9.1740.xx.xxx_TDL14_V3.12_eng

April 4, 2018 | Author: dotronganhtuan | Category: Power Supply, Battery (Electricity), Computer Data Storage, Rechargeable Battery, Switch


Comments



Description

DATALOGGER MeteoLOG TDL 14Instruction for use: 9.1740.xx.xxx Software-Version: as of 3.12 11/2005 Table of Contents 1. 1.1 1.2 CONSTRUCTION OF THE DATA LOGGER ............................................................ 2 Models available ...................................................................................................................................3 Mounting................................................................................................................................................4 2. OPERATION ............................................................................................................. 5 2.1 Standards Displays ..............................................................................................................................5 2.1.1 Sequence of Display Values: ..........................................................................................................5 2.2 CHANGING THE PARAMETERS .......................................................................................................13 2.2.1 STATION NAME............................................................................................................................13 2.2.2 DATE .............................................................................................................................................13 2.2.3 GSM-TIMER ..................................................................................................................................13 2.2.4 MEASUREMENT CYCLE .............................................................................................................14 2.2.5 EXTREME VALUE CYCLE ...........................................................................................................14 2.2.6 DIP-SWITCH SENSOR SETTINGS..............................................................................................15 2.2.7 CHANNEL CONFIGURATION......................................................................................................16 2.3 DATA OUTPUT.........................................................................................................................................16 2.3.1 SERIAL DATA OUTPUT ...............................................................................................................16 2.3.1.1 CONNECTING CABLE OF THE SERIAL INTERFACE ............................................................16 2.3.1.2 COMMAND FORMAT (COM1)..................................................................................................17 2.3.1.3 SERIAL DATA FORMAT ...........................................................................................................20 2.3.2 CONNECTING CABLE OF THE SERIAL INTERFACE (COM2) .................................................21 2.3.3 DATA OUTPUT OVER MEMORY-CARD ....................................................................................21 2.4 CHANGING THE STORAGE BATTERY.............................................................................................22 2.5 EXTERNAL POWER SUPPLY ............................................................................................................23 2.5.1 DATA LOGGER WITHOUT TRANSFORMER (9.1740.x0.xxx)....................................................23 2.5.2 DATA LOGGER WITH TRANSFORMER (9.1740.x1.xxx/ 9.1740.x2.xxx/ 9.1740.x4.xxx)...........23 2.5.3 DATA LOGGER WITH SOLAR PANEL (9.1740.x3.xxx/ 9.1740.x4.xxx) ......................................23 2.6 CURRENT CONSUMPTION ................................................................................................................24 2.6.1 QUERY SECONDS.......................................................................................................................24 2.6.2 QUERY MINUTES ........................................................................................................................25 2.7 MEMORY TIME PERIOD .....................................................................................................................26 2.8 CHANGING THE FUSE .......................................................................................................................27 3. 4. 4.1 TECHNICAL SPECIFICATIONS ............................................................................. 27 APPENDIX .............................................................................................................. 29 Connecting Diagrams acc. to Instruments ......................................................................................29 1 - 30 020879/11/05 1. Construction of the Data Logger The MeteoLOG TDL 14 data logger is a complete measurement system to detect and store meteorological data. The instrument is battery-operated, thus allowing it to be set up acc. to model and sensor equipment at site without any mains supply for some hours or even days. The exchangeable storage battery is situated in the data logger case. The case, which can be locked, is water-tight (IP65) and very sturdy. The case is made of stainless steel to protect the instrument from electro-magnetic fields. Furthermore, operation in a temperature range from -30° to 50°C is guaranteed. The instrument is easy to operate, either with the three keys or over the serial interface. The three keys are indicated by "<∆>", "<∇> on" and "<enter>" in the following. The instrument has a two-line, alphanumeric display. Numerous inputs are available for the connection of measured data transmitters (sensors). A maximum of 10 analog and 4 digital sensors can be connected. The measured values are saved time-controlled in a CMOS-RAM which has been secured against loss of data. This memory is organized as a ring memory and can save 256 KB. The data can be read out either over a serial interface (V.24/RS232-C or RS422) or over a memory card (option). The TDL14 with COM2 allows an additional output of the instantaneous data every second. The COM2 is not possible with the TDL14 with ultrasonic connection. An integrated lithium battery buffers the contents of the data memory and the clock operation when no other power supply is available. This means that the saved values and the time are not lost even when there is no additional power supply. Functional Arrangement of the Data Logger: 2 - 30 020879/11/05 1.1 Models available The data logger is available in different models geared to the requirements of the respective application: Order-No.:9.1740.XX.XXX Datalogger TDL 14 .X0 Power