43500-054-30_en.pdf
Comments
Description
Model IIIPackage Substations Class 6010 Instruction Bulletin Retain for future use. HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. ENGLISH DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury. CAUTION CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage. NOTE: Provides additional information to clarify or simplify a procedure. PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. WARRANTY TO CUSTOMERS PURCHASING THROUGH AUTHORIZED SCHNEIDER ELECTRIC DISTRIBUTORS AND CUSTOMERS PURCHASING DIRECTLY FROM SCHNEIDER ELECTRIC. Schneider Electric warrants equipment manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from date of invoice from Schneider Electric or its authorized sales channels. If within the applicable warranty period purchaser discovers such item was not as warranted and promptly notifies Schneider Electric in writing, Schneider Electric shall repair or replace the items or refund the purchase price, at Schneider Electric’s option. This warranty shall not apply (a) to equipment not manufactured by Schneider Electric, (b) to equipment which shall been repaired or altered by others than Schneider Electric, (c) to equipment which shall have been subjected to negligence, accident, or damage by circumstances beyond Schneider Electric’s control, or to improper operation, maintenance or storage, or to other than normal use or service. With respect to equipment sold but not manufactured by Schneider Electric, the warranty obligations of Schneider Electric shall in all respects conform and be limited to the warranty actually extended to Schneider Electric by its supplier. The foregoing warranties do not cover reimbursement for labor, transportation, removal, installation, or other expenses which may be incurred in connection with repair or replacement. Except as may be expressly provided in an authorized writing by Schneider Electric, Schneider Electric shall not be subject to any other obligations or liabilities whatsoever with respect to equipment manufactured by Schneider Electric or services rendered by Schneider Electric. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES EXCEPT WARRANTIES OF TITLE, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. WARRANTY 43500-054-30R1 02/2004 Model III Package Substations Table of Contents TABLE OF CONTENTS Section 1—Introduction ............................................................................ 5 Section 2—Safety Precautions ................................................................. 6 Section 3—Receiving, Handling, and Storage ........................................ 7 Initial Inspection ..................................................................................... 7 Handling ................................................................................................ 8 Unloading and Lifting....................................................................... 8 Towing and Moving ......................................................................... 9 Storing ................................................................................................... 9 Section 4—Installation ............................................................................ 10 Substation Location ............................................................................. 10 Restricting Access to the Substation ................................................... 10 Electrical Connections ......................................................................... 10 Torque Guidelines for Transformer Electrical Connections ........... 11 Torque Guidelines for Circuit Breaker Electrical Connections....... 11 High Voltage Electrical Connections ................................................... 12 Conduit Area ....................................................................................... 12 Cable Pulling ....................................................................................... 12 Cable Terminations ............................................................................. 12 Section 5—Pre-energizing Procedure Checklist .................................. 13 Section 6—Interlocks .............................................................................. 16 Section 7—HVL and HVL/cc Switch Operating Sequences ................. 16 Section 8—Startup Testing to Energize................................................. 17 Pre-energizing Testing ........................................................................ 17 Drying the Core and Coil Assembly .................................................... 17 Drying Transformer Coils .................................................................... 17 Heaters and Lamps for Drying ............................................................ 18 Insulation Resistance Testing ............................................................. 18 Turns Ratio Test .................................................................................. 18 Effects of Humidity .............................................................................. 18 Energizing the Substation ................................................................... 19 Changing Tap Positions to Adjust Voltage .......................................... 20 Sound Level ........................................................................................ 20 Reduction of Structure Borne Noise .................................................... 21 Section 9—Maintenance .......................................................................... 21 After a Major Fault ............................................................................... 22 Inspection Procedure for HVL and HVL/cc Switches .......................... 22 Transformer Inspection Procedure ...................................................... 22 Cleaning .............................................................................................. 