4 36 34.85 0.53 280.92 48.06 98.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.47 1959.53 7.04 0.85 0.16 3285. CLIENT: STATE OF QATAR .9300 0.0888 4 X 10 60 58.09 0.85 0.22 - 7227. No.34 0.85 0.00 458.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.03 58.00 409.28 0.13 1964.PH LV POWER FEEDER LAID IN AIR .00 216.10 0.46 0.00 180.91 0.53 25.00 18.85 0.00 245.68 3.92 0.00 6.85 0.53 75.50 30.85 0.69 328.34 39.53 18.00 122.87 0.82 483.03 1204.85 0.85 0.00 327.85 0.53 0.90 164.85 0.00 73.25 120.ON CABLE LADDER (INDOOR) From LV Switch Board to Final Loads. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.85 0.85 0.A.00 99.08 0.11 43.53 2.53 0.53 250.C 4X6 44 42.26 451.L.05 0.41 0.05 241.53 22.85 0.2 2. 73 160.85 0.92 71.66 39.53 0.39 3067.37 806.66 - 2886.53 0.0710 4 X 150 334 273.18 458.80 1608.50 3.1964 0.53 % AT F.85 0.02 2.98 539.1284 0.60 48.NEW PORT PROJECT STEERING COMMITTEE 0.12 78.45 43856.85 4360.40 964.91 548.00 99.0750 4 X 70 196 160.0720 4 X 120 280 229.72 128.38 3074.50 7.02 2605.00 25.40 75.0982 0.0710 4 X 240 434 355.99 363.92 49.33 8040.08 399.69 1537.38 120.6/1 kV.0823 4 X 25 109 89.32 1312.64 65.66 7991.51 234.01 5636.4666 0.66 3935.82 786.58 22546.56 395.53 0.20 482.01 95.00 160.02 438.20 130.S.85 0.01 219.89 129.61 676.0799 4 X 50 164 134.7 0.85 0.From LV Switch Board to Distribution Panels CLIENT: STATE OF QATAR .24 239.05 - 4539.85 0.71 1598.06 1096.6 1.33 26639.46 153.20 80.08 409.88 2124.49 59.53 0.23 1127.00 18.00 24.90 1.03 2865.53 0.02 2348.28 Page 27 of 44 REV.L.81 109.45 71.67 - 7044.38 19.63 2663.01 32.1597 0.12 16080.53 0.6686 0.66 6659.90 90.53 0.18 665.21 4385.15 1174.31 51.55 955. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING kW LOAD F.00 280. 01 3-PH POWER FEEDER 0.31 28.85 0.85 0.75 38.52 89.53 0.60 39.6 0.26 108.56 453.17 67638.82 79.91 6.84 122.F xVOLT) 23614.85 0.9 0.67 579.89 191.20 124.00 15.20 11985.44 1274.42 116.17 13319.61 219.83 804.12 477.46 177.51 386.85 0.79 6659.70 393.16 481.13 54.06 17738.78 78.28 18.25 2113.98 144. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.27 - 33819.81 98.64 60.22 65.05 70.59 332.85 0.02 99.81 160.0933 0.00 110.45 4759.A.9273 0.31 799.22 147.16 665.0355 2X(4 X 150) 668 547.40 131.37 80.3336 0.45 277.53 0.70 42.39 37.28 197.65 90.53 0.62 159.01 40.31 338.53 0.60 112.68 403.94 80.15 108.70 47.55 57.09 4.8783 0.76 0.00 4.88 153.94 53998.50 22.gr APPENDIX : 14 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 1 0.94 1073.28 6030.71 72.24 4776.31 13319.55 77.00 200.00 75.40 804.86 24.00 37.2471 0.00 30.53 0.6 0.00 250.28 182.85 0.38 19.70 15372.64 286.28 477.43 599.65 457.79 327.71 160.32 - 12746.85 0.66 61.41 787.9 3.65 240.00 12.53 266.07 10734.93 79.55 76.53 0.31 103.07 704.01 375.22 796.83 2361.ccc.29 11273.42 402.15 196.86 64.85 0.06 4776.62 2388.82 75.9 0.40 30744.01 325.34 151.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.72 21928.14 527.56 8040.03 159.02 1791.64 91.53 0.46 2254.00 61.63 151.76 3202.53 0.29 289.63 163.41 0.75 180.58 45.C COSΦ SINΦ AMPS** 4X4 37 30.72 138.61 0.90 3329.28 36.50 2.91 2497.83 228.00 132.75 1.51 4227.07 45701.85 0.12 268.63 57.83 4994.85 0.40 84.73 105.58 127.00 45.56 9648.86 959.97 908.64 172.97 26999.41 95.85 0.99 221.50 11.05 56.51 261.99 443.14 6481.03 651.0888 4 X 10 61 50.PH LV POWER FEEDER LAID IN AIR .35 65191.64 109.19 281.61 3216.91 536.71 144.97 1079.43 295.87 302.29 13025.0988 0.02 11273.85 0.13 - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.0642 0.79 159.56 131.58 26051.30 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) - - .28 573.65 8612.52 65.53 0.60 109.20 90.38 0.85 0.55 30.53 0.85 0.72 53.53 52.61 563.05 96.55 955.51 187.68 - * SITE CABLE RATING = CCC x DERATING FACTOR 1729.34 15.08 288.85 0.03 16080.86 70.55 95.93 1816.12 119.64 96.39 106.10 117.30 43. No.03 962.25 318.23 1127.60 62.60 387.46 4.36 96483.03 3582.34 96.29 576.55 9.9274 0.63 1108.32 1331.85 0.86 1062.10 2192.13 57.14 3015.50 1967.28 320.87 108.53 0.11 1910. CU/XLPE/PVC (FOUR CORES CABLE .73 76.81 150.0355 2X(4 X 185) 730 598.48 0.0799 0.53 0.99 181.03 651.54 9552.90 2818.16 2063.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.57 436.99 454.85 0.68 91.68 66.49 651.L.0740 4 X 95 243 199.44 587.19 107.0355 2X(4 X 240) 868 711.52 3197.80 193.26 117.07 32161.53 0.53 0.25 325.ON CABLE LADDER (INDOOR / OUTDOOR) Power Distribution Feeders .52 784.98 539.03 768.20 96.4 0.85 0.15 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 1160.77 307.41 1302.92 1475.L.94 64.42 321.34 51.83 23.37 38724.36 133.85 0.97 908.21 774.83 1096.08 19104.04 216.0494 0.00 185.17 1478.06 1303.39 79917.84 - 39958.85 1168.61 1773.44 58.53 0.57 5793.58 319.85 0.54 180.53 0.77 218.63 52.53 0.17 536.C 4X6 45 36.62 288.61 36326.87 591.19 60.11 39.85 0.53 0.56 73.84 201.84 193.81 5636.85 0.82 CABLE C.02 4248.14 - 9593.98 15956.3 0.19 19362.30 18163.34 2956.82 53.48 86.53 0.37 52.55 0.82 86.36 1513.23 2.67 - ***L = 28656.10 60.: DPCT-TCC-CAL-EL-00066 3.30 768.28 4824.80 1608.94 378.51 3381.99 269.0856 4 X 16 80 65.04 22850.05 245.47 1950.44 - 48241.83 30.01 6763.34 5.85 0.37 0.26 0.53 0.15 212.86 67.01 384.38 563.10 112.38 65.00 Document No.2 0.17 4020.66 8063.56 238.00 5.05 319.35 236.00 220.0817 4 X 35 131 107.0355 57312.20 234.61 39.76 0.69 5912.0710 2X(4 X 120) 560 459.65 457.24 72.85 0.44 1816.76 130.77 133.01 1302.11 2192.67 32595.08 7871.21 225.71 206.00 55.04 130.28 283.31 172.96 268.04 440.30 424.0710 4 X 185 365 299.4940 0.34 360.39 181.53 0.80 28.44 95.13 756.60 1537.32 1331.00 150.25 0.16 799.26 327.83 3995.85 0.68 26.06 5731.60 387.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.87 3632.30 914.12 9552.40 260.17 75.53 0.3425 0.21 651. 09 4.09 11940.76 0.90 327.82 135.44 162.88 193.54 1409.51 90815.9273 0.19 1432.55 3782.85 0.59 181.40 1997.6/1 kV.83 264.70 12060.37 238.53 939.96 797.ccc.48 176.53 0.62 109640.01 376.13 - 11348.53 0. CLIENT: STATE OF QATAR .53 0.85 0.00 4.53 0.37 7994.95 1664.68 118.04 1965.50 22.52 399.14 293.85 0.98 199794.25 2285.53 14091.05 1096.16 818.85 0.13 241.53 960.80 223.83 665.53 0.39 241208.61 599.53 362.01 40.53 0.10 503.15 44346.77 967.10 150.62 2922. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING kW LOAD F.00 484.85 0.00 160.0740 4 X 95 243 199.48 674.22 3843.84 134996.72 14782.98 454.13 272. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.21 19679.2 0.7 0.23 2.31 299.37 192.53 % AT F.L.08 378.6 1.93 5158.11 2398.85 0.53 0.38 2388.00 2010.72 28182.38 0.61 693.55 709.96 1349.52 1967.59 1998.35 451.85 0.76 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) - - .95 1409.35 241.0710 4 X 185 365 299.83 402.02 8040.22 147.A.79 3689.28 127.26 281.70 1498.25 1921.84 2683.06 10901.00 15.15 160.91 132.62 601.03 246.34 360.11 153.57 12487.76 0.34 1318.29 72.75 1.00 132.80 162.40 988.54 369.08 8955.26 8454.84 133.31 320.01 274.28 10621.23 1628.91 2270.43 3695.38 270.63 5284.2471 0.94 48.61 0.59 4540.02 1936.11 814.50 156.10 1134.92 49.90 1.56 76.20 456.36 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2901.42 768.L.04 216.84 31865.77 845.50 1206.55 9.38 2388.85 0.99 227.76 7045.99 249.35 7537.25 545.53 0.76 199.8783 0.07 1629.6 0.51 4434.96 301.01 144.F xVOLT) 59037.42 201.26 0.48 704.0720 4 X 120 280 229. CU/XLPE/PVC (FOUR CORES CABLE .4666 0.14 5310.79 1370.85 0.18 269.04 189.15 14328.098 0.19 1194.56 804.47 17611.97 908.85 0.99 454.00 25.28 587.82 143.28 3186.6 0.28 128.07 2818.85 0.48 0.96 1349.70 15075.69 47760.20 494.54 1690.99 268.46 360.C COSΦ SINΦ AMPS** 0.93 2270.51 281.00 150.080 0.54 720.53 0.9 0.70 721.28 18.85 0.85 0.53 0.00 2412.14 19979.66 945.40 332.28 587.75 4919.93 1991.85 0.S.79 3329.29 130.: DPCT-TCC-CAL-EL-00066 3.74 8324.6686 0.34 5.14 3259.14 2741.14 16649.85 0.01 968. No.92 33299.09 - 120604.00 250.00 72.99 162.ON CABLE LADDER (INDOOR / OUTDOOR) From LV Switch Board to Final Loads.01 240.25 0.0888 4 X 10 61 50.85 0.21 228.50 76861.04 199.00 5.20 998.74 1441.06 6512.64 97.72 32563.00 200.07 2818.15 98.75 106.53 0.26 10568.PH LV POWER FEEDER LAID IN AIR .94 113.3 0.08 409.77 4776.71 65.53 0.01 188.10 60.31 23880.96 200.79 40201.58 6659.31 54820.A in mm CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.74 227.85 0.16 20157.04 4477.57 2741.01 563.88 96.36 237.0710 4 X 240 434 355.53 0.53 0.85 0.29 14484.13 1448.78 181.18 9081.20 166.85 0.83 318.28 5482.53 0.59 57126.53 0.91 2699.41 16204.04 1005.4940 0.00 325.43 1062.07 1921.01 328.77 432.37 491.50 11.44 56365.00 75.26 45407.53 0.3336 0.50 7.5 0.55 30.44 65127.93 169095.51 211.76 378.97 1109.36 39.00 110.17 80402.02 2.82 2 4X4 37 30.52 82.00 220.C 4X6 45 36.51 261.00 Document No.46 4.1964 0.79 1340.58 98.064 0.01 651.58 5903.80 670.12 23982.