supply: 14...24 V AC/ 17...33 V AC/ integrated 12 V storage battery .X1 Power supply: an additional integrated power transformer (230 V) .X2 Power supply: an additional integrated power transformer (115 V) .X3 Power supply: solar charge regulator .X4 Power supply: solar charge regulator/ power transformer (230 V) .1X Standard .2X Calculation of the humidity from: Temperature 1 = Dry temperature of humidity 1 Temperature 2 = Wet temperature of humidity 1 Temperature 3 = Dry temperature of humidity 2 Temperature 4 = Wet temperature of humidity 2 .XX0 .XX1 .0XX .01X .50X RS232 (COM1) (optionally: memory card interface) RS422 (COM1) (optionally: memory card interface) Wind speed transmitter compact/standard and gsm (optional) COM2 and wind speed transmitter compact / standard Wind transmitter Ultrasonic Anemometer (4.3800.00.640/641) 3 - 30 020879/11/05 Four screws of 8 mm diameter are required for this.Pull back the cable until the connection is made between the cable screen and contact spring . With thin Wires without an Inner Sheath Strip back the outer sheath Pull back the screen braid approx.Guide the cable through the cable gland . 15-20mm over the outer sheath Insert the cables into the cable gland until the contact is made between the cable screen and contact spring Turn shut …. 90.Make a round cut in the outer sheath approx. depending on the model. 9-3) - Expose the screen braid approx. 60. For details. 10 mm Guide the cable through the cable gland until the connection is made between the cable screen and contact spring Turn shut…and it is ready for use! 4 . With the Standard Contacting . In order to carry out an EMC-compatible installation the cable screen/shielding is to be connected to the contact spring of the cable gland. Proceedure: 1.2 Mounting The data logger is designed to be mounted to a vertical wall. 15 mm along but do not remove the sheath . 102 and 132 mm for installation on a mast. There are special mounting sets available in the following diameters: 48.Pull off the outer sheath .Strip back the outer sheath and screen (shielding) .1. The transmitter cables are lead through the appropriate cable screwing to the connecting terminals. please refer to the connecting diagram. When Routing the Cable Screen to another Connection (see fig.Turn shut… and it is ready for use! 2.and it is ready for use! 3.30 020879/11/05 . 80. precipitation 8. first the clock and the date (see section 2. The data ring memories can be read out over the serial interface or over a memory-card (option) (see section 2. rf.measurement cycle /memory cycle .XX. radiation 7.3) should be set. . then the oldest data record is overwritten. The data logger has two data ring memories with a capacity of 256 KB. The next display value is reached by pressing the <∇> key.2) and then the measurement cycle (see section 2.00X only Datalogger: 9.telegram COM2 . Operation The data logger starts automatically as soon as the storage battery is connected. humidity 5. this indicates that the user can change this value (see 2. Once the instrument has been switched on.transmitter constants: radiation CM 3/CM 6B .date and time . temperature 1 4. 12. 14.1740. special input 5/ air pressure 6.sensor measured values: 1.e.5).1.01X 3) only Datalogger: 9.2. 2.30 020879/11/05 .Baud rate COM2 2) 1) .station name .1 Sequence of Display Values: . Where "* " appears as the first character.channel configuration . The ring memories can record data continuously i. the station name appears.2. Page 11) special input 1 special input 2 3) 2) 1) 2) only Datalogger: 9. when one of the ring memories is full.1 Standards Displays Switch the display on with key <∇> (just press briefly). The data logger is reinitialised during this process.3). special input 3/ rel. After the display has been switched on.2.1740. 13.station elevation .2. 9.extreme values cycle . 11. special input 4/ tensiometer temperature 2 temperature 3 reference/(optionally: temperature 4.2).1740. Furthermore note the sensor settings and the language (see section 2.data output leaf moistening / virtual temp. 2.XX.50X 5 . You can return to the preceding value with the <∆> key. 10. The data logger switches off automatically when no key has been activated over a period of 30 seconds or when no character was either transmitted or received over the serial interface. wind direction 3.status of the A/D converter .gsm-timer .XX. wind speed 2.baud rate COM1/memory card (option) .storage battery voltage . x00) First Class (z.3 Offset..12 X X = 0.640/641) First Class (z.50x) “ (9. 4.1740. the software version („V 3.xxx) Ultrasonic (4.05 time: 12:00:00 GSM-TIMER: 1) *PROG-Timer: X programmed X = 1.30. 4.. with which all other measurements will be corrected (is measured at the time when the instrument is switched on).3519.2) in the second line appears the language selection („Sprache:Deutsch“ or.B. 4.B.01.00X 6 .3800. 4. 4.0xx) “ “ “ “ “ (9.1x. The name (here: „THIES CLIMA“) can be up to 11 characters long..B.3515.xxx) Standard (z.xxx) Compact (z.30. Display of programmed GSM-timer STATUS OF A/D CONVERTER: 0 A/D: OK 0 512 1023 OK (A/D converter is functioning properly) Err (A/D converter defective) Self-test of the A/D converter Setpoint: 1021 ±2 Self-test of the A/D converter Setpoint: 512 ±12 Current measured offset Setpoint: 0 .1740. 1) only Datalogger: 9.B.xxx) Reed (z. Order no: (9.x00) Air transmitter PTB 100A PTB 100B PTB 100A PTB 100B PTB 100A PTB 100B PTB 100A PTB 100B PTB 100A PTB 100B 1) DATE / TIME: *date: 01.30 020879/11/05 .0xx) “ Wind speed transmitter Compact (z.xx.3303.XX.1x.xxx) Standard (z.1740.B.STATION NAME: * THIES_CLIMA TDL14 V3.00. 4.B. 4.2.xx. „9“)..1740.1x.3515.xx. this name appears on the memory card respectively it is output with the data over the serial interface.3519.B. „Lang.00.B. The software variation differentiates between the two opto-electronic wind speed transmitter models (sensor 1) and the air transmitter (sensor 5) Variation 0 1 2 3 4 5 6 7 8 9 LANGUAGE: When changing the station name (see section 2.3 Display of logger date and time.xx.3800. : English“).3350.12 “) and the software variation („0“ .640/641) Ultrasonic (4. For read-out. In the second line you find the instrument model („TDL 14“).3303.9 The station name allows the user to differentiate between the data of several stations. and then you can choose between these two modes.00.00. 4.3350.xxx) Reed (z. Please change or charge the storage battery while „!!!" still appears on the display.6V memory card in the holder of the data logger Memory Card 3.2..e.7V !!! : Voltage 2. Non-configured measurement channels („0"→ not reporting) are indicated on the display and on the serial online commands by dashes („-„).0 V OK Displays the voltage of the memory card battery: The measurement is limited to 3. BAUD RATE (COM1) / memory card * Baudrate 1: 9600 Bd 7E1 No memory card in the holder Displays the baud rate: Settings: 300 Bd. Analog measurements become imprecise below a measured voltage of 8. 