23 Molded Case Circuit Breakers Inspection Procedure .......................... 23 Ground Fault Protection Systems ....................................................... 25 Section 10—Adverse Circumstances .................................................... 25 Clean-up Following a Short Circuit ...................................................... 26 Water-Soaked Substations .................................................................. 26 Water-Sprayed or Splashed Substations (Clean Water Only) ............ 26 Inspection and Clean-up of Clean Water Sprayed or Splashed Substations .......................................................................................... 26 © 2001–2004 Schneider Electric All Rights Reserved 3 ENGLISH ...................... Distribution Reference Catalogs ....................................................................................... 27 Fans (Forced Air) ............................................................. 31 ENGLISH LIST OF FIGURES Figure 1: Figure 2: Figure 3: Figure 4: Figure 5: Figure 6: Typical Unit Substation ................................................................................................................................................ Instruction and Maintenance Bulletins ....................... 8 Using a Spreader Bar .............................................................................................................. Insulation Resistance Values..... QED-3 Circuit Breaker Connector Bolts ......................................................... 28 Other Optional Equipment ... 28 Powerlogic® Circuit Monitor ........... 16 LIST OF TABLES Table 1: Table 2: Table 3: Table 4: Table 5: Table 6: Table 7: Table 8: Table 9: Table 10: Table 11: Table 12: Transformer Torque Values............................................................. Multiple Conductor Neutral and/or Ground Bar ...... 5 Typical Nameplate ................................................................................................................................ Incoming... 28 Section 14—Installation and Maintenance Log ...................... 7 Typical Base ............................ Installation Instructions ..................... 14 Key Interlock ......................... and Neutral Lug ............................................................................................................................................................................................................................................................ Branch............. Other Reference Literature .......................................................... Ground Fault Field Test Instructions.................................................... 11 11 11 11 18 24 28 28 29 29 29 30 4 © 2001–2004 Schneider Electric All Rights Reserved ... 28 Section 13—Reference Publications ...................................... 27 Temperature Monitoring Systems ..Model III Package Substations List of Tables 43500-054-30R1 02/2004 Section 11—Optional Equipment . 28 Section 12—Replacement Parts . Factory-Set Temperature Alarm and Control Settings....................................... 9 Instantaneous Trip Setting ...................... Blank Fillers and Extensions.................... Installation of this electrical equipment may require special licenses or training. such as installation. and local codes for specific requirements. contact your Schneider Electric field sales representative. The transformer section is an open-ventilated. This instruction bulletin is not an application guide for the package substation or a substitute for adequate training in safe working procedures for this and related electrical equipment. loading.12. and the low voltage distribution section. operating. and maintaining package substations. . These features are detailed in the substation outline and nameplate drawings. The successful operation of any substation depends on various factors. or an air terminal chamber. or Square D Services at 1-800-634-2003.01 Usual Service Conditions. The substation should be installed in conditions as specified in ANSI/IEEE Section C57. Each substation has its own specification and unique construction features.43500-054-30R1 02/2004 Model III Package Substations Section 1—Introduction SECTION 1—INTRODUCTION The package substation is made up of three sections: the incoming line section. industry. and the low voltage distribution section is I-LINE® molded case circuit breakers or separately mounted molded case main circuit breaker. dry-type transformer. and maintenance. Consult applicable national. The incoming line section is a type HVL or HVL/cc switch. service conditions. NOTE: If additional information is needed that is not covered by this instruction bulletin. unless the transformer is designed specifically for operation in conditions other than the usual service conditions. the transformer section. Figure 1: Typical Unit Substation © 2001–2004 Schneider Electric All Rights Reserved 5 ENGLISH This instruction bulletin details information about installing. Model III Package Substations Section 2—Safety Precautions 43500-054-30R1 02/2004 SECTION 2—SAFETY PRECAUTIONS ENGLISH 6 DANGER HAZARD OF ELECTRIC SHOCK. and tagged. • Some foreign objects that can cause short circuits are tools. Neglecting fundamental installation and maintenance requirements will lead to personal injury. • Before making any electrical connection. grounded. which can result in severe damage. as well as damage to electrical equipment or other property. Use only electrically insulated tools. Use care while removing or installing panels so that they do not extend into bus. EXPLOSION. • Read and understand this entire instruction bulletin before installing. Short circuits can release large amounts of energy due to a rapid expansion of super-heated. • Before performing visual