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.84 66598.03 814.15 9839.24 177.02 548.0750 4 X 70 196 160.53 0.88 189.60 325.13 140.62 179.53 3256.65 443.1284 0.79 3329.61 238.31 346.9 0.01 4020.05 5970.68 - 84547.85 0.14 - 7216.09 739.85 0.0856 4 X 16 80 65.53 0.56 73.28 Page 28 of 44 REV.87 302.76 5482.0823 4 X 25 109 89.53 0.53 0.53 0.3425 0.39 1202.01 4020.28 1100.42 2015.18 458.9 3.00 30.48 16649.53 0.4 0.00 61.79 327.42 67498.79 134.03 3256.40 1664.10 483.85 0.84 800.42 332.57 2771.14 5636.18 114253.0710 4 X 150 334 273.10 716.51 274.04 799.57 146.51 1090.08 2405.00 37.96 196.17 26835.57 9989.18 81489.55 290.50 3.30 1960.21 - * SITE CABLE RATING = CCC x DERATING FACTOR 4324.84 20100.85 0.39 24120.89 670.53 0.65 384.51 3843.53 16909.1597 0.0988 0.57 2655.00 55.08 7164.71 1467.0710 2X(4 X 120) 560 459.89 325.85 0.09 430.11 796.84 201.80 3280.21 1007.049 0.10 241.92 400.NEW PORT PROJECT STEERING COMMITTEE 0.10 162.55 0.54 164.99 312.39 20100.0355 2X(4 X 150) 668 547.84 122.0933 CABLE C.00 280.01 968.41 2935.06 28182.0355 2X(4 X 240) 868 711.86 7391.85 0.11 - 99897.21 1891.85 0.86 265.79 178.33 131.83 192.64 271.05 245.gr APPENDIX : 15 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 2.08 2010.08 58.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.15 11940.45 7686.10 228.76 983.83 4540.19 3997.62 21530.37 109.50 2.0355 143280.85 0.13 1142.53 0.98 398.89 11899.22 477.52 14091.02 1628.08 40201.41 0.18 - ***L = 71640.42 10050.91 6.29 196.0817 4 X 35 131 107.28 36.79 6243.65 90.28 402.71 531.11 239.64 293.08 409.03 548.98 150.00 24.85 1761.9274 0.93 96811.28 33299.85 0.99 324.85 23880.53 0.36 162978.85 0.13 1142.97 1135.00 18.66 515.18 4875.57 144.75 38430.06 724.02 99.98 554.62 7667.56 571.75 180.22 257.50 29963.L.15 169.53 0.16 60.00 45.00 12.53 0.47 94.45 39890.81 1194.97 832.0355 2X(4 X 185) 730 598.92 1341. 01 3-PH POWER FEEDER 0.17 1478.44 49.37 0.0799 4 X 50 164 134.21 215.71 384.40 597.46 48405.85 0.82 5870.00 185.00 120.53 0.82 - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.27 469.52 10964.40 8005.88 590.27 97.06 398.07 1629.05 215. 44 - 33819.31 103.064 0.04 216.19 19362.79 327.00 5.22 147.02 4248.69 1537.56 73.01 5636.56 8040.85 0.21 774.44 1274.61 1773.0 0.85 0.28 36.08 19104.30 18163.51 3381.53 0.67 32595.02 99.75 1.55 955.45 43856.50 7.85 0.51 261.83 2361.25 0.56 453.65 240.20 482.85 0.08 288.98 144.64 109.46 153.87 302.53 0.80 193.17 536.46 2254.26 327. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.28 573.37 0.67 579.08 399.06 1096.51 386.01 325.01 95.75 5.98 15956.31 799.85 0.02 438.92 49.85 1168.L.58 319.31 172.54 9552.28 4824.60 1537.42 116.36 1513.18 458.07 704.00 132.55 - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.72 21928.14 6481.51 187.99 443.PH LV POWER FEEDER LAID IN DUCTS (INDOOR / OUTDOOR) Power Distribution Feeders .07 32161.85 0.31 13319.98 539.89 129.83 1096.21 225.88 2124.14 527.57 5793.26 117.00 160.8 3.1 0.03 16080.85 0.39 106.85 0.70 393.20 96.1964 0.01 375.85 0.66 7991.31 - 2886.61 563.53 % AT F.60 - 39958.80 1608.85 0.0817 4 X 35 116 52.85 0.56 395.10 60.NEW PORT PROJECT STEERING COMMITTEE 0.20 124.60 387.53 0.97 26999.45 4759.53 0.00 18.54 180.41 0.A.30 424.52 784.5 312.30 914.11 2192.1284 0.17 13319.15 196.09 4.92 1475.50 22.10 117.28 477.12 477.28 6030.23 1127.00 75.22 796.L.10 2192.32 1312.85 0.81 150.38 - - - .26 - 67638.32 1331.53 0.39 3067.85 0.24 4776.60 387.50 3.94 378.91 2497.63 163.00 150.25 2113.53 0.53 0.53 0.17 4020.91 548.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.46 177.82 786.99 181.6/1 kV.71 1598.52 3197.90 2818.40 804.50 11.36 133.30 768.85 0.00 200.C 4X4 35 15.77 307.00 12.85 0.85 0.58 22546.85 0.51 234.53 0.1597 0.17 75.24 239.83 804.97 908.00 Document No.90 1.53 0.43 295.01 1302.16 2063.25 318.96 268.82 86.C 4X6 44 19.85 0.53 0.62 2388.40 30744.86 98.65 90.0933 AMPS** 0.71 144.03 651.0710 4 X 240 347 156.85 0.51 4227.7 234.98 539.46 4.55 955.9 265.73 160.01 6763.43 599.0888 4 X 10 58 26.75 38. No.20 80.99 269.90 3329.17 1478.44 1816.0856 4 X 16 72 32.From LV Switch Board to Distribution Panels CLIENT: STATE OF QATAR .63 2663.69 5912.04 22850.29 13025.53 0.66 8063.32 1331.53 0.77 133.12 268.94 1073.05 245.22 65.21 651.85 0.0355 0.85 0.40 964.28 18.12 9552.66 3935.53 0.23 1127.02 11273.13 756.12 119.9 0.35 65191.28 320.65 457.0799 4 X 50 138 62.70 15372.62 288.25 325.03 159.S.20 11985.L. CU/XLPE/SWA/PVC (FOUR CORES CABLE .29 576.86 959.OUTDOOR 0.098 0.5 0.0355 0.61 0.81 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) 57312.0823 4 X 25 98 44.42 402.72 138.28 197.58 26051.19 281.1 0.85 0.F xVOLT) 23614.05 70.83 3995.72 128.87 - 96483.86 1062.85 0.68 - * SITE CABLE RATING = CCC x DERATING FACTOR 1729.16 481.01 384.01 40.97 908.0710 4 X 185 295 132.44 587.03 768.61 676. 01 3-PH POWER FEEDER (LAID IN DUCTS) .15 108.53 0.16 799.85 0.21 4385.3336 0.049 0.01 219.3 0.71 160.50 2.2 0.49 651.64 286.53 0.66 39.87 3632.94 53998.91 6.00 4.: DPCT-TCC-CAL-EL-00066 3.33 26639.9273 0.88 153.00 110.76 3202.00 37.53 0.63 1108.41 95.66 6659.99 454.85 0.06 17738.11 1910.20 - 48241.03 3582.53 0.35 236.20 234.34 2956.56 131.37 806.03 651.50 1967.61 36326.12 78.0988 0.0710 4 X 150 261 117.53 266.44 - 9593.38 563.63 151.34 - 7044.06 5731.89 191.15 212.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.00 61.00 15.68 403.85 0.53 0.10 - 79917.65 457.55 30.80 1608.93 1816.23 2.14 3015. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.04 440.41 1302.33 8040.81 160.8 0.00 25.0750 4 X 70 171 77.04 130.45 CABLE C.0355 0.00 55.37 38724.31 338.9274 0.71 206.05 96.59 332.0710 2X(4 X 120) 2X(4 X 150) 2X(4 X 185) 2X(4 X 240) 466 522 590 694 209.60 48.66 61.05 319.03 2865.81 5636.28 182.55 9.61 219.53 0.56 238.gr APPENDIX : 16 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 1 0.28 283.45 277.12 16080.11 - 4539.15 1174.8783 0.39 181.41 787.02 1791.02 2605.4940 0.76 130.61 3216.34 151.0355 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 1160.6686 0.00 24.84 201.99 363.79 6659.07 45701.57 436.28 Page 29 of 44 REV.85 4360.02 2348.00 250.84 193.18 665.93 79.06 1303.62 159.94 - 12746.99 221.08 409.85 0.65 8612.38 3074.79 159.63 57.53 0.85 0.08 7871.00 30.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.53 0.56 9648.84 122.53 0.00 185.00 220.58 127.91 536.0720 4 X 120 233 104.03 962.53 0.85 0.42 321.71 72.85 0.080 0.00 280.53 0.20 130.83 4994.29 289.00 45.19 - ***L = 28656.07 10734.53 52.ccc.53 0.2 0.3425 0.29 11273.53 0.0740 4 X 95 200 90 0.06 4776.40 260.83 228.87 591.47 1950.55 0.53 0.16 665.53 0.1 2.40 131.4 1.75 180.97 1079.2471 0.34 360.4666 0.64 172.77 218. ccc.53 200.52 1967.61 599.71 531.53 150.29 196.11 814.51 3843.02 1936.66 945.21 1007.08 40201.00 325.99 - 120604.53 55.56 804.6686 0.85 0.00 302.85 0.06 398.8 0.85 0.61 - 84547.00 458.37 7994.76 7045. 01 3-PH POWER FEEDER 0.65 443.53 362.C AMPS** 0.57 144.53 0.8 3.79 3689.5 0.35 7537.36 162978.85 0.71 1467.38 2388.72 28182.01 968.21 1891.53 11.00 90.64 246.04 4477.3336 0.85 0.96 1349. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.L.85 1761.95 1409.0355 143280.59 4540.01 4020.37 - ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.61 0.48 704.28 0.95 1664.53 220.0933 % AT F.0799 4 X 50 138 62.1 2.83 4540.51 1090.40 8005.52 10964.39 24120.00 409.1 0.064 0.37 0.64 - 169095.93 2270.53 37.19 3997.34 0.50 76861.88 590.50 9.85 0.21 19679.52 399.13 272.19 1432.70 15075.13 1142.1597 0.3425 0.46 360.00 180.08 2010.7 0.05 1096.93 1991.098 0.: DPCT-TCC-CAL-EL-00066 3.42 768.16 20157.54 1690.85 0.96 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2901.97 908.00 60.48 674.40 1997.10 483.85 0.18 4875.60 325.62 601.00 0.0710 4 X 185 295 132.70 1498.0750 4 X 70 171 77.08 8955.01 0.5 0.30 1960.8783 0.28 587.00 261.42 10050.31 346.17 26835.12 23982.50 4.78 181.85 0.0355 2X(4 X 240) 694 312.77 967.01 376.65 384.9273 0.03 3256.C 4X6 44 19.55 709.74 1441.02 0.64 293.50 29963.84 66598.59 1998.31 320.53 2.53 14091.53 160.09 430.50 1206.27 - 11348.4940 0.57 2741.080 0.38 2388.25 545.56 571.20 456.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 50 Hz 2.PH LV POWER FEEDER LAID IN DUCTS (INDOOR / OUTDOOR) From LV Switch Board to Final Loads.04 799.53 22.4 1.53 18.84 134996.18 0.15 98.28 10621.19 1194.91 2270.36 237.35 451.47 17611.53 30.45 7686.00 40.42 332.70 721.62 7667.85 0.22 477.2 0.71 384.04 1965.66 515.28 402.98 398.0823 4 X 25 98 44.84 31865.50 2.86 7391.84 800.57 12487.23 0.87 0.53 5.00 360.25 1921.15 9839.43 3695.09 11940.59 57126.01 4020.71 - * SITE CABLE RATING = CCC x DERATING FACTOR 4324.79 0.75 38430.07 2818.08 7164.0856 4 X 16 72 32.85 0.79 3329.17 80402.53 25.72 32563.0720 4 X 120 233 104.1964 0.08 409.15 11940.S.89 670.40 332.85 0.53 960.13 1142.96 1349.53 132.75 5.93 96811.85 0.00 2010.15 14328.4666 0.07 1629.55 3782.79 3329.62 109640.83 665.40 1664.11 796.79 1370.53 45.88 96.85 0.25 2285.18 114253.50 30.00 6.08 0.99 454.97 832.51 - 99897.28 3186.55 290.F xVOLT) 59037.08 2405.54 720.85 0.28 200.85 0.10 0.85 0.53 7.62 21530.79 1340.00 0.14 2741.26 - 199794.10 503.63 5284.00 73.53 61.62 2922.85 0.55 0.56 0.51 4434.55 0.11 153.L.99 312.53 1.04 0. CU/XLPE/SWA/PVC (FOUR CORES CABLE .0710 4 X 150 261 117.09 0.6/1 kV.54 1409. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.58 5903.26 8454.90 327.00 49.91 0.85 0.34 1318.03 814.26 45407.84 0.3 0.84 2683.00 18.92 400.1284 0.05 0.40 988.45 39890.81 1194.38 270.0710 4 X 240 347 156.14 5310.85 23880.00 245.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.39 1202.53 16909.85 0.31 23880.18 - 241208.0 0.51 0.01 328.85 0. CLIENT: STATE OF QATAR .14 5636.53 75.53 3256.28 1100.20 494.91 2699.42 2015.53 0.00 99.89 325.75 4919.0740 4 X 95 200 90 0.50 12.57 9989.52 14091.28 587.98 554.46 48405.85 0.0355 2X(4 X 150) 522 234.90 0.53 15.18 81489.2 0.17 1478.03 548.94 176.46 0.11 239.53 185.53 939.85 0.29 - 7216.01 651.13 1448.31 299.54 164.76 378.41 0.02 8040.29 14484.33 131.44 65127.77 432.09 739.99 324.83 318.5 0.41 16204.9 0.92 33299.11 2398.79 6243.85 0.53 250.01 240. No.31 54820.14 3259.05 5970.70 12060.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.1 0.53 280.88 189.06 10901.06 6512.92 0.77 845.10 1134.84 20100.28 0.01 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) - - .07 2818.72 14782.A.97 1109.0817 4 X 35 116 52.gr APPENDIX : 17 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 415 V Document No.92 1341.22 257.74 8324.75 1.40 597.20 998.08 378.37 491.0710 2X(4 X 120) 466 209.96 797.85 0.42 67498.65 0.53 110.18 9081.97 1135.00 4.53 0.25 0.15 44346.76 5482.41 2935.L.77 4776.85 0.NEW PORT PROJECT STEERING COMMITTEE Page 30 of 44 REV.02 548.39 20100.85 0.58 6659.48 16649.13 241.57 2655.14 16649.23 1628.06 28182.07 1629.53 4.0355 2X(4 X 185) 590 265.02 1628.56 215.89 11899.85 0.93 5158.27 469.85 0.10 716.28 5482.43 1062.049 0.00 327.53 4X4 35 15.85 0.26 10568.80 3280.01 968.98 454.04 1005.00 24.2471 0.01 563.44 56365.53 3.80 670.9 0.69 47760.99 - ***L = 71640.14 19979.00 122.9274 0.28 0.76 983.00 484.00 2412.47 199.61 693.55 0.0988 0.00 120.45 CABLE C.28 33299.57 2771.06 724.79 40201.54 369.22 3843.00 36.51 90815.83 402.75 0.07 1921.86 265.82 5870.16 818.00 216.0888 4 X 10 58 26.14 293. 85 0.37 0.NEW PORT PROJECT STEERING COMMITTEE 0.53 0.86 55.0933 AMPS** 1. 3X6 45.53 0.85 0.29 857.42 137.53 0.92 5.00 58.53 90.00 Document No.0856 - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 485.54 816.53 0.85 0.65 431.INDOOR) 0.47 - ** IN (FLC) = (LOAD x 1000) (P.85 0.41 53.25 0.00 43.33 100.00 150.53 0.85 0.6/1 kV.58 549.50 22.53 161.ON CABLE LADDER (INTDOOR) From LV Switch Board to Final Loads.17 327.L.: DPCT-TCC-CAL-EL-00066 1.31 367.53 0.53 0.53 0.85 0.53 54.97 CABLE C.96 29.85 0.70 3.85 0.23 1.33 0.55 0.85 0.06 120.86 Page 31 of 44 REV.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.92 73.00 185.53 * SITE CABLE RATING = CCC x DERATING FACTOR % AT F. 01 1.85 0.53 0. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.9274 0.85 201.50 6. No.00 4.85 0.L.00 5.85 0.00 15.00 175.00 75.53 0.53 0.61 26.5 0.85 0.68 7.S.53 0.72 241.86 171.71 75.53 0.C 3X4 36.A.gr APPENDIX : 18 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 240 V 50 Hz 2.53 0.85 0.71 19.53 0.00 58.81 220.53 0.53 0.18 488.06 735.93 50.85 0.18 60.78 14.PH POWER FEEDER (LAID IN AIR .33 402.72 80.85 0.35 10. CLIENT: STATE OF QATAR .50 2.00 34.22 - 723.20 2.C.20 3.53 0.05 20.53 0.50 32.ON CABLE LADDER .37 539. CU/XLPE/PVC (THREE CORES CABLE .26 45.36 27.53 82.ccc.53 0.00 35.81 2.32 22.57 220.00 132.69 107.59 284.00 11.13 - 1208.63 328.53 0.00 45.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.65 3.8783 0.20 32.85 0.00 88.53 0.85 0.00 110.84 134.87 30.85 0.00 27.84 906.00 18.53 0.85 0.85 0.22 647.85 0.75 1.80 156.PH POWER FEEDER LAID IN AIR .53 0.85 0.85 0.L.43 30.85 0.53 0.0888 3 X 10 60.F xVOLT) - ***L = (Vd%) x V x 1000 X n 2 x INx (RcosΦ + XsinΦ) . IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.13 40.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.85 0. 20 32.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.00 88.66 490. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.00 65.53 0.85 0.INDOOR / OUTDOOR) 0.53 0.85 0.3336 0.: DPCT-TCC-CAL-EL-00066 1.86 Page 32 of 44 REV.35 10.13 40.74 334.C 3X4 37.86 55.00 11.50 6.00 134.53 0.18 488.00 89.53 0.57 220.07 43.21 250.85 0.53 0. 0.12 137.80 156.81 2.06 133.9273 0.96 29.10 91.00 30. 01 1.56 75.09 1776.86 1338.85 50.48 0.60 1.02 121.20 3.00 50.53 0.53 161.00 58.9274 0.72 241.24 201.20 888.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.78 14.71 815.00 107.S.00 110.68 7.0823 3 X 25 109.58 316.53 0.99 1989.81 72.53 0.14 118.13 - 2944.00 5.85 0.51 402.82 CABLE C.85 0.00 75.50 2.69 107.10 605.0750 4010.20 - 5328.85 0.53 0.23 1.0856 3 X 16 80.53 0.00 35.53 0.8783 0.0817 3 X 35 131.0933 AMPS** 1.50 32.42 0.84 906.00 15.PH POWER FEEDER LAID IN AIR .59 3600.85 0.21 222.41 455.53 90.NEW PORT PROJECT STEERING COMMITTEE CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 240 V 50 Hz 2.01 60.6/1 kV.87 30.28 - ** IN (FLC) = (LOAD x 1000) (P.26 79.0799 3 X 50 164.52 444.85 0.85 0.84 54.53 * SITE CABLE RATING = CCC x DERATING FACTOR % AT F.F xVOLT) 1897.00 36.53 0.53 0.53 0.85 0.00 185.L.13 - 1206.00 27.53 0.83 668.63 328.0888 3 X 10 61.5 0.00 132.85 0.494 0.49 2709.73 1282.84 134.86 171.70 3.ON CABLE LADDER (INDOOR / OUTDOOR) From LV Switch Board to Final Loads.55 0.79 1822.25 862. CU/XLPE/SWA/PVC (THREE CORES CABLE .59 284.53 0.61 86.38 0.22 647.ccc.85 0.41 53.43 30. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.92 73.25 0.34 5.93 49.53 0.85 0.L.85 0.65 158.00 18.37 539.71 19.85 0.00 150.85 0.31 367.60 632.26 45.10 88.40 2422.63 981.53 0.06 120.17 327.85 0.05 20.90 3.83 334.35 548.86 122.13 100.53 82.00 4.53 0.95 1336.00 45.53 0.32 22.08 - ***L = (Vd%) x V x 1000 X n 2 x INx (RcosΦ + XsinΦ) .C.85 0.02 2.37 0.85 0.00 Document No.29 215.85 0.18 60.53 0.85 0.A.55 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 485.42 184.PH POWER FEEDER (LAID IN AIR . No.85 0.85 0.05 333.42 54.65 431.66 182.72 80.85 0.00 175.4666 0.85 0.53 0.66 245.29 857.22 - 723.53 0.gr APPENDIX : 19 CLIENT: STATE OF QATAR .6686 0.06 735.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.15 66.29 167.53 0.85 0.75 1.61 26. 3X6 45.04 242.71 66.53 0.L.81 220.50 22. F xVOLT) 1897.85 0.5 0.21 250.02 121.53 0.50 22.74 334.85 0.53 0.9273 0.75 1.85 0.35 548.66 490.59 284.6/1 kV.85 0.53 0.29 215.L.13 40.04 242.53 0.20 - 1206. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.85 0.73 1282.PH POWER FEEDER (LAID IN DUCTS .53 161.50 6.0933 CABLE C.00 18.53 0.85 0.00 150. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING kW LOAD F.85 0.00 5.29 857.0856 3 X 16 72 32.53 0.85 0.20 3.63 981.24 201.53 0.85 0.57 220.14 118.53 0.10 0.61 86.53 0. No.10 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** ** 0.0823 3 X 25 98 44.37 539.00 185.71 815.00 1.53 0.22 647. 01 1.53 0.gr APPENDIX : 20 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: 240 V Document No.26 79.53 90.72 241.85 0.85 0.61 26.PH POWER FEEDER LAID IN DUCTS (OUTDOOR) From LV Switch Board to Final Loads.53 0.00 45.80 156.85 0.35 10.06 735.53 0.69 107.53 0.85 0.: DPCT-TCC-CAL-EL-00066 1.00 35.65 158.10 2.40 1.31 367.53 0.84 906.53 0.L.00 88.52 444.83 668.99 1989.85 0.53 0.96 29.51 402.85 0.00 11.05 333.86 1338.53 0.NEW PORT PROJECT STEERING COMMITTEE Page 33 of 44 REV.06 133.86 171.68 7.55 0.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 50 Hz 2. CLIENT: STATE OF QATAR .79 1822.56 75.65 431.53 * SITE CABLE RATING = CCC x DERATING FACTOR 485.13 100.23 1.0799 3 X 50 138 62.43 - 723.20 0.09 1776.8783 0.59 3600.10 - 5328.00 27.6686 0.80 3.A in mm CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.66 245.00 75.25 0.25 862.53 0.70 3.85 0.63 328.60 632.L.85 0.40 2422.81 220.49 2709.00 175.78 14.50 32.53 82.INDOOR / OUTDOOR) 0.85 0.20 888.0817 3 X 35 116 52.85 0.0888 3 X 10 58 26.92 73.53 0.9274 0.00 4.29 167.00 15.85 0.58 316.41 455.ccc.50 2.85 0.53 0.37 0.53 0.83 334.17 327.0750 4010.53 0.21 222.85 0.S.45 2 3X4 35 15.10 0.4666 0.84 134.86 0.12 137.00 110. 3X6 44 19.A.85 0.86 55.71 19.53 0.10 605.42 184.71 - ***L = (Vd%) x V x 1000 X n 2 x INx (RcosΦ + XsinΦ) .86 122.72 80.42 - ** IN (FLC) = (LOAD x 1000) (P.81 2.41 53.C.07 - 2944.18 488.95 1336.85 0.18 60. CU/XLPE/SWA/PVC (THREE CORES CABLE .53 0.494 0.06 120.C COSΦ SINΦ AMPS % AT F.85 0.75 5.00 58.26 45.3336 0.85 0.00 132.66 182. 71 50.0435 4X(2 X 630) 1616 1294. CU/XLPE/AWA/PVC (SINGLE CORE CABLE .22 96.60 736.S.92 0.53 0.1970 0.18 50.00 150.00 40.51 286.91 73.42 100.67 58.44 0.53 0.85 0.24 73.84 326.10 53.12 59.04 164.1080 4X(1 X 95) 244 195.42 327.0418 0.4940 0.15 296.79 54.35 100.85 0.31 371.72 114.19 941.85 0.14 - 1152. No.78 50.1140 CONDUCTOR RESIST.A.85 0.10 491.032 0.1010 4X(1 X 150) 328 262.00 225.31 494.10 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** - * SITE CABLE RATING = CCC x DERATING FACTOR - - 122.88 87.00 525.02 - 220.0412 742.02 88.15 247.33 82.85 0.53 0.74 121.13 143.51 109.75 96.49 - 1002.00 Document No.53 0.79 82.45 118.00 125.06 230.46 134.35 52.78 64.L.85 0.61 52.13 125.97 123.01 67.01 60.09 185.94 - 501.12 - (LOAD x 1000) (SQRT 3 x P.00 75.53 0.77 654.96 148.00 375.70 67.42 163.026 0.85 62.72 54. 01 3-PH POWER FEEDER 50 Hz 1.NEW PORT PROJECT STEERING COMMITTEE 0.53 0.47 182.0 0.74 77.87 - 365.53 0.22 104.73 0.00 600.35 50.04 144.85 0.57 71.36 163.48 110.6/1 kV.53 0.23 59.26 409.53 0.0930 4X(1 X 300) 523 418.85 0.85 0.01 0.53 0.08 - 311.63 66.66 65.13 217.00 575.36 859.76 146.26 434.1040 4X(1 X 120) 287 229.47 65.71 52.64 57.0450 4X(2 X 500) 1374 1100.56 167.92 81.89 0.00 100.39 250.11 982.53 0.21 - ***L = 439.37 73.52 777.35 0.0823 4X(2 X 300) 1046 837.85 0.85 0.gr APPENDIX : 21 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: REV.03 115.40 0.00 50. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.53 0.03 128.38 57.95 1063.041 0.06 130.00 475.62 742.85 0.47 68.92 247.67 - ** IN (FLC) = 168.42 186.82 91.97 81.03 1022.28 91.71 100.23 67.00 550.39 334.75 163.16 83.35 111.67 204.57 0.35 93.85 0.70 167.ON CABLE LADDER (INDOOR / OUTDOOR) Power Distribution Feeders .44 212.1290 0.30 54.44 818.85 0.71 93.69 88.85 0.86 57.53 0.97 92.20 106.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.86 59.03 115.17 1484.85 0.46 66.L.23 70.11 288.97 0.85 613.0810 0.05 84.30 76.79 87.00 61.53 0.52 652.59 245.09 60.85 0.85 0.00 350.53 0.42 0.30 56.26 250.13 260.37 50.18 86.0455 4X(2 X 400) 1206 966.95 130.53 0.27 900.00 275.18 450.28 83.26 125.C CABLE C.00 400.90 217.93 572.70 200.58 148.0900 4X(1 X 500) 687 550.0960 4X(1 X 240) 453 362.06 144.08 288.25 62.85 0.82 72.L.44 185.00 625.10 - 1304.85 0.45 192.53 0.021 0.99 55.PH LV POWER FEEDER LAID IN AIR .85 0.01 531.85 0.34 53.30 72.61 103.18 81.01 64.14 71.0910 4X(1 X 400) 603 483.46 123.53 0.86 Page 34 of 44 0.87 371.48 61.85 0.: DPCT-TCC-CAL-EL-00066 3.85 0.53 0.53 4X(1 X 70) 199 159.17 - - - - .1600 0.0990 4X(1 X 185) 372 297.801 % AT F.29 0.2480 0.55 61.45 108.48 64.From LV Switch Board to Distribution Panels CLIENT: STATE OF QATAR .F xVOLT) 265.04 98.67 55.24 51.14 - 576.00 650.68 695.21 0.02 82.63 62.23 576.60 144.01 57.87 52.53 76.03 56.85 0.14 74.53 72.02 49.53 0.58 164.3430 0.59 108.0638 0.80 62.49 55.37 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) 652.ccc.C COSΦ SINΦ AMPS** 40.61 54.53 219.0991 0.48 74.85 0.72 106.79 501.85 0.57 77.00 450.63 82.00 200.53 0.34 368.04 92. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING kW LOAD F.48 78.11 384.22 155.00 500.53 0.85 0.84 122.91 52.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * 4X(1 X 50) 154 123.0517 0.53 0.53 0.38 132.00 250.00 300.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 25.74 72.53 0.0870 4X(1 X 630) 808 647.26 326.00 425.00 325.00 175.00 0.23 62.06 192. 34 0.60 0.0870 0.85 0.ccc.58 164.00 491.00 368.84 326.0960 0.00 327.53 100.85 0.53 400.95 130.85 0.13 260.0 0.41 % AT F.86 4X(1 X 70) 180 73.22 155.00 736.53 650. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) LOAD IN RATING LOAD COSΦ SINΦ kW F.03 - (Vd%) x V x 1000 x n SQRT(3) x IN x (RcosΦ + XsinΦ) 652.13 217.82 - ***L = 439.04 144.1290 0.53 275.38 132.00 777.0810 0.53 Document No.39 4X(1 X 185) 317 129.00 204.00 572.24 - (LOAD x 1000) (SQRT 3 x P.53 219.0990 0.0517 0.0910 0.00 900.0823 0.53 350.46 134.92 4X(1 X 400) 464 190.70 167.00 941. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.0412 742.53 225.86 4X(1 X 150) 279 114.34 0.A.26 0.11 384.0450 0.00 409.OUTDOOR 0.0930 0.53 175.3430 0.19 0.1970 0.01 0.L.85 0.44 212.53 250.F xVOLT) 265.00 - ** IN (FLC) = 168.0900 0.C 2 CABLE C.53 425.52 652.26 326.85 0.00 450.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.4940 0.62 742.42 163.00 40.84 4X(2 X 400) 928 380.00 982.95 0.15 4X(1 X 630) 587 240.00 818.60 144.08 288.85 0.26 250.00 81.1080 0.00 613.39 250.00 531.85 0.53 450.0455 0.1600 0.18 0. 