4800 Bd. no (none) parity. These channels are stored with the general error identification („?"). Please Note: The storage battery should not be discharged below 10.14 Displays the configured measurement channels („1"→ reporting).0 V.7 on page 16. there is no appreciable capacity available anymore and. higher voltages are not displayed. 2400 Bd. X = 0 sensor not reporting X = 1 sensor reporting STORAGE BATTERY VOLTAGE Accumulator: OK 12. 1 stop bit. 0. (default: 9600Bd 7E1) Please note: On the beginning of operation the baud rate COM1 must be adjusted to the respective receiving instrument.6 .30 020879/11/05 . The first number to the left stands for sensor 1 (wind speed).7V Low : Voltage <2. first of all. the last for sensor 14. 1) OK : Voltage > 2.5 V OK : Voltage >11.5 V because..5 V Low: voltage <10. because the operating life of the battery will be considerably shortened..6.CHANNEL CONFIGURATION: *Channel config: xxxxx xxxxx xxxx Sensor 1. 9600 Bd 7 data bits (even) parity 1 stop bit or 8 data bits. 1200 Bd.. i.. The function of the „MC“ is not guaranteed below 2. The actual storage battery voltage is higher (approx. Please note: To Change the channel configuration see chapter 2.6 V 7 .5V Charge/ change batteries recommended! Displays the measured voltage of the storage battery.5 V. This COM-Port is designed to communicate with “Mevis” and so on. We recommend that you change the battery when "!!!" appears on the display.2.2 V). 11. secondly.. 600 Bd.5 V !!!: Voltage 10. xx.however with STX at the beginning of the telegram. output of the instantaneous wind value for THIES wind display LED (4. (for ex. This telegram is conceived only for the combination of digital display with parallel- 2) only Datalogger: 9. Telegram COM2 2) *Telegramm COM2: NNNNNNNN Display of output telegram at interface COM2.322x. Order of sensors like “online 2“. 1 stop bit (8N1) or 7 data bits. 300 Bd. 600 Bd. 1 Stop bit ( 7E1) Please note: On the beginning of operation the baud rate COM2 must be adjusted to the respective receiving instrument.30 020879/11/05 . "Test" Test-output ("The quick brown fox jumps over the lazy dog"). Please take care that the same baud rate and parity is set with all parallel-connected instruments! "AMS sensor" output telegram for the connection of a sensor electronics.X1X 8 . 1 200 Bd. however output of the mean value of the last storage time.1. The output interval of the telegrams is every second. 2 400 Bd 8 data bits.BAUD RATE COM2 2) * Baudrate 2: 9600 Bd 7E1 (default: 9600Bd 7E1) Display of baud rate and parity for COM2.). however without information on time and date. no telegram online-output of all instantaneous values (command "mm" as with COM1. The COM2 is only designed to outputs the Online-Telegrams. AMS11 required baud rate 2400Bd7E1).xxx required baud rate 1200Bd7E1) output of the telegrams online and LED as one telegram. even parity.2) like „online“ .1740.XX. ref. and ETX at the end of the telegram like „online“.. no parity. to 2.3. which can be used by “Meteo-Online” (for ex. "Off" "Online" "Online 2" "Online ls" "Wind-LED" "Online + LED" connected LED-display. 12. CM3 Konst.30 020879/11/05 . Settings memory cycle: 1. SENSOR MEASURED VALUES: Please note the DIP switch setting on certain sensors (SW4.35.6). 2. Settings extreme value cycle: 1. 30 and 60 minutes (see section 2. 3. 15.N m/s Outputs the mean wind speed per second (measured once a second). 3. 10.0000. 5. 5. 15. so-called "QFE").2. 15. 60 seconds. 20. 30.. 4.2. All others have 1 second measurement cycle. 20. 6.5 = close. cyc: 1 s Memory cyc: 10 min Displays the measurement cycle and the memory cycle which has been set. 60. 5. the sensor signal is output directly (air pressure at station elevation. 4. Elevations between 0 and 4000m can be set in consideration of the operation range from the air pressure sensor.4) EXTREME VALUE CYCLE: *Extreme cycle: 120 min Displays the extreme value cycle. Settings measurement cycle: (only Data logger: 9. 3. 4. P15 see 2. Setting range: 9.2. 2.4) TRANSMITTER CONSTANTS: CONCERNING SENSOR 6: RADIATION CONSTANT PYRANOMETER CM3/ CM6B *Pyr.xx. 20. 120. 6. 2.9999 mV/ 1000 Wm-2 CONCERNING SENSOR 5: STATION ELEVATION: * Station altitude: NNNN m Inputting the station elevation is only of significance if an air pressure sensor has been connected to special input 5 (S4. 10.0000 mV Displays the radiation constant set on the "pyranometer CM3" or „CM6B“ sensor. 6. Should you measure air pressure. When you enter station elevation 0 m. 12.. see 2. 12. 9 . The value to be set is stipulated in the sensor's test certificate. then enter the station elevation here in order to obtain air pressure reduced to sea level (so-called "QFF"). 180 and 240 minutes (see section 2.00x) 1.2. 10. 30.MEASUREMENT CYCLE / MEMORY CYCLE: *Meas. 15.6) SENSOR 1 WIND VELOCITY Windvelocity: NN.1740. .360° Resolution: 1° (valid for a Ultrasonic wind direction transmitter) ≤ 3° (valid for a wind direction transmitter with 8 bits) (standard) ≤ 12° (valid for a wind direction transmitter with 5 bits) (compact) SENSOR 3 TEMPERATURE 1 Temperature 1: NNN.3%.2%.1°C SENSOR 4 SPECIAL INPUT 3/ REL.?" appears if there has been a measurement error (for example...50 m/s resolution: 0.8 m/s Measuring range: 0. the sensor is not connected.)..1 m/s Measuring range: 0.N % Outputs the instantaneous measured relativ humidity (measurement once a second)..4 = open Input 3 0-1V: NNN.1 m/s Measuring range: 0.60 m/s resolution: 0.3.. S4.4 = close rel.Software Variation 0 or 1: (Compact-Wind transmitter) Software version 2 or 3: (Standard-Wind transmitter) Software version 4 or 5: (Sensor with Reed contact) Software version 6 or 7: (Ultrasonic-Wind transmitter) Software Variation 8 or 9: (First-Class Wind transmitter) Measuring range: 0.N % Outputs the measured input voltage in % (measurement once a second).30 020879/11/05 . humidity: NNN...+60°C Resolution: 0..1 % S4. 60.1 % 10 .1.52.100% (corresponds to 0-1 V) Resolution: 0.100% Resolution: 0.2 and S4. HUMIDITY S4.9 m/s resolution: 0.. "???. the ouput is limited to 102..? appears if the measuring range has been exceeded or not reached. the sensor is not connected.3 have no function when using an Ultrasonic wind transmitter.. "???.1 m/s Please Note: The switches S4.?" is output if there has been a measurement error (for example. Measuring range: 0...N °C Outputs the instantaneous measured temperature (measurement once a second).3. the measuring range has been exceeded etc. SENSOR 2 WIND DIRECTION Wind direction: NNN ° Outputs the measured wind direction (continuous measurement). For measurements above 102..60 m/s resolution: 0. ???. the measuring range has been exceeded) Measuring range: -40. Measuring range: 0.1 m/s Measuring range: 0.5.3.0 m/s resolution: 0.... Measuring range: 0. 