inspections. Products of this instantaneous expansion can quickly engulf and burn personnel before preventive action can be taken. and other conduction or semi-conducting materials. or death. Always assume that terminal is energized unless it is checked with a properly rated meter to ensure the terminal is de-energized and grounded. This short circuit source can cause additional injuries by propelling personnel or objects several feet from the equipment. operation. operating. See NFPA 70E. • If circuit breaker settings are adjusted. These workers must understand the hazards involved in working with or near high voltage equipment. Such work should be performed only after reading this complete set of instructions. • Before energizing the substation. © 2001–2004 Schneider Electric All Rights Reserved . wire. and maintenance. Workers must also be careful to keep clothing and body parts out of the equipment. clothing. • Introducing foreign objects into this equipment can cause a short circuit. Failure to follow these instructions will result in death or serious injury. installation. all unused I-LINE circuit breaker mounting spaces must be filled with blank fillers and/or extensions. personal injury. but it is not possible to eliminate every hazard with these features. or maintaining a package substation. carefully inspect the bus work area for tools and objects left inside the equipment. for wearing protective safety equipment. Follow all applicable local and national codes. or maintenance on this equipment. ensure all static charge has been discharged by grounding the coils with an appropriate grounding device. and for taking adequate safety precautions. do not set the long time trip rating at a higher ampacity than the rating of the bus bar or load cables it supplies. • Do not make any adjustment to the equipment or operate the system with safety features removed. Assume that all circuits are live until they have ben completely de-energized. Pay particular attention to the design of the power system. OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. tested. including the possibility of backfeed. the person using this device is responsible for recognizing the potential hazards. instruments not designed for high voltage circuits. test leads. • Before replacing covers or closing doors. • Only qualified electrical workers with training and expertise on high voltage circuits should perform work described in this set of instructions. • Before servicing the transformer. tests. • HVL or HVL/cc switches have features designed to promote proper operation. and protective gear when working around electrical equipment. Consider all sources of power. Therefore. ionized gases. disconnect all sources of electric power. Contact your local Schneider Electric representative for additional instructions if the HVL or HVL/cc switch does not function as described in this manual. • The successful operation of substations depends upon proper handling. take every precaution to see that all connections are de-energized and grounded. off load the substation. the transformer core and coils. Remove the protective covering. Handling. and Storage Initial Inspection Before unloading the substation. carefully inspect the leads. or current transformers. file a claim with the carrier at once. 2. After completing all of the above steps and if no problems are found. 3. Figure 2: Typical Nameplate Schneider Electric POWER DRY II © 2001–2004 Schneider Electric All Rights Reserved 7 ENGLISH SECTION 3—RECEIVING. such as fans. AND STORAGE . bolted mechanical and electrical joints. HANDLING. the substation is split for shipment. perform the following inspection: 1. and notify Schneider Electric. heater strips. 4. An internal inspection of the enclosure is not usually required unless possible external damage has been observed. controls. If the substation is provided with an HVL or HVL/cc switch. control power transformers. Review the shipping papers to ensure that the order and shipment is complete. List any noticeable damage on the receiving papers.43500-054-30R1 02/2004 Model III Package Substations Section 3—Receiving. Refer to “Handling” on page 8. and accessory equipment. Inspect the substation for any obvious external damage that may have occurred during shipment. If an internal inspection is required. and Storage 43500-054-30R1 02/2004 Handling The transformer and low voltage section are built on a rigid base. The base allows for lifting the entire substation at one time. The substation is top heavy and may become unbalanced. DO NOT attempt to lift the complete substation with these eyes. The approximate weight of the substation is shown on the transformer nameplate. Handling. See Figure 3. © 2001–2004 Schneider Electric All Rights Reserved . Failure to follow these instructions will result in death or serious injury. • Keep all unnecessary personnel away while handling and moving the transformer. DO NOT UNLOAD using a forklift. A crane is required to unload the substation.Model III Package Substations Section 3—Receiving. ENGLISH Unloading and Lifting 8 Figure 3: Typical Base Follow these safety measures when handling the substation: DANGER TOP HEAVY LOAD • Use a crane to unload the transformer. The HVL or HVL/cc switch is provided with four lifting eyes on the top of the enclosure for lifting of the switch only. which supports the transformer and LV section. Store Indoors Only. Protect the substation and connection points from the environment. and a spreader bar.43500-054-30R1 02/2004 Model III Package Substations Section 3—Receiving. Storing © 2001–2004 Schneider Electric All Rights Reserved 9 ENGLISH 1. immediately install space heaters. Always make an internal inspection before the substation is placed in service. Handling. . upright position. If the substation must be stored. and Storage Follow these instructions to lift the transformer and LV