01 3-PH POWER FEEDER (LAID IN DUCTS) .00 286.L.021 0.85 0.67 4X(2 X 300) 824 337.0435 0.48 4X(2 X 500) 1030 422.53 525.85 0.52 0.032 0.85 0.42 186.87 371.85 0. No.53 500.79 501.59 0.53 600.03 128.85 0.53 375.85 0.13 125.31 494.84 0.85 0.53 325.06 230.45 - - - - .15 296.96 148.85 0.53 150.85 0.53 125.77 0.93 0.53 50.026 0.1010 0.ARMOURED) 50 Hz 1.58 148.97 - *MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** - * SITE CABLE RATING = CCC x DERATING FACTOR - - 122.27 0.30 4X(2 X 630) 1174 481.92 247.97 4X(1 X 120) 246 100.47 182.35 - 1152.00 163.67 0.68 0.A in mm CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.31 371.09 185.76 146.00 1063.80 4X(1 X 95) 217 88.69 - 311.53 475.75 0.53 200.53 300.06 192.C AMPS** 25.44 0.S.90 217.46 - 1002.05 - 220.06 130.11 288. CU/XLPE/AWA/PVC (SINGLE CORE CABLE .00 245.24 4X(1 X 500) 515 211.26 434.85 0.03 0.00 1022.: DPCT-TCC-CAL-EL-00066 3.03 - 1304.From LV Switch Board to Distribution Panels CLIENT: STATE OF QATAR .44 185.83 4X(1 X 300) 412 168.85 0.48 110.35 - 576.00 859.85 0.85 0.13 143.53 575.2480 0.51 - 501.56 167.85 0.26 125.85 0.61 - 365.74 121.0638 0.42 0.00 695.85 0.0418 0.70 200.23 576.04 164.NEW PORT PROJECT STEERING COMMITTEE 4X(1 X 50) 146 59.0991 0.00 122.6/1 kV.45 - 1484.36 0.10 0.92 0.gr APPENDIX : 22 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR CABLE SPECIFICATION: FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 415 V Page 35 of 44 REV.85 0.85 0.00 654.86 0.53 550.85 0.06 144.97 4X(1 X 240) 363 148.041 0.PH LV POWER FEEDER LAID IN DUCTS (OUTDOOR) Power Distribution Feeders .53 625.36 163.L.1040 0.39 334.51 0.1140 0.53 75.85 0.15 247.45 192.11 0. 53 573.42 3269.80 0.74 98.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.92 5.RUN LAID IN AIR .60 % AT MOTOR F.50 11.87 58.PH MOTORS RUNNING 0.6/1 kV.21 81.13 26.60 0.60 0.65 3.60 0.60 0.60 0.04 19.83 5.L.13 482.60 0.LC .0856 - - - - - - - - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2895.43 0.60 0.00 55.80 0.60 0.60 0.61 96.26 43.48 52.51 196.80 0.77 156. CLIENT: STATE OF QATAR .45 449.37 0.81 1198.56 13.80 0.17 64.00 45.80 0.60 0.NEW PORT PROJECT STEERING COMMITTEE 0.96 131.00 5.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.38 1956.00 25.00 58.09 32.96 9.97 CABLE C.ON CABLE LADDER (INDOOR) From LV Switch Board to LV Motors.51 193. No. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR MOTOR IN RATING L.80 0.60 0.80 0.00 34.13 - * SITE CABLE RATING = CCC x DERATING FACTOR 4312.20 3.65 106.60 0.11 1669.17 38.43 599.60 0.61 3.60 0.30 2.43 191.60 0.50 7.00 71.95 31.68 490.80 0.00 30.R.24 321.36 718.97 239.26 95.34 269.74 57.75 1.80 0.28 180.56 329. CU/XLPE/PVC (THREE CORE CABLES .93 59.00 150.C 3X4 36.39 78.80 0.49 119.00 43.26 114.00 143.61 3.78 163.02 241.55 260.02 386.74 2397.09 2913.03 229.60 0.60 0.95 - ** IN (FLC) = - (LOAD x 1000) (SQRT 3 x P.80 0.33 0.60 0.64 0.06 469.00 43.96 1.59 326.5 0.29 1565.34 1316.74 1377.60 0.80 0.80 0.0933 3X6 45.30 41.0888 3 X 10 60.80 0.80 0.L.55 0.00 110.9274 0.60 0.27 49.00 Document No.12 - 7193.65 22.43 4860.80 0.48 782.00 61.00 37.90 817.22 6.60 0.60 0.C **** AMPS ** 0.89 97.C LOAD kW AMPS COSΦ SINΦ F.08 965.80 0.55 1147.01 359.58 1960.26 39.29 229.45 1930.04 1437.50 2.80 0. 01 3.80 48.00 75.00 160.55 260.80 0.R.85 313.50 22.80 0.60 0.ccc.85 278.00 15.80 0.60 0.83 15.80 0.74 7.72 2.L.80 0.60 0.S.74 71.34 78.00 185. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.00 132.PH LV MOTOR FEEDERS .80 0.F xVOLT) - - - ***L = - - (Vd%) x V x 1000 SQRT(3) x IN x (RcosΦ + XsinΦ) ****L.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.86 5.08 130.: DPCT-TCC-CAL-EL-00066 3.8783 0.00 4.51 65.20 2.25 0.80 0.00 18.30 Page 36 of 44 REV.gr APPENDIX : 23 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 2.C = 6 x F.80 0.A.87 636. 20 0.98 0.16 1315.20 0.04 19.46 3624.65 3.97 CABLE C.74 7.00 185.51 193.45 1930.23 247. CLIENT: STATE OF QATAR .20 10670.00 4.0888 3 X 10 60.ON CABLE LADDER (INDOOR) From LV Switch Board to LV Motors.98 0.61 3.64 0.98 0.30 Page 37 of 44 REV.LC .94 4176.02 386.48 52.53 573.C 3X4 36.98 0.98 0.00 150.55 260.26 43.09 32.39 78.98 0.74 57.00 34.20 0.20 0.04 16930.00 5.20 0.29 1565. CU/XLPE/PVC (THREE CORE CABLES .00 55.50 22.74 157.98 0.95 362.C **** kW AMPS ** 0.17 64.96 1.23 263.46 526.72 2.22 6.20 0.NEW PORT PROJECT STEERING COMMITTEE 0.01 3.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.74 1377.57 208.L.13 358.90 569.00 58.98 0.20 0.27 717.62 986.00 132.00 15.08 130.98 0.0856 - - - - - - - - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 10873.83 5.13 1235.98 0.47 181.94 213.75 1.C = 6 x F.81 - * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = - - (LOAD x 1000) (SQRT 3 x P.05 494.98 0.98 0.43 191.STARTING LAID IN AIR .20 0.96 9.0933 3X6 45.8783 0.65 106.19 417.06 469.20 0.00 61.45 284.81 7347.: DPCT-TCC-CAL-EL-00066 3.20 0.77 156.98 0.00 110.24 321.36 906.20 0.86 5.37 0.F xVOLT) - ***L = - - - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.31 2631.20 0.gr APPENDIX : 24 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 15 0.39 835.20 0.9274 0.00 45.34 78.85 278.30 2.PH MOTORS STARTING 0.98 0. No.33 0.R.67 7178.92 5.00 75.R.20 0.98 0.85 313.ccc.66 25056.07 679.67 1794.20 0.86 15791.20 0.00 18.65 22.61 3.98 0.L.00 37.20 3.20 0.98 0.20 2.29 229.98 0.00 25.55 1147.62 5263.03 229.27 1812.87 636.20 0.89 8352.28 4942.20 0.00 43.C MOTOR LOAD AMPS RATING COSΦ SINΦ F.50 7.55 0.17 38.98 0. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.98 0.13 26.11 1669.20 0.R.56 13.20 0.80 1138.00 160.98 % AT MOTOR L.98 0.20 0. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.A.00 Document No.20 0.50 11.43 0.97 2088.00 30.26 114.PH LV MOTOR FEEDERS .98 0.20 0.98 0.92 250.95 31.98 0.55 260.61 179.98 0.03 11389.6/1 kV.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.98 1566.83 15.25 0.48 782.40 338.61 146.26 95.20 0.S.20 0.30 41.51 2847.50 2. 78 163.8783 0.80 0.51 196.60 0.74 71.80 0.50 22.R.55 0.74 1377.74 98.60 0.28 180.95 31.LC .01 359.30 41.60 0.60 0.74 57.60 - 2895.96 131.55 1147.49 119.26 43. CLIENT: STATE OF QATAR .80 0.04 19.89 97.56 13.00 160.R.80 50 Hz 2.00 5.C % AT MOTOR L.34 1316.00 185.43 4860.50 7.34 78.80 0.00 45.80 0.61 3.06 469.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.L.45 1930.00 132.80 0.09 2913.80 0.80 0. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.80 48.96 9.80 0.gr APPENDIX : 25 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: CABLE C.20 3.90 817.03 229.80 0.80 0.00 150.25 0.51 65.PH MOTORS STARTING/ RUNNING 0.60 0.80 0.60 0.83 5.22 6.13 26.53 573.60 0.60 0.00 55.00 4.60 0.95 - ** IN (FLC) = - - (LOAD x 1000) (SQRT 3 x P.60 0.43 0.00 43.00 15.08 965.00 18.17 38.00 34.86 5.75 1.00 37.C MOTOR LOAD AMPS RATING COSΦ F.80 0.27 49.42 3269.R.60 0.80 0.24 321.97 239.80 0.ON CABLE LADDER (INDOOR) From LV Switch Board to LV Motors.80 0.60 0.L.26 39.58 1960.87 58.50 11.77 156.ccc.00 30.C 3X4 36.29 229.9274 0.43 191.: DPCT-TCC-CAL-EL-00066 3.59 326.80 0.60 0.60 0.09 32.00 110.SELECTION LAID IN AIR .29 1565.11 1669.30 2.56 329.60 0.87 636.74 7.39 78.60 0.02 241. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.08 130.6/1 kV.60 0.00 75.43 599.60 0.80 0.0933 3X6 45.33 0.00 58.0888 3 X 10 60.61 3.00 25.L.81 1198.UNARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP (Run) = MAXIMUM PERMISSIBLE VOLT DROP (Starting) = DERATING FACTOR = 0.A.65 106.02 386.S.83 15.04 1437.68 490.61 96.00 143.26 95.00 61.80 0.51 193.72 Page 38 of 44 REV.38 1956.48 782.13 482.12 - 7193.60 0.30 0.60 0.55 260.60 0.45 449.37 0.00 Document No.97 % AT MOTOR F.36 718.PH LV MOTOR FEEDERS .48 52.60 0.65 22. 01 3.00 43.NEW PORT PROJECT STEERING COMMITTEE 2.17 64.13 - 4312.34 269.80 0.85 278.26 114.20 2.55 260.60 0.50 2.C = 6 x F.80 0.92 5.74 2397. No.85 313.80 0.80 0.80 0.65 3.93 59.21 81.60 0.C **** kW AMPS ** 0.F xVOLT) - ***L = - - - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.0856 - * SITE CABLE RATING = CCC x DERATING FACTOR - - - - - - - - - - - - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** SINΦ 0.80 0.5 15 0.64 0.00 71.96 1.60 0.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST. CU/XLPE/PVC (THREE CORE CABLES . 