9 mm Resolution: 0. that is independent from the DIP-switch. "???. the output is limited to 102.30 020879/11/05 . Measuring range: -40..N °C Outputs the instantaneous temperature values (measurement once a second). SENSOR 6 RADIATION Radiation : NNNN W/sm Outputs the measured radiation (measurement once a second). Version 0 an 1 (Transmitter PTB 100A) Measuring range: 800. Measuring range: 0..5 = open Input 5 0-5V: NNN.5 hPa *The measuring range is relative to a station elevation of 0 m. Measuring range: 0.N hPa Outputs the instantaneous measured air pressure (measurement once a second). ???.1 % Please note: In order to keep a telegram length.3 hPa Version 2 and 3 (Transmitter PTB 100B) Measuring range: 600.3%..1060 hPa* Resolution: ≤ 0.: NNN.1°C Please note: If an Ultrasonic wind sensor (version 5 or 6) is connected the virtual temperature is measured instead of the precipitation state of event. The measured value depends on the radiation constant of the transmitter (for the setting.+60°C Resolution: 0. (The sum of all precipitation since midnight.>1328 Wm-2 Resolution: ≤ 5 Wm-2 SENSOR 7 PRECIPITATION Precipitation: NNN. The measuring range changes for other station elevations. please see TRANSMITTER CONSTANTS)..99. continuous measurement). the measuring range has been exceeded)... S4. Measuring range: 0. j/n: N Outputs the status of the event (continuous measurement) 1 → input closed 0 → input open virt...1 mm SENSOR 8 PRECIPITATION (j/n) / VIRTUAL TEMPERATURE Precipit. (please also refer to TRANSMITTER CONSTANTS).N % Outputs the measured input voltage in % (measurement once a second).100 % (corresponds to 0-5 V) Resolution: 0.1060 hPa* Resolution: ≤ 0. For measurements above 102.?" indicates measurement errors (for example the sensor is not connected...N mm Outputs the amount of precipitation which has fallen during the current day.? appears if the measuring range has been exceeded or not reached.. we added a leading blank space.5 = close Air pressure: NNN..SENSOR 5 SPECIAL INPUT 5/ AIR PRESSURE S4. 11 . Temp.2%. .1 % SENSORS 10. Measuring range: 0.2 Outputs the measured input voltage (resp..2. (Measurement once a second).. For measurements above 102.1 % Please note: Outputs the measured input voltage (resp. Measuring range: -40.8 = open Input x 10V/20 mA: NNN.7).6 = open Input 4 0-5V: NNN. Measuring range: 0. for compatibility reasons the telegram output remain unchanged.1°C Please note: Temperature 4 is used as reference. SENSORS 13.?" appears when the measuring range has been exceeded.3). The temperature channel 4 is handled like a logged-off channel.7 = close S4.2%.N % Outputs the measured input voltage in % (measurement once a second)..3. Measuring range: -1000.0 mbar Resolution: 1 mbar X = 2. it is guaranteed that the temperature inputs of the Logger remain linear in case it is used with extreme temperature ranges.3%. to channel configuration chap.. DATA OUTPUT Data output ? Starts data output (see section 2...6 = close Tensiometer: NNNNN mbar Outputs the instantaneous soil saturation potential.. 4 Temperature X: NNN.100% (@0-10V / 0. 11.N % x = 1.2% the output is limited to 102. Measuring range: 0. (If necessary. current) in % (measurement once a second).20 mA) Resolution: 0. sensor 12 can be re-utilized with omission of the temperature compensation). However.(4) Outputs the instantaneous temperature values (measurement once a second).2 S4.. "???.?" indicates measurement errors (for example the sensor is not connected.2. and the value of the reference is output.20 mA) Resolution: ≤ 0.7 = open S4. 14 SPECIAL INPUT 1. 12 TEMPERATURE 2. the output is limited to 102.. "???..5). The temperature compensation is switched off by fadingin the channel (ref.100 % (match to 0…5V) Resolution: 0. 2. For measurements above 102.2 % You can switch back and forth between current measurement and voltage measurement with the S5 DIP switch (see 2.30 020879/11/05 .N % x = 1. 3. Thereby. current) in % (measurement once a second).8 = close Input x 4-20 mA: NNN.100% (@ 2-10 V / 4.N °C S4.SENSOR 9 SPECIAL INPUT 4/ TENSIOMETER S4..3%.+60°C Resolution: 0.. 2 S4.. 12 . the measuring range has been exceeded). . If the online time is reset and confirmed through the <ENTER>-key.2). time. Through the setting of small time windows (<2 0 min) the medium current consumption of the modem (operating current approx. 200 mA) per day can be kept at a low level.00X optionally 13 . in order to guarantee a re-query within this period in case the data query was incorrect. During the data transmission via a timer controlled mode the remaining switch-on period is kept on 5 min. extreme value cycle. To edit the displayed value. The value to be changed is indicated by the flashing cursor. „HH:MM“ gives the starting time of the current time window in the format „std:min“. 2. All letters and numbers as well as the underlining "_" and the space bar can be used for the name. date.2.7 on page 16. measurement cycle . 2.xx.2.(see also example rection 2.2. With serial data output. the current and the following timers are deactivated.3 The GSM-Timer serves for activating a time window for a GSM-modem which is externally connected to a datalogger of the type 9. These values are: Station name.2. then press the <ENTER> key to leave the editing mode or to select the next variable. Please note: To Change the channel configuration see chapter 2.. all 11 characters of the station name are output.2 DATE If an invalid date is entered the computer automatically corrects it.6. If the set value is satisfactory.3 GSM-TIMER TIMER X:HH:MM ONLINE: NN min X = 1. channel configuration. simply press <ENTER> and the <∇> key. baud rate.00x.1740. The value can be raised with the <∆> or lowered with the <∇> key. In the editing mode the 3 time windows for the GSM-modem can be set one after the other.2. Now release both keys.2. each of them should be given a different name. the GSM-modem is switched off in order to avoid a low-discharge of the accu! 1) 2) only Datalogger: 9. radiation constant and station elevation. When changing the station name the second line indicates the output language which can be selected through the arrow-key accordingly between “Deutsch “ or “English”.1740.1 STATION NAME The station name is used to identify the measuring site.30 020879/11/05 . For output onto a memory-card the first seven characters are given. memory cycle.2 CHANGING THE PARAMETERS All display values which appear with a „*“ to the upper left can be changed. If several data loggers are in use. The ONLINE-time is selectable in minute-intervals: maximum online-time minimum online-time deactivate timer Remark: : : : 60 min 5 min 0 min In case the accu voltage falls below 11 V. 2. 