section. take precautions to keep the unit from contacting an earthen surface. it is preferable to locate it in its permanent location on a concrete pad. Figure 4: Using a Spreader Bar Spreader bar Protect paint from damage by slings Substation Enclosure Sling Sling Clevis pins (not provided) 2. a crane is preferred to move the transformer and LV section into position. The HVL or HVL/cc switch may be moved with a forklift. Always handle the substation in the normal. For storage of other equipment. If a level concrete surface is not available. See “Drying the Core and Coil Assembly” on page 17 for more information. When a crane cannot be used. or other small electric heaters. Do not tilt the substation. slings. make periodic inspections of the substation exterior and interior for corrosion or other possible damage. Figure 4 illustrates the use of these items. To reduce condensation and avoid moisture absorption in the transformer section while it is being stored. never lift from the ends. refer to the applicable instruction bulletin(s) listed in “Section 13—Reference Publications” on page 28 If the substation is stored for an extended time. Towing and Moving After the substation has been off-loaded. which are not supplied. If you have any concerns. Ensure the spreader bar is wider than the enclosure and protect the paint from the slings. contact Schneider Electric. 3. Attach appropriately-sized clevis pins. the transformer and LV section can be skidded or moved on rollers. incandescent lamps. take extra care not to damage the transformer. Lift the transformer and LV section from the base by the side holes provided. When doing so. EXPLOSION. Seismic regulations may require that the substation be anchored to the pad. Refer to the tables on page 11 for torque information. 2. preferably of reinforced concrete. Substation Location Restricting Access to the Substation Install the substation in an area that is secure and that allows only authorized personnel access to the substation. Refer to the nameplate and wiring diagram to make the electrical connections. OR ARC FLASH Do not touch the windings of an energized transformer. are clear. EXPLOSION. from installation to comprehensive testing and verification of the new equipment. Contact Square D Services at 1-800-634-2003. Connection points are clearly labeled on the transformer. which may be necessary because of the specific supply voltage or transformer load characteristics. therefore restrict access to it. Schneider Electric recommends that you do not place the substation directly on an earthen surface. 24-hours a day. Follow all local and national codes when locating the substation. Make sure the ventilated openings. on the top and bottom of the enclosure. see “Changing Tap Positions to Adjust Voltage” on page 20. They can provide assistance in a variety of areas. Locate the substation on a level foundation strong enough to support the weight of the substation. If the substation is located near combustible materials. Use leads that are long enough to avoid mechanical strain caused by expansion and contraction. DANGER HAZARD OF ELECTRIC SHOCK. Failure to follow this instruction will result in death or serious injury. make sure the location meets or exceeds the minimum clearances as required by the National Electric Code® (NEC®) or other applicable local codes. Clean the contact areas of the terminals (if applicable). 10 © 2001–2004 Schneider Electric All Rights Reserved .Model III Package Substations Section 4—Installation 43500-054-30R1 02/2004 SECTION 4—INSTALLATION ENGLISH NOTE: Complete startup services are available from Square D Services. If tap adjustments are necessary. 3. Failure to follow this instruction will result in death or serious injury. OR ARC FLASH The transformer is not tamper proof. Follow these guidelines when making connections: 1. The substation has both high voltage (HV) and low voltage (LV) connections. Strain can cause loose connections over time. ensure all bolted connections are torqued to the values given on the substation labels and in this bulletin. Using a torque wrench. Ensure the foundation has adequate drainage. Multiple tap positions are available on the HV winding of the transformer to allow for adjustments. Allow only authorized personnel access to the transformer. Consult local and national codes to ensure all applicable requirements are satisfied. Electrical Connections DANGER HAZARD OF ELECTRIC SHOCK. 00–14 Detail D Detail E . FI KA.2–230. 5/16 in.50–13 . ME NA.3–27.3–95. MH.1 N•m) 100–155 lb-ft (135. NC.7–210. FH.3 N•m) 3–6 lb-ft (4.6 N•m) 110–130 lb-ft (149.0 N•m) 80–90 lb-ft (108. Branch.5–122. C. LH MA. Table 3: Multiple Conductor Neutral and/or Ground Bar Torque Value 20 lb-in (2 N•m) 25 lb-in (3 N•m) 35 lb-in (4 N•m) 36 lb-in (4 N•m) 45 lb-in (5 N•m) 100 lb-in (11 N•m) 275 lb-in (31 N•m) Screw Type Lug Wire Range Conductor Size 14-10 Cu. MX. KH.1 N•m) 110–170 lb-ft (149.50–13 .0–8.38–16 .43500-054-30R1 02/2004 Model III Package Substations Section 4—Installation Torque Guidelines for Transformer Electrical Connections Bolt Size Tinnerman nut Detail A Polyester insulator Detail B Tinnerman nut Detail C .1 N•m) 15–20 lb-ft (20.3–67. D Detail B Detail E Detail B.1 N•m) 40–50 lb-ft (54. 1/2 in. KI LA. FC. 3/8 in.38–16 . 