16 511.15 38532.60 0.0710 3 X 240 430 352.78 163.31 63850.55 939.39 78.92 0.66 - 112528.80 0.80 0.60 0.75 213.41 21148.61 - (Vd%) x V x 1000 SQRT(3) x IN x (RcosΦ + XsinΦ) ****L.06 112.00 319.00 143.60 0.23 385.56 788.00 159.60 0.00 61.02 1073.38 0.61 3.0888 3 X 10 60.37 14424.27 13435.74 7.99 787.38 1956.51 65.60 0.83 15.50 2.38 9504.77 15749.48 52.9274 0.83 5.02 782.01 359.0823 3 X 25 106.00 49.64 236.18 792.35 3564.36 718.gr APPENDIX : 26 CLIENT: STATE OF QATAR .05 570.PH LV MOTOR FEEDERS .60 0.75 1.21 4295.23 31499.F xVOLT) 23640.87 58.74 760.00 25.09 950.47 4752.: DPCT-TCC-CAL-EL-00066 3.34 3606.08 3940.88 7921.25 0.27 145.0750 3 X 70 200 164.45 1930.73 432.42 3269.75 96.0720 3 X 120 275 225.97 239.6/1 kV.12 1147.69 177.47 721.00 150.40 196.94 1442.88 19009.33 0.0740 3 X 95 238 195.00 Document No.55 175.02 386.38 7033.48 173.29 1878.17 64.30 512.52 5.23 15973.11 671.80 0.10 255.70 1043.00 30.26 95.43 191.60 % AT MOTOR F.73 131.48 782.00 15.06 290.22 233.89 142.R.28 - 43272.59 326.C LOAD kW AMPS COSΦ SINΦ F.ON CABLE LADDER (INDOOR / OUTDOOR) From LV Switch Board to LV Motors.47 1875.28 26870. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.24 1089.6686 0.24 - 57028.39 1970.343 0.66 1278.NEW PORT PROJECT STEERING COMMITTEE CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 2.80 0.80 0.60 0.80 0.73 360.21 81.21 584.47 1980.09 2913.89 396.60 0.C 3X4 36.27 128.46 268.83 11774.59 76032.00 160.06 469. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR MOTOR IN RATING L.96 131.41 - 80610.78 1.60 0.42 3149.21 3756.82 259.34 78.37 0.08 130.ccc.45 235.L.78 0.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.80 0.11 187.0710 3 X 150 313 256.32 6717.80 0.C **** AMPS ** 0.29 937.80 0.01 382.13 2687.28 180.72 190.56 329.13 10745.28 475.96 355.60 0.94 3750.00 18.24 2294.35 521.60 0.197 0.S.25 14227.11 1669.00 5.50 147.49 638.85 313.60 0.04 5114.43 0.77 156.93 - ** IN (FLC) = 11268.06 688.71 1574.00 105.20 2.65 22.94 5906.03 806.00 64.65 648.21 152.36 37509.06 1343.21 573.08 965.PH MOTORS RUNNING 0.58 1960.34 1316.51 1074.10 5122.51 196.68 490.0856 3 X 16 79.46 - ***L = 31299.50 11.84 366.40 156.50 22.91 76.51 1089.67 447.90 817.55 260.77 491.80 31282.98 2147.82 282.07 704. CU/XLPE/SWA/PVC (THREE CORE CABLES .00 185.72 2.60 0.49 461.29 229.86 5.494 0.248 0.68 312.35 144.34 312.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.57 5038.61 96.60 0.74 71.01 537.60 0.41 330.51 465.12 187.02 241.75 2608.20 3.80 0.99 1277.80 0.33 625.80 0.80 48.94 1296.95 2557.5 0.38 0.55 260.L.02 930.98 157.80 0.69 93.89 97.70 183.00 37.14 9160.60 0.81 152.77 178.L.30 41.40 197.42 983.28 394.02 1477.50 7.60 0. 0.18 3664.76 36641.00 75.86 944.31 711.22 117.A.26 43.53 573.13 26.04 19.87 636.22 6.48 1520.80 0.00 36.18 46500.66 422.C = 6 x F.89 10738.76 544.03 1832.55 1147.60 0.80 0.27 - 7193.50 198.07 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2895.74 98.63 256.80 0.80 0.0933 3X6 45.76 12787.95 31.60 0.19 1900.96 1.RUN LAID IN AIR .56 7880.53 18754.03 174.04 1437.0710 3 X 185 359 294.24 321.80 0.74 1377.0799 3 X 50 159.89 42954.927 0.20 7820.13 482.18 375.83 51149.09 32.34 269.14 - 17426.22 375.51 193.38 240.39 11470.09 129.60 0.56 13.26 2592.00 86.00 214.56 7874.00 4.LC .80 0.28 128.35 22940.37 268.82 CABLE C.30 2.90 3.57 3556.64 0.67 - 94499.00 130.16 0.25 19669.60 0.32 1452.28 1956.00 132.21 1422.60 0.30 Page 39 of 44 REV.R.61 29238.87 7614.83 211.0710 68821.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.00 0.80 0.54 387.33 107.100 0.73 1125.51 525.10 4301.82 - (LOAD x 1000) (SQRT 3 x P.85 278.4666 0.129 0.55 0.33 316.34 916.8783 0.14 5216.80 0.04 2686.26 114.94 2904.54 1966. 01 3.05 229.45 449.20 7212.80 0.34 9377.50 0.29 1565.61 3.80 0.0817 3 X 35 129.59 5735.00 110.00 10433.60 0.80 0.13 580.05 2704.160 0.96 9.00 29.10 4917.47 770.03 229.80 0.43 599.74 2397.69 6480.29 5808.29 315.60 0.61 292.43 4860.00 55.15 1280.17 38.66 0.65 106.99 260.81 1198.00 429.83 152.49 119. No.32 3128.53 25921.81 54466.60 0.00 45.60 0.74 57.00 71.26 - * SITE CABLE RATING = CCC x DERATING FACTOR 4312.04 1564.80 0. 79 2873.74 10831.4940 0.71 - 114677.09 905.45 35070.20 0.61 3.37 5415.20 0.20 0.20 0.29 363.08 4815.05 2302.96 32570.24 44414.79 8471.81 77485.20 0.20 0.82 2630.00 1282.00 37.69 569.00 61.73 1748.50 2.20 0.55 260.87 636.23 10663.04 19.18 23592.43 986.73 65670.0856 3 X 16 79.44 1053.10 2665.48 256.S.48 287.27 338.92 57474.67 12825.38 4176.0720 3 X 120 275 225.22 542.79 51904.93 1952.23 1228.77 6995.98 0.53 451.83 5.07 1083.98 0.34 7173.54 2407.13 1730.89 307.02 181.20 0.50 1039.0710 3 X 150 313 256.86 3283.68 589.57 368.: DPCT-TCC-CAL-EL-00066 3.82 CABLE C.59 328.98 0.09 25650.26 469.20 0. No.37 - 135549.26 95.74 418.91 1315.75 1540.34 78.73 6567.29 2954.74 1377.55 1320.00 699.71 592.65 22.0817 3 X 35 129.67 2259.98 0.65 1477.47 1235.0998 0. CU/XLPE/SWA/PVC (THREE CORE CABLES .77 156.6686 0.L.98 0.43 13328.26 43.20 0.R.04 362.00 64.36 4186.72 2107.48 782.44 519.99 382.50 240.01 3497.20 0.20 0.74 679.95 1674.98 0.89 21073.37 4941.96 9.16 1831.95 31.00 349.25 0.44 4214.25 25056.72 2359.78 799. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.23 7385.98 0.98 0.0710 126443.00 2079.92 66022.51 61613.00 30.63 8650.00 36.20 0.10 2220.C MOTOR LOAD AMPS RATING COSΦ SINΦ F.3425 0.C **** kW AMPS ** 0.59 2606.55 1332.61 614.00 150.PH MOTORS STARTING 0.13 26.37 3623.A.64 0.00 86.38 1138.33 1793.98 0.98 0.24 321.15 213.48 7167.63 240. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.98 0.LC .20 0.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.64 656.39 78.29 247.50 1129.71 439.00 49.73 2565.82 738.94 1811.0750 3 X 70 200 164.77 291.9300 0.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.98 0.31 1911.71 9087.35 702.40 42147.40 - * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.50 0.15 2166.51 193.1290 0.29 1565.03 229.00 29.97 7902.11 481.00 5.19 802.20 0.3300 0.85 313.47 207.42 45183.49 11103.97 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 10870.18 263.45 1930.89 701.2480 0.34 4518.00 160.74 57.61 497.37 977.07 3070.9270 0.74 - 153900.98 0.28 24894.39 1566.ON CABLE LADDER (INDOOR / OUTDOOR) From LV Switch Board to LV Motors.00 52126.10 521.83 15.82 7345.29 16417.28 38225.57 9556.30 2.78 48158.74 3244.20 0.PH LV MOTOR FEEDERS .47 837.50 11.32 3080.66 0.00 Document No.20 0.48 21662.69 12039.81 36843.07 256.00 75.gr APPENDIX : 27 CLIENT: STATE OF QATAR .68 85434.26 17301.20 0.39 1708.27 3635.68 16930.02 9618.85 278.98 0.28 54035.72 - 144475.00 15.38 0.0823 3 X 25 106.0933 3X6 45.43 191.C 3X4 36.98 0.R.STARTING LAID IN AIR .NEW PORT PROJECT STEERING COMMITTEE CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 15 0.57 43911.08 130.75 11389.55 630.4666 0.L.30 Page 40 of 44 REV.83 308.96 1.70 1436.17 22591.75 1.16 1146.36 361.75 8352.98 0.64 9029.73 5747.30 1549.03 4061.16 0.20 0.98 0.33 36351.38 0.C = 6 x F.35 444.23 284.55 0.36 526.0799 3 X 50 159.00 185.98 % AT MOTOR L.94 19112.74 513.04 26657.29 229.87 1080.75 1628.90 3.00 105.88 753.34 1355.47 5130.74 7.63 3822.70 1303.09 32.87 1539.98 0.44 540.86 1264.03 432.50 3257.27 660.20 3.96 976.20 0.98 0.85 6161.98 0.59 15403.61 3.05 17488.35 273.94 350.ccc.04 649.20 0.0740 3 X 95 238 195.52 91587.50 22.0710 3 X 185 359 294.55 260.27 12281.65 774. 01 3.74 6107.8800 0.R.54 541.04 417.58 915.17 38.44 2847.92 0.1604 0.79 225.76 1203.00 4.36 4998.17 64.60 10536.20 2.02 386.37 1641.98 0.72 666.57 248.74 518.37 0.98 0.72 2.74 8142.36 5212.00 45.55 1147.30 41.60 0.00 0.27 103986.77 1444.26 114.00 130.78 0.13 6140.65 5260.21 421.98 0.20 0.56 13.13 555.19 2088.67 51300.87 855.57 24079.48 52.20 0.06 469.95 15782.F xVOLT) ***L = 79972.80 494.79 5898.13 717.6/1 kV.43 0.76 - 97712.35 11295.76 6664.71 97618.36 1179.70 854.71 908.0888 3 X 10 60.26 260.00 110.67 69954.22 6.06 865.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.78 955.51 250.11 1669.20 0.11 288.46 16747.44 1110.86 5. 0.65 106.32 4325.85 637.05 616.46 325.52 5.20 0.53 573.98 0.45 64988.00 18.05 295.41 878.46 574.13 814.00 132.98 0.06 4441.07 358.74 1817.20 0.00 55.78 1.51 327.15 400.50 7.08 835.1970 0.97 13031.95 14368.0710 3 X 240 430 352.97 16285.63 - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.00 25.93 29540.85 444. 