2) .XX. GSM-timer 1). and precipitation (formation of sums). cycle memory cycle 1 second 10 minutes A mean value is calculated from 600 measuring values. There are 23 different measurement intervals available: seconds: 1.7. 60 Please note: The measuring cycle of a datalogger with COM2 or ultrasonic wind transmitter is set permanently on 1 second. 30. 3. The memory cycle influences the storing period of the mean values (ref. 15. or accumulated. The measurement cycle can be changed during operation without the preceding data being lost. 6. 60.2. and extreme values is corrected automatically to an integer multiple.00x 14 . 12. 10. 20. 10. The memory cycle is selectable in 12 steps. 60 meas.30 020879/11/05 .5 EXTREME VALUE CYCLE The extreme value cycle gives the time point the extreme values are saved. 15. 10. the cycles of storing. 20. 4. 12. 3. 12.. the measuring values are averaged. The calculation of the mean value is carried out as arithmetic mean with „normal“ sensors. precipitation) are continuously measured independent of the measured value set. 3. 1) only Datalogger: 9. The memory cycle indicates time interval for storing the measuring values. 6. Please note: When changing the measurement cycle. 5. 30. 15. 2. 5. 30. 4. 2. 3. 2.4 MEASUREMENT CYCLE The measurement cycle indicates the time intervals at which the analog and serial sensor values are measured by the data logger. For this. 4.2. 5. 6. Exceptions are the wind direction (vectorial mean). 240 The extreme value cycle influences the extreme value memory period (see section 2. and stored. 30 minutes: 1. 6.7) 2. 10. The initial measurement interval set when the instrument is first switched on is 1 minute 1) . 5.2). 180.1740. Minutes Example: : 1.2. 15. 12. 2. The extreme value cycle is selectable in 15 steps: Minutes : 1. to section 2. 4. 20. 20. All digital counting inputs (for example wind speed. 120. x0.x00 4.6 open close special input 4 (sensor 9) 0-5 V universal-input tensiometer (Thies) S 4.007 4.7 open close open close S 5.8 open close open close S 5.2 open open open close S4. You can only read in the switch setting of S4 after you have switched the instrument on. This makes the setting valid for the data logger.33. humidity (Thies) S 4.4 open open close close special input 2 (sensor 14) 0-10 V universal-input 2-10 V universal-input 0-20 mA universal-input 4-40 mA universal-input DIP-switch S4 OFF (OPEN) 1 2 3 4 5 6 7 8 ON (CLOSE) DIP-switch S5 OFF (OPEN) 1 2 3 4 ON (CLOSE) 15 . you should adjust the switch during measurement operation (display off) and then switch the data logger on with the on-key. Readjusting the switch during measurement operation has no effect.x00 S 4.22. S 4.2.30 020879/11/05 .4 open close special input 3 (sensor 4) 0-1 universal-input rel.0.3519.5 open close special input 5 (sensor 5) 0-5 V universal-input air pressure transmitter S 4.1 S 5.000 4.3350.2 open open close close special input 1 (sensor 13) 0-10 V universal-input 2-10 V universal-input 0-20 mA universal-input 4-20 mA universal-input S 4.3 open open close close wind speed transmitter Standard Compact First Class Reed contact 4.3 S 5.e. i.3515.1 open close close open S 4.2.00.30.6 DIP-SWITCH SENSOR SETTINGS Below the front panel of the data logger there is an 8-pole (S4) and a 4-pole DIP switch (S5) to configure a number of sensor settings. xx0) (V. This means that any text editing program can be used to examine. The transmission of all mean values stored in the memory takes at least 15 minutes 1) at 9600 baud.xx.Output: Order No.2.24 .xx.1. The countdown appears on the display. make sure that the memory card1 is not in its holder2 . manipulate and print the data.memory card An external computer can be connected with an appropriate cable to the serial interface of the Datalogger to access the stored data.1740. 2. 2. such as table format programs. Accordingly you are able to conduct further data analyses with standard software. you can use a standard terminal program (for example "TeraTerm" or "Terminal" from Windows).7 CHANNEL CONFIGURATION In order to be able to change the channel configuration. All data are transferred in ASCII format (text).1 SERIAL DATA OUTPUT ) ) For the output of data over the serial interface COM 1. you can adjust the values as you usually do.1740. etc. data banks. ) ) ) If you leave the memory card 1 in its holder 2 .11 / RS422 9. edit.. you must first simultaneously press the <ENTER> key and the <∇> key and then do the following: The second line is deleted and a question mark appears. We recommend that you use our communications program "Mevis" to read out the data.xx. Moreover.3 DATA OUTPUT The Datalogger provides two possibilities to read out the data: . the data will be written on the memory card! 1 Serial data output can follow by pressing the key or via cable.1740.: 9.1 CONNECTING CABLE OF THE SERIAL INTERFACE The serial interface (COM1) is a "three-wire" connection.xx0 PC/TERMINAL Sub-D25 (25-pol) TxD RxD ground 2 3 7 LOGGER terminal strip LOGGER RS232 Sub-D9 2 3 5 9 11 13 RxD TxD ground Sub-D9 RxD 2 TxD 3 ground 5 9 11 13 RxD TxD ground 2 3 5 1) + 2 ) optional 16 .30 020879/11/05 .xx1) 1) .serial (V. RS232 / V.2. Data transmission to a memory card is considerably faster (less than 2 minutes) because the data are transferred in parallel. The transmission line (TxD) and the receiving line (RxD) must be cross-connected in the cable.3. After the countdown is concluded.3. Now press the <∇> and the <∆> keys simultaneously for 10 seconds.24 / RS232 9. 2. 2 RxD.Mo.Mo.J> "ds" <T. For line lengths exceeding 100 m.1740. TxD+/TxD-).30 020879/11/05 . output one day's stored data (mean values) output one day's stored data (extreme values) output stored data (mean values) from a certain timepoint on "GS" "ts" <T.Output: Order-No.Mo. 2.1.3 RxD+ 4 ground LOGGER Terminal strip 15 protective ground PE (respectively connect to PG screw coupling) 8 RxD+ 10 RxD14 TxD12 TxD+ 13 ground Please Note: Shielded cable should be used.RS422 .xx1 Interfaceconverter IC-485SI RS422 shield • TxD+ 1 TxD. twisted wire in pairs should be used (RxD+/RXD-. The commands consists of 4 to 9 bytes: STX ? ? ? ? ? ? ? ETX 02H command Ctrl-B Ctrl-C (respectively Strg-C) 03H LIST OF COMMANDS: "HH" "SS" Help: shows the list of input commands mean value memory: output of saved mean values entire mean value memory: only useful if the logger has re-initialized itself in order to rescue data which has not yet been overwritten.xx.J> "te" <T.H.Mi> 17 .: 9.3. The connection of the shield (pin 15) to protect the instrument from surges (for example lightning) is also important.J. The manufacturer is not responsible for damages resulting from surges.2 COMMAND FORMAT (COM1) This section is only important for those who want to use their own communication program. .: STX "ds" 29 31 32 40 28 ETX 1 3 04 12 0 Mean value data from 01. 