12-10 Al 14–4 Slotted Head 14–1/0 14–1/0 6–300 kcmil 8 Cu-Al 6-4 Cu-Al 14-8 Cu-Al 6-1/0 Cu-Al All All Socket Head Table 4: QED-3 Circuit Breaker Connector Bolts Torque Value Line/Load Connector Bolts 55-65 lb-in (6–7 N•m) 65-75 lb-in (7–8 N•m) 145-160 lb-in (16–18 N•m) 130-150 lb-in (15–17 N•m) 130-150 lb-in (15–17 N•m) Circuit Breaker Type FA.0–8.75–10 .62–11 1.4 N•m) Bolt Lock washer Belleville Nut* Belleville Nut* (Minimum 2 threads showing) Flat washer Flat washer *(Minimum 2 threads showing) Bolt Flat washer Material Torque Guidelines for Circuit Breaker Electrical Connections Table 2: Incoming. D Detail B Detail B Detail B Detail B Torque Range 3–6 lb-ft (4.25–20 . and Neutral Lug Torque Value 180 lb-in (20 N•m) 250 lb-in (28 N•m) 340 lb-in (38 N•m) 620 lb-in (70 N•m) Socket Size Across Flats 1/4 in. NE © 2001–2004 Schneider Electric All Rights Reserved 11 ENGLISH Table 1: Transformer Torque Values .62–11 Grade 2 2 5 2 2 5 2 1018 5 Application (see diagram at left) Detail A Detail B.8 N•m) 40–70 lb-ft (54.2–176. KC. NX. 2. the transformer leads must be bolted to the terminals below the switch. Strip a length of insulation from the end of the cable sufficient to fit into the full length of the lug barrel. and ring connectors to the substation enclosure with approved electrical connections. If an HVL or HVL/cc switch was not provided. Refer to page 11 for torque information. 5. Use hubs and ring connectors to protect the cables and to prevent condensation on the conduit from entering the substation. or below the fuses. Use only cable sizes suitable for a proper fit with the corresponding lugs. ENGLISH Conduit Area Cable Pulling Cable Terminations 12 1. Thoroughly clean aluminum cable contact surfaces with a wire brush or scrub them with an abrasive cloth to remove oxides and foreign matter. See section 300-20(a) of NEC. the transformer high voltage terminations are located in an air terminal chamber. Use a proper insulation stripping tool. © 2001–2004 Schneider Electric All Rights Reserved . Where cables enter or leave the substation or pass through any metal that has magnetic properties. 2. When instructed. Pull the proper number of line-side and load-side cables according to the load served and the NEC®. stubs. 3. brace or cable lace the conductors. Under seismic conditions. Maintain the maximum possible bending radii and proper clearance to bus bars and grounded parts. be certain to run all phase conductors. 1. being careful not to nick or ring the strands. If an HVL or HVL/cc switch was provided. Refer to the transformer nameplate and wiring diagram before making connections. Install cable stress relief terminator kits on each high voltage cable (when shielded cable is used) before connecting to the transformer terminals. 3. do not use the top of the substation to support the weight of the conduit. 1. the top of the substation can move as much as 3 inches (76 mm) in any direction. 2. 4. including the neutral. Locate and terminate all conduit in the substation enclosure in the “available conduit area” designated on the equipment drawing.Model III Package Substations Section 4—Installation 43500-054-30R1 02/2004 High Voltage Electrical Connections Cable terminals for connecting incoming cables are located on the top of the HVL enclosure. Install the conduit properly. 6. Bond all conduit. if provided. Install cable stress relief terminator kits on each high voltage cable (when shielded cable is used) before connecting to the HVL or HVL/cc switch. Position the cables inside the substation so that they are not subject to physical damage. Otherwise. support them to relieve this condition or place suitable protective material at the bearing point to protect the cable insulation. 3. If any cables are lying or bearing on structural members. Cable terminals for connecting incoming cables are located on the top or bottom of the HVL/cc enclosure. NOTE: If top entry. overheating can result. through the same opening. Support the conduit independently. Connection points are clearly labeled. Refer to page 11 for torque information. Any top incoming cables must accommodate this motion. Immediately apply an acceptable joint compound to the bare aluminum surfaces. An auxiliary source of control power may be necessary to accomplish this. checking for correct alignment and free operation. Torque the bolts to the values given in the tables on page 11. Check all relays. 9. using the crimping tool. the specified values. SECTION 5—PRE-ENERGIZING PROCEDURE CHECKLIST Conduct a complete inspection before the substation is energized to ensure that all components function and operate properly. 5. Current transformers (CTs) supplied for customer use require connection to a metering device load before energizing. Check all factory and field-installed lug terminations for tightness. 1. Insert the cable into the lug barrel and. Check all field-installed bus bar connections. Torque these lugs to. and instrumentation to verify that all field installed wiring connections are made properly and that the devices function properly. 4. circuit breakers. 10. Torque values for circuit breaker and switch lugs are marked on these units. Check all accessible connections for tightness. circuit breakers. make the specified number of crimps per the manufacturer’s recommendations. but do not exceed. 8. Operate all electrically operated switches. 6. All CT circuits supplied by Schneider Electric for metering use are shorted for shipment. Torque values for other lugs are marked on the substation (Table 2 on page 11). switches. © 2001–2004 Schneider Electric All Rights Reserved 13 ENGLISH 4. 7.43500-054-30R1 02/2004 Model III Package Substations Section 5—Pre-energizing Procedure Checklist a. Check the rigidity of all bus bar supports. Complete steps 1–24 before energizing the substation. Manually open and close all switches. Remove shorting terminal screws on shorting terminal blocks or jumpers and store in the block. including main substation connections to remote equipment. or as the main incoming power lugs. remount the lugs onto the bus bars. and other operating mechanisms. c. unbolt and remove them to create sufficient room for crimping the lugs to the cables with the crimping tool. 11. Set screw-type lugs may be furnished as main incoming lugs and are standard on molded case circuit breakers and QMB/QMJ fusible switches. Check the enclosure for dents or other damage that reduces electrical clearances inside the substation. b. from the electrical devices. Verify that the metering device load is properly connected. Wipe excess joint compound from the connector and insulation. 