0710 68821.C MAXIMUM PERMISSIBLE VOLT DROP (Starting) = 15 DERATING FACTOR = 0.0710 3 X 185 359 294.05 570.12 187.13 21148.0710 3 X 150 313 256.L.26 95.34 939.55 260.60 0.00 45.45 1930.39 78.20 7820.129 0.16 511.11 1669.29 5808.50 2.33 0.60 0.34 312.76 36641.25 0.77 128.80 0.60 0.60 0.21 152. No.27 236.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.34 916.80 0.59 5735.00 71.80 0.73 1125.61 7614.43 599.25 5122.11 671.80 0.0823 2895.37 3756.17 64.91 145.0817 3 X 35 129.160 0.80 0.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.100 0.80 0.29 229.96 584.83 51149.95 31.00 18.57 7212.50 11.0710 3 X 240 430 352.14 117.82 282.80 0.00 160.35 983.09 2913. CU/XLPE/SWA/PVC (THREE CORE CABLES .37 0.81 1198.28 177.45 449.48 292.32 6717.57 5038.01 382.07 1452.52 5.00 260.33 316.00 15.12 1147.80 0.20 2.23 31499.53 25921.26 2592.38 96.66 - 112528.07 MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** SINΦ 0.494 0.50 147.72 190.10 255.24 321.36 37509.27 13435.98 157.21 7921.51 465.61 76.51 1089. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.89 788.51 525.75 159.50 7.80 3X4 36.84 366.5 % AT MOTOR L.61 96.75 1.43 191.00 110.47 187.14 14424.66 721.10 11774.24 2294.89 10738.68 491.60 0.80 0.47 4752.R.50 0.29 315.13 482. Page 41 of 44 REV.06 198.0740 3 X 95 238 195.06 1343.31 1442.60 0.28 711.18 3664.19 1900.78 0.56 329.08 10433.82 259.26 114.47 3940.SELECTION LAID IN AIR .04 19.60 0.73 211.80 0.60 0.66 1278.13 1074.06 688.26 43.51 65.00 29.00 143.55 175.60 0.55 0.00 214.38 9504.70 183.29 10745.70 1966.15 2904.60 0.06 469.39 3556.21 2704.22 197.49 461.63 580.C **** kW AMPS 0.85 278.80 0.49 638.77 178.8783 0.40 312.R.78 1.22 6.ARMOURED) FREQUENCY 50 Hz % AT MOTOR F.00 86.02 1073.56 14227.41 43272.6686 0.89 97.28 180.28 26870.30 2.36 718.51 1956.00 521.32 2686.64 0.43 4860.197 0.60 0.80 48.60 0.64 355.69 6480.59 76032.38 0.14 9160.28 3606.05 229.00 5.00 132.55 1980.10 1280.68 490.42 3149.86 5.22 233.00 0.92 0.97 239.94 3750.99 432.33 173.34 9377.41 330.71 1574.99 787.00 ** 0.248 0.25 29238.60 0.45 394.33 625.83 23640.6/1 kV.67 447.60 0.74 2397.83 15.28 235.26 - 4312.02 782.60 0.09 950.0750 3 X 70 200 164.21 81.L.0799 3 X 50 159.55 260.gr APPENDIX : 28 CLIENT: STATE OF QATAR .00 55.94 7880.10 4301.83 5.59 326.60 0.66 0.24 - (LOAD x 1000) (SQRT 3 x P.53 18754.ON CABLE LADDER (INDOOR / OUTDOOR) From LV Switch Board to LV Motors.77 156.17 38.00 4.ccc.80 0.73 93.00 64.67 - 94499.50 22.96 9.00 130.37 268.90 3.00 19669.60 0.99 1277.80 0.75 4917.34 78.73 112.60 0.74 98.04 1437.61 3.00 429.35 22940.21 4295.29 1565.83 360.65 106.LC .41 - 80610.18 46500.80 0.31 63850.A.75 213.06 537.82 CABLE C.00 61.22 792.01 359.94 375.51 196.04 5216.58 1960.47 770.03 229.86 944.69 128.96 1.38 0.74 760.98 2147.38 1956.60 3 X 16 79.85 313.13 2687.72 2.88 15973.60 0.46 142.02 241.38 7033.C = 6 x F.0888 3 X 10 60.76 12787.65 648.76 544.61 3.65 22.60 0.51 193.49 119.74 57.21 152.03 268.32 3128.87 17426.C MAXIMUM PERMISSIBLE VOLT DROP (Run) = 2.80 0.77 15749.60 0.21 573.00 25.20 1878.80 0.02 386.11 396.90 817.80 0.42 256.60 0.95 2557.: DPCT-TCC-CAL-EL-00066 3.55 1147.34 1316.28 475.88 19009.30 1089.9274 0.F xVOLT) ***L = 57028.53 573.27 - 7193.00 185.87 58.74 7.42 3269.09 129.05 704.35 144.34 269.80 0.01 1043.30 41.18 1477.20 3.13 26.R.46 422.74 1377.56 1422.00 30.03 1832.30 0.48 1520.00 37.40 156.24 1970.02 930.89 42954.81 54466.16 0.35 3564.S.00 36.50 319.83 152.96 131.89 240.80 0.29 937.L.23 31299.23 385.80 0.39 11470.4666 0.80 0.08 965.80 31282.0933 3X6 45.02 2608.27 196. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.80 0.C MOTOR LOAD AMPS RATING COSΦ F.00 105.93 - ** IN (FLC) = 11268.0720 3 X 120 275 225.54 387.82 131.80 0.80 0.NEW PORT PROJECT STEERING COMMITTEE CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V Document No.0856 * SITE CABLE RATING = CCC x DERATING FACTOR 3 X 25 106.80 0.47 1875.56 13.56 7874. 01 3.04 1564.927 0.03 806.00 49.60 0.08 130.78 163.94 1296.60 0.60 0.94 5906.00 75.61 - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.04 5114.00 150.48 782.15 38532.43 0.PH MOTORS STARTING/ RUNNING CABLE SPECIFICATION: 0.54 512.48 52.18 375.69 174.09 32.81 290.343 0.74 71.60 0.PH LV MOTOR FEEDERS .87 636.40 107. 42 3149.08 130.82 - 80610.51 193.24 1089.50 198.43 191.33 316.34 78.60 0.35 3.51 196.38 1956.45 235.34 916.66 1278.42 983.03 1832.96 9.50 11.0823 3 X 25 96 43.00 5.61 3.82 - (Vd%) x V x 1000 SQRT(3) x IN x (RcosΦ + XsinΦ) ****L.47 721.A.60 0.00 25.00 4.72 2.51 - * SITE CABLE RATING = CCC x DERATING FACTOR 4312.04 19.10 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 2895.0998 0.2480 0.13 26.02 782.77 156.34 9377.F xVOLT) 23640.55 1147.00 55.11 187.87 7614. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR MOTOR IN RATING L.80 0.0817 3 X 35 114 51.16 511.09 32.31 63850.54 387.PH MOTORS RUNNING 0.55 939.06 1343.80 0.53 25921.NEW PORT PROJECT STEERING COMMITTEE 0.00 429.37 0.65 22.80 0.0720 3 X 120 232 104.60 0.35 22940.60 0.80 0.74 98.04 1564.83 11774.76 544.73 432.23 385.64 236.95 31.08 965. CU/XLPE/SWA/PVC (THREE CORE CABLES .47 4752.30 0.6686 0.80 31282.94 1442.L.17 64.87 636.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.80 0.9274 0.61 29238.60 0.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.0710 3 X 240 347 156.50 7.89 10738.60 % AT MOTOR F.80 0.60 0.60 0.06 469.81 1198.83 - 43272.6/1 kV.00 15.95 2557.60 0. No.00 319.05 2704.26 43.02 1073.80 0.34 1316.70 1043.94 1296.00 61.37 - 94499.81 - 17426.18 792.00 110.3300 0.00 Document No.48 1520.49 461.61 3.56 13.30 41.14 9160.39 78.83 15.80 0.21 4295.02 386.19 1900.25 0.60 0.S.45 CABLE C.0710 3 X 185 294 132.49 - ** IN (FLC) = 11268.9270 0. CLIENT: STATE OF QATAR .80 0.R.76 12787.60 0.32 6717.R.3425 0.80 0.77 491.43 0.06 290.54 1966.33 625.68 490.29 937.0799 3 X 50 137 61.15 1280.30 Page 42 of 44 REV.56 329.15 38532.61 292.28 180.17 38.29 1565.80 0.13 482.32 3128.95 0.99 260.41 330.0856 3 X 16 71 31.94 3750.80 0.81 54466.60 0.89 42954.61 96.99 787.53 573.63 256.21 573.41 21148.47 770.25 14227.88 19009.85 313.04 1437.34 269.65 648.80 0.10 5122.43 4860.89 396.29 5808.0933 3X6 43 19.09 2913.29 1878.20 3.99 1277.53 18754.96 355.58 1960.50 22.07 704.76 36641.01 382.85 278.31 711.05 570.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.60 0.74 7.PH LV MOTOR FEEDERS .30 2.55 0.21 584.59 5735.60 0.59 76032.4666 0.18 3664.4940 0.8783 0.60 0.11 671.78 163.00 75.56 788.30 5.C = 6 x F.00 132.L.59 326.80 0.18 375.14 5216.51 465.36 37509.27 13435.08 3940.80 0.60 0.68 312.23 31499.46 268.00 - 7193.80 0.98 2147.00 10433.03 229.60 0.0740 3 X 95 199 89.36 718.1970 0.49 638.00 37.1604 0.02 1477.97 239.55 260.35 3564.60 0.60 0.LC .21 1422.66 422.30 0.15 0.L.65 0.30 512.25 19669.64 0.96 131.77 15749.28 475.80 0.74 1377.45 449.73 1125.: DPCT-TCC-CAL-EL-00066 3.13 10745.57 5038.23 15973.03 806.12 1147.11 1669.0888 3 X 10 57 25.00 45.01 537.60 0.39 11470.80 0.80 0.40 - ***L = 31299.02 930. 01 3.18 46500.74 57.80 0.55 260.80 0.00 30.50 2.26 114.80 0.95 1.74 2397.40 0.26 2592.60 0.20 7212.48 52.00 18.39 1970. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.56 7874.22 6.47 1875.20 0.60 0.26 95.48 782.5 0.80 0.32 1452.28 394.80 0.86 5.94 2904.10 4301.C 3X4 34 15.83 51149.03 - (LOAD x 1000) (SQRT 3 x P.84 366.34 3606.65 2.22 375.90 817.04 5114.80 0.75 1.73 360.69 6480.01 359.51 1089.gr APPENDIX : 29 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 2.24 2294.74 760.24 321.00 143.0750 3 X 70 171 76.60 0.21 3756.13 2687.20 7820.67 447.C LOAD kW AMPS COSΦ SINΦ F.00 185.55 0.86 944.42 3269.10 4917.0710 68821.65 106.1290 0.80 0.60 0.02 241.56 7880.45 1930.RUN LAID IN DUCTS (OUTDOOR) From LV Switch Board to LV Motors.00 150.38 - 57028.34 312.00 160.00 - 112528.83 5.43 599.37 14424.51 525.47 1980.38 9504.04 2686.C **** AMPS ** 0.88 7921.45 0.ccc.06 688.60 0.35 521.60 0.94 5906.75 2608.57 3556.96 1.29 315.28 26870.0710 3 X 150 261 117.29 229.71 1574.38 7033.51 1074.09 950.28 1956.13 580. 