59) Mo J H Mi : : : : Month in binary + 28 Year in binary + 28 Hour in binary + 28 Minute in binary + 28 (29 .STATUS> channel configuration CH: channel (1.. extreme value cycle channel configuration radiation constant station elevation 1) GSM – timer "MM" and "mm" instantaneous measured values: Output all the values measured by the sensors.99> extreme value memory: output of extreme values Last record from the mean value memory (see 'MM') mean value records stored till now extreme value records stored till now.......00X 18 .. Output with sensor identification Output as with the mean value data record however with the addition of the second.127) (without (28 ..99> “le“ <1. 52) Century) (28 ."de" <T. 77) Ex. "KK" <CH....J.03.00 on are called up..1740.2004.H. 12.NNNN "SH" <0. memory cycle.XX.4000> "LL" enter station height logger status: Output logger date and time.31> 1) only Datalogger: 9. logger date "MM" "mm" "DD" "DT"<1. The data are only valid three seconds after the instrument has been switched on..14) STATUS(0/1) for activating and de-activating each individual channel "SK" <KONSTANTE> enter constant of radiation NN.Mi> output stored data (extreme values) from a certain timepoint on T : Day in binary + 28 (29 .30 020879/11/05 . storage battery voltage. 40) (28..Mo. measurement cycle. Characters have to enter without spaces! "EE" “LS“ “ls“ <1. logger date Enter day: setting the day of the logger Response: entered day. status of the A/D converter.. "DM" <1..99> "ZZ" "ZH"<0. "ts". logger date Enter year: setting the year of the logger Response: entered year.23> "ZM"<0. "de". "EE" software handshake (output continues) software handshake (stops output. logger time Enter minute: setting the minute of the logger Response: entered minute. logger time Output of station name. "DJ" <0.. logger date logger time Enter hour: setting the hour of the logger Response: entered hour. "GS". "te". instrument model and software version Response to an unknown command respectively to an incorrect parameter..12> Enter month: setting the month of the logger Response: entered month.30 020879/11/05 . "ds".. 30 second maximum. otherwise the data logger switches off automatically!) XON (011H) XOFF (013H) 19 .59> "XX" CR LF"?" CR LF ADDITIONAL CHARACTERS OF IMPORTANCE: STX (02H) ETX (03H) EOT (04H) start of a command end of a command Abort of memory output for the commands: "SS". .94 8:44 CR LF line feed carriage return Time Date 2. END LINE: "END OF DATA" "THIES CLIMA" "TDL 14 V3.1) 8. Sensor 11.3 11:01 3.Sensor 1. Lines are concluded with "CR LF"..1. The separator character is at least one space (ASCII 32).3 SERIAL DATA FORMAT The data are delivered in tabular form with constant telegram length so that they can be processed by a tabular calculation program. The data are output in tabular form.09.30 020879/11/05 .03.0 11. END LINE: "END OF DATA" "THIES CLIMA" "TDL 14 V3. MEAN VALUES: DATE LINE: Sensor values: Sequence as in display (see 2.1 8.12" Software-version Instrument model Station name EXTREME VALUES: DATA LINE: Sensor values: sequence as in display (see 2..7333 30. „EXCEL“.Sensor Time in decimals Remark: The date and time refer to the end of the measurement..3.2.1) 1.02 11:05 CR LF line feed carriage return time date time of the maximum value maximum value time of the minimum value minimum value time in decimals Remark: Date and time refer to the end of measurement. Erroneous values are indicated by one or more "?" respectively "!". for example..0633 0. 8.12" Software-version Instrument model Station name 20 .1 11:03 . is possible.1.000 (DCE) RXDRXD+ ground Logger 3-pole terminal strip 2 TXD1 TXD+ 3 ground Please pay attention to the remarks in 2. The memory card should only be inserted into the holder of the data logger for read out. After returning the battery compartment to its original position. Thus there must be a functioning battery in the memory card. During transport and storage.2. To open the battery compartment. The battery compartment is situated across from the contacts.01X optional 21 . set the battery compartment lock to "UNLOCK" (use a tweezers or similar object).1702. as well.30 020879/11/05 .3. SUGGESTIONS ABOUT USING THE MEMORY-CARD: Battery-buffered static memories are used for data storage.or the RS422-output.3. make sure that the memory card is always in the anti-static cover! 1) 2) only Datalogger: 9.XX. RS232 – transmission: PC/terminal SUB-D9 (9-pole) RXD ground 2 5 Logger SUB_D9 (9-pole) 3 TXD 5 ground RS422 – transmission: Interface converter RS422/RS232 9.20. set the battery lock to "LOCK".3 DATA OUTPUT OVER MEMORY-CARD Output requires a memory card ("STARCARD" from ITT CANNON or compatible) with a memory capacity of at least 256 KBytes.1740. A simultaneous connection to the RS232. Now pull out the battery compartment.3.1 concerning the cable with the RS422-transmission ! 2) 2.2 CONNECTING CABLE OF THE SERIAL INTERFACE (COM2) 1) The serial interface COM2 serves for the simple-transmission (transmission operation) of data. thus when the memory card is not used for a longer period of time. Pressing the <ENTER> key interrupts transmission. 2. No power is drawn from the buffer battery when the storage battery is connected (or when there is an external power supply). Please Note: During installation it is important to make sure that all terminals are switched voltage-free and that individuals and/or instruments are not endangered! 22 . The memory card can be read out by a PC with a reading program and the corresponding reader (THIES accessories).30 020879/11/05 . 3% per month). Remove the memory card from the holder.5 V! The new storage battery should be "freshly" charged once more as. 3.) 2. The data format is set up in correspondence with the data lines in section 2. at the latest. Without the storage battery. Selecting the memory output: "M" stands for mean values and extreme values "E" stands for extreme values Mean values press <∇> Extreme values press <∆> Mean values and extreme values can be stored in succession on the memory card. The buffer battery can only be replaced by the manufacturer. Switch the data logger on with the <∇> key.1. Press <ENTER>: data output starts. Either "E" or "M" appears in the second line of the display. the operational life of the buffer battery is 10 years.3. depending on what has been selected. the data logger starts. press the <∇> ON key and hold it down. only the self-discharge factor is of importance for the operational life. In addition "MCard" and the number of data records output also appear. The operational life of the storage battery is considerably reduced when operated below 10. Please note: 5. However. 