3. 5. and other devices equipped with remote operators (not under load). . Torque values are listed on page 11. Remove all foam blocks. With the cables connected. or circuit breakers. or other temporary cushioning or retaining material. If compression-type lugs are furnished on any switch or circuit breaker. 2. meters. The markings between “LO” and “HI” settings represent a range of instantaneous magnetic trip values of 5–10 times the circuit breaker’s continuous current rating. including the primary support insulators and isolation barriers. Fasten all barriers and covers in place. resulting in overheating. by the single setting (Figure 5).Model III Package Substations Section 5—Pre-energizing Procedure Checklist 43500-054-30R1 02/2004 12. when used. adjust the magnetic trip as outlined in the respective instruction manual. have an adjustable magnetic trip. 16. This can cause a loose connection. beginning on page 28 for circuit breaker information. Inspect all insulation surfaces for dirt and moisture. refer to “Section 13—Reference Publications”. If necessary. CAUTION HAZARD OF EQUIPMENT DAMAGE Do not pry open or spread the fuse mounting clips. 14. On substations containing an electronic trip circuit breaker. wipe with a clean cloth. To provide coordinated operation during a fault. Factory-installed molded case circuit breakers. Figure 5: Instantaneous Trip Setting ENGLISH 14 Magnetic Trip Adjustment 13. 19. 17. Verify that all grounding connections are correctly made. NOTE: For molded case circuit breakers. which is shipped on the “LO” setting. All poles are adjusted simultaneously. 250 A frames or larger. 15. Insert the proper keys in the interlocks. Check all control wiring (when present) with the wiring diagrams to ensure that connections are properly made. 18. using a screwdriver. conduct electrical insulation © 2001–2004 Schneider Electric All Rights Reserved . set the tripping characteristic curve of the adjustable electronic trip unit as outlined in the respective instruction manual or coordinating study. With the neutral isolated from the ground and the HVL or HVL/cc switch and circuit breakers open. Conduct an electrical insulation resistance (megger) test to ensure that the substation is free from short circuits and undesirable grounds. Failure to follow this instruction can result in injury or equipment damage. Open all control power and metering disconnects or remove the fuses from the control circuits. scrap wire. Consult Square D Services at 1-800-634-2003 to help correct any problems. to withstand fault currents. Verify that all control wiring between sections is connected. when instructed. and then close the doors. If disconnect switches cannot be opened. © 2001–2004 Schneider Electric All Rights Reserved 15 ENGLISH tests from phase to phase. the system may be unsafe and should be investigated. . 22. EXPLOSION. Make certain all enclosure parts are aligned properly and fastened securely. Failure to follow this instruction will result in death or serious injury. causing overheating and improper operation. Vacuum to remove any dust. check for any pinched wires. 21. Check all field-installed wiring.43500-054-30R1 02/2004 Model III Package Substations Section 5—Pre-energizing Procedure Checklist DANGER HAZARD OF ELECTRIC SHOCK. CAUTION HAZARD OF EQUIPMENT DAMAGE Do not use an air hose to blow out the substation. 20. If the resistance reads less than one megohm while testing with the branch circuit devices in the open position. or other debris. Replace all covers. 24. phase to ground. phase to neutral. replace all control power fuses that may have been removed and close power disconnects that have been opened. The dust may settle inside relays and overcurrent devices. and neutral-to-ground. Failure to follow this instruction can result in injury or equipment damage. Make certain it is clear of all live parts and secured. disconnect the line leads. OR ARC FLASH Exercise extreme care to prevent the HVL or HVL/cc switch from being energized while conducting the preliminary tests. 23. After completing the electrical insulation resistance test. the door interlock is designed to prevent opening the front door while the load interrupter switch is closed. the user is responsible for removing the extra keys. Figure 6: Key Interlock SECTION 7—HVL AND HVL/CC SWITCH OPERATING SEQUENCES Refer to the Schneider Electric instruction bulletins below for specific operating instructions for HVL and HVL/cc switches. often supplied in conjunction with metal-enclosed switchgear to direct proper operation of the equipment. the user should provide only the necessary keys to properly operate the equipment. DANGER HAZARD OF ELECTRIC SHOCK. unauthorized personnel will have access to the equipment.Model III Package Substations Section 5—Pre-energizing Procedure Checklist / Section 6—Interlocks 43500-054-30R1 02/2004 SECTION 6—INTERLOCKS ENGLISH Mechanical interlocks are standard features designed to promote proper operation of the substation. After reviewing the key interlock specifications. — 9840IM9301 (Alt. 2. accessible to only selected personnel.5 kV 16 © 2001–2004 Schneider Electric All Rights Reserved . Failure to follow this instruction will result in death or serious injury.4kV–38 kV — 6045-1 HVL/cc Metal-Enclosed Switchgear. Extra keys should be destroyed or placed in a secure place. If extra keys are made generally available. 