74 1377.45 35070.23 589.20 0.76 1203.78 955.70 1303.81 77485.95 14368.27 3635.98 0.85 637.08 4815.20 0.87 636.86 1264.98 0.53 573.98 0.63 8650.20 0.00 37.39 835.00 160.59 - 153900.0720 3 X 120 232 104.0856 3 X 16 71 31.03 4061.48 7167.13 555.34 1355.98 0.96 32570.30 41.31 2631.20 0.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.17 38.15 2166.00 5.98 0.94 4176.85 278.92 66022.36 5212.74 1817.00 15.20 0.4666 0.98 0.16 1146.NEW PORT PROJECT STEERING COMMITTEE 0.42 45183.33 36351.04 362.92 57474.55 1147.03 11389.30 0.R.98 0.23 1228.00 45.27 12281.20 0.36 1179.20 10670.43 191.11 1669.65 0.62 986.00 4.C 3X4 34 15.05 17488.44 4214.20 0.98 0.0823 3 X 25 96 43.37 977.00 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** 10873.45 64988.40 42147.07 1083.32 3080.64 0.77 156.70 854.10 2220.61 3.PH LV MOTOR FEEDERS .89 21073.20 0.00 699.90 569.20 0.20 0.13 26.46 574.78 48158.98 0.09 906.65 22.26 43.98 0.50 7. 01 3.9270 0.20 0.65 2.77 1444.31 1911.60 10536.27 717.A.51 2847.11 481.55 260.50 2.35 3.37 3624.00 Document No.36 4186.44 1110.30 0.95 1.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.71 9087.15 0. CLIENT: STATE OF QATAR .29 2954.79 8471.28 54035.32 4325.00 52126.26 17301.29 358.55 0.85 6161.66 25056.gr APPENDIX : 30 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: 50 Hz 15 0.73 5747.95 0.78 799.26 95.74 679.6/1 kV.56 13.95 1674.50 11.82 738.64 9029.0750 3 X 70 171 76.71 592.77 6995.83 15. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.71 97618.97 7902.1604 0.54 2407.98 0.06 865.37 4942.89 8352.46 16747.73 2565.00 132.98 0.98 0.PH MOTORS STARTING 0.20 0.13 814.86 3283.48 52.74 8142.67 1794.98 0.00 30.76 6664.16 1831.65 774.75 1628.00 2079.61 3.45 CABLE C.34 4518.3300 0.26 114.70 1436.48 21662.20 0.41 878.67 12825.55 260.67 51300.87 855.44 - 97712.73 1748.98 0.80 494.37 5415.49 11103.87 1080.62 5263.45 1930.40 0.02 614.43 0.0710 126443.4940 0.6686 0.98 0.55 1320.47 837.: DPCT-TCC-CAL-EL-00066 3.03 229.98 0.17 64.00 18.98 % AT MOTOR L.0817 3 X 35 114 51.98 0.L.05 2302.74 7.72 2.87 1539.06 469. No.10 2665.19 802.20 0.98 1566.34 78.20 0.30 2.72 2107.1970 0.74 57.06 4441.67 69954.74 6107.25 0.0710 3 X 185 294 132.75 1.51 649. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.9274 0.30 Page 43 of 44 REV.96 1.39 1708.20 0.98 0.20 0.47 5130.48 782.59 15403.55 630.89 - * SITE CABLE RATING = CCC x DERATING FACTOR ** IN (FLC) = (LOAD x 1000) (SQRT 3 x P.64 656.00 55.20 0.22 - 114677.27 103986.69 12039.10 - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.01 3497.72 666.0710 3 X 240 347 156.81 36843.18 23592.20 0.36 4998.L.00 75.52 91587.00 185.28 24894.59 2606.00 1282.15 701.09 32.0933 3X6 43 19.C = 6 x F.74 10831.97 13031.08 130.82 7347.13 1730.R.16 1315.37 0.20 0.51 193.98 0.0799 3 X 50 137 61.17 22591.00 110.LC .58 915.47 1235.2480 0.04 19.65 1477.13 6140.29 229.96 9.45 0.85 313.22 6.20 3.67 7178.00 150.86 15791.50 3257.50 22.65 106.02 386.96 976.55 1332.50 1039.79 2873.24 321.29 16417.68 85434.0710 3 X 150 261 117.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP = DERATING FACTOR = 0.0998 0.73 65670.27 660.02 9618.94 1812.98 0.74 3244.37 1641.3425 0.39 78.98 0.S.C **** kW AMPS ** 0.43 13328.44 1053.09 25650.20 0.00 25.98 0.20 0.0740 3 X 95 199 89.23 7385.20 0.63 3822.67 2259.79 5898.93 1952.57 24079.05 616.95 31.94 19112.20 0.1290 0.74 513.00 61.72 2359.55 0.C MOTOR LOAD AMPS RATING COSΦ SINΦ F.20 0.0888 3 X 10 57 25.53 - 144475.04 26657.71 908.35 702.57 43911.07 3070.98 0.98 0.93 29540.04 16930.97 16285.35 11295.30 1549.50 1129.80 1138.29 1565.20 0.73 6567.97 2088. CU/XLPE/SWA/PVC (THREE CORE CABLES .28 38225.ccc.75 1540.24 44414.83 5.STARTING LAID IN DUCTS (OUTDOOR) From LV Switch Board to LV Motors.F xVOLT) ***L = 79972.8783 0.74 - 135549.51 61613.46 526.88 753.R.30 5.79 51904.86 5.57 9556.20 0. 21 4295.80 0.54 387.00 25.29 937.0817 3 X 35 114 51.51 196.33 625.67 447.65 22.94 5906.38 - (LOAD x 1000) (SQRT 3 x P.74 57.60 0.16 511.60 0.1290 0.03 806.06 688.83 23640.ARMOURED) FREQUENCY MAXIMUM PERMISSIBLE VOLT DROP (Run) = MAXIMUM PERMISSIBLE VOLT DROP (Starting) = DERATING FACTOR = 0.34 9377.90 817.65 0.0856 * SITE CABLE RATING = CCC x DERATING FACTOR 3 X 25 96 43.86 5.56 1422.02 2608.99 1277.00 - 7193.00 30.35 983.00 185.9274 0.45 394. No.29 10745.00 - 112528. 01 3.94 1296.30 0.31 1442.51 465.77 15749.60 3 X 16 71 31.02 930.18 375.01 382.60 0.80 0.L.80 0.17 38.63 580.30 5.30 1089.75 1.81 54466.02 782.3425 0.: DPCT-TCC-CAL-EL-00066 3.80 0.38 9504.66 721.80 0.60 0.36 37509.28 711.60 0.0710 3 X 240 347 156.83 51149.4940 0.68 490.74 2397.18 3664.60 0.4666 0.55 1980.65 2.96 584.22 792.C **** kW AMPS ** 0.80 0.51 525.80 0.07 1452.L.87 636.00 160.09 950.66 1278.00 4.09 2913.28 3606.0823 2895.60 0.74 1377.88 15973.00 37.49 638.1604 0.24 321.95 31.20 3.60 0.26 114.23 31299.85 278.23 31499.80 0.20 7820.35 3564.39 78.29 1565.LC .F xVOLT) ***L = 57028.60 0.R.25 0.21 7921. (CCC) TEYSEER CONTRACTING COMPANY (TCC) www.74 7.47 1875.ccc.69 6480.83 5.81 290.1970 0.73 1125.09 32.30 0.0799 3 X 50 137 61.20 1878.08 965.15 38532.10 - MAXIMUM PERMISSIBLE ROUTE LENGTH IN METERS*** SINΦ 0.C 3X4 34 15.03 1832.43 0.60 0.35 3.01 1043.08 130.42 256.00 18.42 3149.30 41.17 64.68 491.55 1147.00 132.89 42954.10 11774.47 4752.47 3940.34 939.36 718.37 3756.L.50 22.29 5808. CU/XLPE/SWA/PVC (THREE CORE CABLES .80 0.10 1280.87 17426.60 0.74 760.00 429.70 1966. IN OHM/KM (90o C) CABLE REACTANCE in OHM/KM (X) MOTOR IN L.50 319.08 10433.61 7614.50 2.43 4860.15 0.13 2687.80 0.39 3556.35 22940.0998 0.02 241.29 315.95 2557.73 236.39 11470.80 0.40 0.51 193.65 648.97 239.49 - ** IN (FLC) = 11268.6/1 kV.94 7880.94 3750.04 1564.95 0.51 - 4312.41 43272.80 0.43 191.80 0.04 5114.0720 3 X 120 232 104.80 0.37 0.61 96.04 1437.C % AT MOTOR L.C = 6 x F.80 0.gr APPENDIX : 31 CONTRAT NO: NPP/0026 PROJECT: CONTAINER TERMINAL INFRA AND UTILITY BUILDINGS CABLE SELECTION CHART FOR 415 V CABLE SPECIFICATION: CABLE C.00 5.18 1477.12 1147.55 0.80 0.2480 0.00 45.54 512.00 15.NEW PORT PROJECT STEERING COMMITTEE 2.00 143.00 61.86 944.81 1198.34 1316.34 78.45 0.PH LV MOTOR FEEDERS .33 316.00 19669. CLIENT: STATE OF QATAR .49 461.80 0.24 1970.13 21148.76 12787.56 7874.R.60 0.76 544.SELECTION LAID IN DUCTS (OUTDOOR) From LV Switch Board to LV Motors.0740 3 X 95 199 89.83 15.53 573.64 0.21 235.14 9160.84 366.61 3.59 5735.89 10738.96 9.0750 3 X 70 171 76.60 0.57 5038.15 2904.00 521.55 260.04 19.80 0.60 0.85 313.05 704.11 396.56 13.51 1956.38 1956.99 787.19 1900.61 292.C MOTOR LOAD AMPS RATING COSΦ F.45 1930.11 671.95 1.76 36641.10 4301.28 180.50 11.34 312.45 449.20 0.77 156.55 260.21 2704.72 Page 44 of 44 REV.32 2686.80 0.88 19009.06 537.60 0.75 4917.38 7033.48 782.14 14424.04 5216.11 1669.S.00 Document No.59 76032.48 1520.A in mm2 CURRENT CARRYING CAPACITY (CCC) in AMPS SITE CABLE RATING * CONDUCTOR RESIST.53 18754.53 25921.83 360.03 268.50 7.80 0.89 788.40 312.99 432.71 1574.02 1073.8783 0.34 916.03 229.26 95.82 - 80610.80 0.22 6.96 131.60 0.A.64 355.28 475.60 0.80 0.56 329.13 26.80 0.34 269.94 375.47 187.65 106.59 326.9270 0.0710 3 X 185 294 132.60 0.55 0.30 2.26 2592.00 55.61 3.5 15 0.74 98.PH MOTORS STARTING/ RUNNING 0.37 - 94499.21 573.3300 0.02 386.06 1343.80 0.05 570.41 330.51 1089.24 2294.42 3269.31 63850.46 422.00 150.80 50 Hz 2.0933 3X6 43 19.29 229.23 385.80 0.60 0.JOINT VENTURE CONSOLIDATED CONTRACTORS GROUP S.27 13435.60 0.48 52.78 163.43 599.32 3128.0888 3 X 10 57 25.80 31282.28 26870.R.77 198.73 260.96 1.30 0.0710 68821.18 46500.47 770.57 7212.01 359.60 0.58 1960.00 75.25 5122.00 110.26 43.0710 3 X 150 261 117.06 469.45 % AT MOTOR F.25 29238.56 14227.13 1074.60 0.32 6717.82 - (Vd%) x VL x 1000 SQRT(3) x I (LRC)x (RcosΦ + XsinΦ) ****L.60 0.6686 0.60 0.13 482.98 2147.60 0.
Copyright © 2024 DOKUMEN.SITE Inc.