9. Insert the memory card into the data logger holder Keep pressing the <∇> key until the words "data output" appear on the display. the storage battery should not be discharged below 11. When no power is drawn. 7.0 V as there is no appreciable capacity available anymore. Before the storage battery is disconnected. Continue to press the key (3 seconds) until the words "M-data" appear in the second line of the display. it is advisable to remove the battery. no measurements are carried out.The nominal operational life of the battery of the 256 KB memory card (type BS256F1-C) is 4 years. Press <ENTER> to be able to operate the data logger "normally" again. 4. 8. 6. The stored data are retained during the exchange process.4 CHANGING THE STORAGE BATTERY The storage battery. 1.e. The end of the transmission is indicated in the display by ""end". the data should be secured. has to be replaced when the indicated storage battery voltage drops below 9. Before the storage battery is connected. during this time. (The only difference: the data from the memory card always have only one space character as the separator. owing to selfdischarge (approx.0V.3. After the battery has been connected and the key released once again. it may not have its maximum capacity. i. For winter operation (with limited solar radiation) we recommend that you set an elevation angle adapted to the site (for Germany approx.3 DATA LOGGER WITH SOLAR PANEL (9. the charging voltage changes with the temperature.30 020879/11/05 .xxx/ 9.2. The power supply must supply a current of at least 500 mA. The use of a different panel could destroy the electronics! General information of the solar panel: Solar panels in use in the Northern Hemisphere should be aligned towards the South.5 EXTERNAL POWER SUPPLY 2. Be careful that the arrangement of sensors or traverses above the panel does not cast shadows. Please Note: The integrated regulator is designed for a solar panel with nominal data 12V/20W. The voltage range for direct voltage is 17 to 33 V DC and for alternating current voltage 14 to 24 V AC. Clean the surface of the solar panel as required (to remove snow.5. We recommend a medium anti-surge 1 A-fuse (1 A mtr) to protect the mains voltage.x2.xxx/ 9. The storage battery must always be connected. This controls the external power supply (LED lights up). 50°).x4. 2.xxx/ 9. Please Note: The connection of protective earth PE to the transformer is absolutely imperative for safety reasons! 2.x0.2 DATA LOGGER WITH TRANSFORMER (9. Above pin 3 of the terminal there is a red lightemitting diode (LED). That is why the storage battery should always be in the data logger case.1740.xxx) The solar panel is connected over pin 3 and pin 4 on the terminal strip.1 DATA LOGGER WITHOUT TRANSFORMER (9.x4.1740.1740.5. leaves etc.1740. first connect the storage battery.x1.5. Switch-off takes place in reverse order.1740. The terminal is situated below the cover plate for the sensor connections (pin 1 and 2). Then the external power supply can be switched on.xxx) The input for external power supply can be used to charge the storage battery and to supply the data logger with current. In the integrated charge regulator in the data logger. 23 .).1740. To switch the data logger on.xxx) The AC mains voltage on the transformer generates two low-voltages to supply power to the sensor heaters (26 V AC) and to the data logger (16 V AC).x3. 6 s for measurement of the sensors. operating current approx. these calculations are only approximations due to the variable performance and ageing of the electronic components and the storage battery. The exact time intervals at which the storage battery needs to be recharged can be determined only by practical experience. the current usage depends on the selected time intervals of data acquisition. However. wind velocity sensors). 50 mA (RS232 / V. Furthermore. data transfer approx.30 020879/11/05 . we basically recommend that you only set the measurement cycle to greater than or equal to one minute.00X 24 . in case of pure accu-solar operation the GSM-online periods should be brief In the following we show how to calculate the current consumption for both modes of operation. 55 mA (RS422 connect with Interface Converter) The measurement current consists of a permanent component Iquery and a current Isensor which is dependent on the connected sensors. 2. For these cases the additional current consumption must be added to the calculated values. Note that these calculations assume that the sensors are only switched on up to the time of data acquisition.2. Therefore. increases the current consumption considerably (min.g. (RS 232-Interface) 30 mA 18 mA 18 mA + 30 mA Imean = 50 mA + 5s * 0.24) Icont = ca. It is necessary to differentiate between second and minute intervals 1) .6s EXAMPLE: Measurement cycle Isensor Iquery = = = 5 s.1 QUERY SECONDS Power consumption is composed of a continuously flowing current Icont and a current which only flows together for approx 0. A GSM-mode that is switched-on and accu-operated. Due to the high current consumption of the ultrasonic a power-supply-independent operation with ultrasonic as wind sensor is not possible without additional external accu. In addition one must differentiate between the active phases of operation.6 CURRENT CONSUMPTION As already mentioned in section 2.3.6. 56 mA 1) only Datalogger: 9.XX. = ca. 50 mA. and solar panels of appropriate dimensions. 200 mA).2. some sensors must be in operation continuously (e.6s = approx. The capacity depends greatly on the temperature: For operation below 0° assume only half the capacity. For the data logger in mains-independent operation (only storage battery and solar panel).1740. because two different processor modes are employed. The total current Imean can be calculated as follows: Iquery Imean = Icont + Measurement cycle [s] + Isensor * 0. = approx.2 QUERY MINUTES 1) As with QUERY SECONDS. Iquery = 18 mA The total current Imean can be calculated as follows: Iquery + Isensor Measurement cycle [min] * 60s Imean = Icont + * 1.1740.xx.24) (RS422) The measurement current. 