2. For example.4 kV–17. # 9840-3) Type HVL Load Interrupter Switch — 6040IM9202 (Alt. OR ARC FLASH When equipment is supplied with extra interlock keys. # 6040-2) Metal-Enclosed Switchgear. to be used during installation. EXPLOSION. Key interlocks (Figure 6) are optional equipment. or any other low voltage control system that is connected to the transformer windings that are involved in these tests. low voltage. Drying Transformer Coils CAUTION FIRE HAZARD Constant attendance during the drying process is recommended.43500-054-30R1 02/2004 Model III Package Substations Section 8—Startup Testing to Energize DANGER HAZARD OF ELECTRIC SHOCK. Contact Square D Services at 1-800-634-2003. and neutral connections. from installation to comprehensive testing and verification of the new equipment. EXPLOSION. . the fan and temperature control system. They can provide assistance in a variety of areas. OR ARC FLASH • Only qualified personnel should perform these tests. Have a suitable fire extinguisher on hand for use in the event of an emergency. © 2001–2004 Schneider Electric All Rights Reserved 17 ENGLISH SECTION 8—STARTUP TESTING TO ENERGIZE NOTE: Complete startup services are available from Square D Services. Place the lamps or heaters a minimum of 4 to 6 inches (102 to 152 mm) away from the transformer coils. Failure to follow these instructions can result in injury or equipment damage. meters. Failure to follow this instruction can result in injury or equipment damage. • Do not allow the lamps or heaters to contact the transformer coil insulation. Pre-energizing Testing Before energizing the transformer and placing it in service. Failure to follow these instructions will result in death or serious injury. Turns Ratio: Measures the ratio of the primary to secondary turns to check for possible insulation degradation in the windings. The transformer MUST be kept dry during storage. Use lamps or heaters to keep the surface dry and the core and coil from absorbing moisture. • Drying the Core and Coil Assembly CAUTION FIRE HAZARD • Do not exceed 100 °C air temperature. • DO NOT disconnect the ground connection to the transformer frame. Good ventilation is essential. • Disconnect auxiliary equipment. Schneider Electric recommends that the following tests be performed: • Insulation Resistance: Measures the resistance of the insulation between the primary and secondary windings and from each winding to ground. such as lightning arresters. • Disconnect ALL high voltage. 24-hours a day. if the transformer is de-energized and allowed to cool to ambient temperature. When measured in accordance with ANSI/IEEE Standard C57. apply external heat to the transformer using the heater or lamp method described above. If heaters are not used.) If moisture is present or if the insulation resistance is low.2 2. dry the transformer using one of the methods described in “Drying the Core and Coil Assembly” on page 17.7 15. Measuring insulation resistance is valuable in determining the drying status. If the transformer is shut down for longer than 24 hours during high humidity. ENGLISH Heaters and Lamps for Drying Insulation Resistance Testing Turns Ratio Test Effects of Humidity 18 Heaters: Blow the heated air from space heaters or other small heaters into the bottom grills of the transformer enclosure and through the winding ducts. Lamps: Use six 150 watt lamps.94. Before performing the insulation resistance test. If the transformer has more than surface moisture present. If the shutdown occurs during low humidity. Drying time depends on the condition of the transformer. size. the minimum insulation resistance should be as listed in Table 5: Table 5: Insulation Resistance Values Insulation Resistance (MΩ) 600 1000 1500 2000 3000 Winding kV Class 1. not around the core sides.91 for additional information. After de-energizing the transformer. © 2001–2004 Schneider Electric All Rights Reserved . voltage. Refer to ANSI C57. To dry the transformer. place space heaters below the core and coils to keep the transformer temperature a few degrees centigrade above that of the surrounding air. Place two lamps under each coil–one on each side of the core. However. amount of moisture absorbed. (See “Drying Transformer Coils” on page 17.12. inspect the transformer for visible moisture and measure the insulation resistance. high humidity may affect transformer start up and operation.0 Perform the turns ratio test at each tap position and for the full winding: 1. use a vacuum cleaner to clean the core and coil assembly.Model III Package Substations Section 8—Startup Testing to Energize 43500-054-30R1 02/2004 The transformer core and coils MUST be dry before the transformer can be tested and energized. 2. humidity is relatively unimportant. No special precautions are necessary. particularly if condensation occurs within the enclosure. and method of drying. more extensive drying may be required to ensure that the core and coils are dry.5 5. then precautions are required. When the transformer is energized. Compare these measurements to the transformer nameplate voltage ratio. Use a Transformer Turns Ratio (TTR) to measure the ratio between the primary and secondary windings. The measurements should be within 1/2 of 1% of the nameplate voltage ratio. the transformer can be energized following normal startup procedures.0 8. Verify the voltages on the transformer primary and secondary. or other auxiliary devices. and ensure clearances are adequate between the transformer enclosure and internal bus bars. Turn off all downstream loads. © 2001–2004 Schneider Electric All Rights Reserved 19 ENGLISH a. DANGER HAZARD OF ELECTRIC SHOCK. EXPLOSION. Energize the HVL or HVL/cc switch with the switch in the open position. 2. See “Changing Tap Positions to Adjust Voltage” on page 20. Before energizing the substation. Verify the selection of taps and ratio connections against the transformer nameplate information. relays.43500-054-30R1 02/2004 Model III Package Substations Section 8—Startup Testing to Energize Energizing the Substation 1. Torque all connections according to the torque guidelines on page 11. If the voltages are not as required. Remove all hand tools. 5. 4. 