1 mA 4 mA (RS232 / V. 5 days) Remark: The data logger 9. The current Icont is lower than comparable current in query seconds by a factor of 10. Approx. Icont = approx.From mean power consumption Imean.6. Thus. power consumption is composed of a continuously flowing current Icont and a current which only flows together for about 1. consists of a permanent component Iquery and a current dependent on the connected sensors Isensor.6s * min = 2.6s * min EXAMPLE: Measurement cycle = 1 min RS232-Interface Isensor = 30 mA 18 mA + 30 mA Imean = 1 mA + * 1.6 s for sensor measurement. 30 mA for sensors result in a theoretical life period of approx. 55 mA.30 020879/11/05 . conclusions can be drawn about the operating life of the storage battery: Capacity Operating life = Current EXAMPLE: Capacity 7 Ah Current Imean = 56 mA 7 Ah Operating life = 56 mA = 125 h (ca.3 mA 1 min * 60s 1) only Datalogger: 9.00X 25 . 82 h. query minutes is preferable in storage battery operation.XX.1740. in turn.x1x (with COM2) operates only in a second’s cycle and needs approx. 2. For the operating life of the storage battery one calculates: Capacity Operating life = Current EXAMPLE: Capacity 7 Ah Current Imean = 2.8 69.4 - Extreme Values Time Period (days) Standard 16 Values *) 0.3 mA 7 Ah Operating life = 2.08 40.92 1. 44 days) = 6.43 18.15 1.68 1. The time period of the extreme value memory depends on the extreme value cycle set.XXX 26 . Memory Cycle and Extreme value cycle 1 2 3 4 5 6 10 12 15 20 30 60 120 180 240 Mean Value Time Period (days) Standard 16 values ∗) 4.6 81.6 ∗ ) only Datalogger: 9.75 72.68 61.08 5.8 122.28 12.92 16.5 mA Itotal 2.38 0.84 3.3 mA + 24 h 7 Ah = 1076 h (approx.2 23.1740.84 40.2 92.76 0.2X.31 54. the total current increases and the operating life reduces as follows: EXAMPLE: Online time: tonline = ½ h per day = 3043 h (126 days) IGSM * tonline Itotal = Imean + 24 h Capacity Operating life = = 200 mA * ½ h = 2.4 46.8 11. The data logger has two ring memories.4 4.76 5.12 61.25 218.35 14.87 36.68 6.01 7.2 24.04 20.2 245.36 1.52 10.56 20.4 49.53 1.30 020879/11/05 .17 7.34 0.52 21.16 81.7 2.5 mA The storage period is the period of time until the old data are overwritten.02 1.64 8.04 3.6 4.05 43.3 mA In case a GSM-modem is connected to the accu.08 3.26 10. The time period of the mean value memory depends on the memory cycle set.7 MEMORY TIME PERIOD 6.3 2.62 109. TECHNICAL SPECIFICATIONS : : : : : : : : : : stainless steel.cycle w/o GSM and w/o sensors) min..1740. Check the fuse again.2.6V 0.1740. Check the fuse with a measurement instrument to test the flow of current (a visual check usually does not suffice!). range 10 3x temperature Pt 100. open the slide lock (press down and rotate towards the left) and remove the fuse.x4.xx.1740. accuracy : Channels : (1 min meas.x10.5 days with COM2 nominal 4 months -30.x2. 55 mA (9. If the data logger still does not switch on. COM1: RS232) approx. return it to us for a check.30 020879/11/05 ..x3..2% of the meas..xxx/ 9..1740.xx.1740. value A/D-converter : Meas. 50 mA (9. rustproof IP 65 12V 7Ah (lead gel. To check whether this is the case.24V AC / 17. this could mean that the fuse (situated above pin 6) has blown. values Channels : 1) Datalogger: 9.cycle and 20°C ambient Case Type of protection Power supply Internal storage battery Buffer-battery External power supply External mains External solar panel Current consumption (w/o sensors) Operating life Accumulator temperature) : Operating temperature : Storage temperature : Analogue meas..1740. If the fuse is defective: exchange it for one of a similar type (100 mAT).. (condition: storage battery not discharged).+50°C -40. 10 bit (1024 steps) ± 0. COM1: RS422) nominal 3..xxx) 12 V / 20 W (with optional solar-regulator) (9. then connect the cable one by one to the sensors until the fuse blows again to pinpoint the defective sensor.xxx/ 9. 3. If the data logger still does not go on: Disconnect all sensor and serial connecting lines.50X 27 . If the data logger now switches on. Please Note: The blowing of a fuse as a result of a direct or indirect bolt of lightning is a normal protective function. Return the defective sensor to the manufacturer for testing.+70°C (1 s meas.xxx) approx. fuse for power supply failure) 3.33 V DC 230 V AC (with optional transformer) (9.XX. (and optionally 1x temperature.75Ah (lithium) 14.xxx) or 115 VAC (9.x1.x4.8 CHANGING THE FUSE If nothing appears on the display after you have pressed the on-key.x11.1740. if a temperature compensation is not necessary!) 1x radiation transmitter CM3/CM6B 1x 0-1V 2x 0-5V 2x 0-10V/ 0-20mA/ 2-10V/ 4-20mA 4 synchronous-serial (wind direction) 16 bit counter (wind speed) 8 bit counter (precipitation) 8 bit counter + status (precipitation) or virtual temperature 1) Digital meas.1740. .10 V 0. RS232 (V. no parity. 2. 6. 2. 6. Option: Memory-card interface for 256 KB-memory-cards („starcard“).11). 120. 30.1 V R = 20 kΩ R = 50 kΩ R = 100 kΩ R = 250 Ω special input 4/ 5 0. 6. 4.20 mA 1) 2 Datalogger: 9.30 020879/11/05 . 20. 10..xx.Measurement cycle Memory cycle Mean values Extreme values Time base : 1 s fix adjusted or 1.. 20. 1 stop bit (8N1) or 7 data bits. 60 min 1) : : : 1. 60 min as mean values. 2) 2) : 256 KB data contents are secured by the buffer battery. 10.1740.9600 baud.XX. 10. 3.output Parameter: 300 . 57600bd 7 data bits. 1 second 2 output telegrams RS232 and RS422.4 days extreme values 23.24). 5.. transmission distance 1000 m (9.XXX 3 ) Datalogger: 9. 2 lines à 16 characters : special input 3 0. 30 s.. 4.00X ) Datalogger: 9. 15. (accuracy ± 10ppm = ± 0.xx0) : RS422 (V.01X 28 .1740.XX. no parity.. 3. mean value cycle 5 min. even parity. 1.5 V special input 1/ 2 0.0 days Data output Serial Interface COM1 : Remote control query via the serial interface (COM1).1740. 15.. 30.1740. 180 and 240 minutes are additionally adjustable real time clock with automatic leap year adjustment. 5..2X.. 1 stop bit (7E1) Operation LCD-Display Input resistance Sensor inputs : 3 keys on the instrument. 12.. 19200bd u. 15. 9600 Baud 8 data bits. extreme value cycle 60 min: mean values 20. 12. 12.xx1) Parameters: 300. 2. 4. remote control operation via serial interface (COM1).. 20. transmission distance 15 m (9.9s/ 24h at 25°C) Memory capacity Semiconductor memory Number of data records Mean values Extreme values Memory period : : : 5886 / 5246 553 / 490 for ex. 5. 1 stop bit (8N1) basic setting: 9600bd 7E1.xx. 1 stop bit (7E1) or 8 data bits. output cycles min. XON/XOFF-Handshake Serial Interface COM2 3) : interface for online output..1740. even parity. 3. powered by the buffer battery. to Instruments see enclosed circuit diagrams 29 .4.1 Connecting Diagrams acc. APPENDIX 4.30 020879/11/05 . com .thiesclima.com [email protected] THIES GmbH & Co.30 020879/11/05 . KG Hauptstraße 76 37083 Göttingen Germany P.Alterations reserved - 30 . Box 3536 + 3541 37025 Göttingen Phone ++551 79001-0 Fax ++551 79001-65 www.
Copyright © 2024 DOKUMEN.SITE Inc.