6. beginning on page 13. or any other foreign material from inside the enclosure. use the taps to adjust the voltage. They are clearly tagged or painted yellow. e. Remove all shipping braces and shipping bolts (if present). do the following: NOTE: DO NOT remove the fiberglass tubing (if provided) that surrounds the high voltage cables. c. controllers. • Correct short circuit conditions detected during the checkout procedures described in “Section 5—Pre-energizing Procedure Checklist”. motors. Do not leave tools or other equipment on the core and coil assembly. Check the transformer nameplate before measuring voltages and ensure that properly rated meters are used to verify the primary and secondary transformer voltages. b. Energize the transformer with no load on the LV distribution section by closing the HVL or HVL/cc switch. • Qualified electrical personnel must be present when energizing this equipment for the first time. d. 3. . No load should be on the I-Line panelboard or main breaker when it is energized. Verify the operation of fans. Failure to follow these instructions will result in death or serious injury. OR ARC FLASH • Only qualified personnel with appropriate measurement devices should measure the voltages on the transformer. equipment. • Follow the instruction in this section to properly energize the I-Line® panelboard or main breaker. NOTE: For multiple voltages or other special arrangements. Failure to follow these instructions will result in death or serious injury. equipment. Use an appropriate grounding device to ground the coils and discharge any static charge. refer to NEMA ST-20. To meet NEMA listed average sound levels. Do not rely on visual indications. • Disconnect all power and verify the transformer is de-energized before servicing the transformer. Locate the transformer taps above the coils of the transformer. ceilings. The tap jumpers must be on the same tap position for each phase. such as switch position or fuse removal for determining a de-energized condition. Change the tap jumpers on each phase to the appropriate tap connection. To change the tap position: 1. each unit should be installed in a location where there is a 10-foot clearance on all sides except floor or ground. Energize the transformer. 4. Refer to the torque values on page 11. 3. They can be accessed by removing the rear access panel on the back of the low voltage distribution section. conduits. Inspect the enclosure to ensure all hand tools. Avoid rooms where hard surfaces are in close proximity to the transformer. 20 © 2001–2004 Schneider Electric All Rights Reserved . see the transformer nameplate. 5. When transformers must be located in noise sensitive areas. review “Section 2— Safety Precautions” on page 6. De-energize the transformer following the safety messages above and your company’s lock-out/tag-out procedures. or any other foreign materials are removed from the enclosure. 6. The fundamental frequency is twice that of the applied voltage.Model III Package Substations Section 8—Startup Testing to Energize 43500-054-30R1 02/2004 Changing Tap Positions to Adjust Voltage DANGER HAZARD OF ELECTRIC SHOCK. and mounting bases. • Ensure no paths are present for backfeeding power to the transformer (such as through a tie-breaker). Install the unit in an area where the noise will be least objectionable. Use a properly rated meter to measure for the presence of voltage at the terminal and to verify the transformer is de-energized. Sound waves may be amplified by means of reflected waves and/or radiated waves via walls. 8. precautions should be taken to avoid amplification of the transformer sound. For average expected sound levels. floors. OR ARC FLASH • Before performing this procedure. Locate the tap jumpers. Re-install the rear access panel. 2. mechanical vibrations of air ducts. • Do not change the tap connections when the transformer is energized. Torque the tap connections. Units located in close proximity to hard surfaces may produce higher than average sound levels. 9. 7. EXPLOSION. ENGLISH Sound Level All transformers have an inherent sound level that varies with the size of the units. 3. inspect the substation every three months or sooner. insulators. . Check the torque values on all electrical connections.01. condensation buildup. floors. cables.) Use flexible conduit and bus connections. Be absolutely sure no backfeed exists through any feeder circuit. After the first few inspections. and parts replacement must be performed only with the primary source(s) of power disconnected and locked open. Inspect all conduit entrances and cracks between the enclosure panels for dripping leaks. Vacuum the substation interior to remove any dirt and dust deposits. Check the substation interior carefully for moisture. from installation to comprehensive testing and verification of the new equipment. Avoid uneven mounting surfaces. (Except on certified seismic units. NOTE: If overheating occurs. If the transformer is operating in usual service conditions as defined in ANSI/IEEE C57. OR ARC FLASH Inspection. hallways. If specified. Tighten and/or repair if necessary. Loose or contaminated connections can cause overheating. and signs of any previous wetness. be sure that all conditions that caused the overheating have been corrected. and ceilings. Discoloration and flaking of insulation or metal parts are indicators of overheating. determine a more definite schedule based on the existing conditions. De-energize the substation following the safety messages in “Section 2— Safety Precautions” on page 6 and your facility’s lock-out/tag-out procedures. with a clean. Condensation in conduits may be a source of moisture and must not be allowed to drip onto live parts or insulating material. They can provide assistance in a variety of areas. 1. 24-hours a day. for unusual locations where the air is contaminated with particles such as dust or chemical fumes.43500-054-30R1 02/2004 Model III Package Substations Section 9—Maintenance Reduction of Structure Borne Noise Loosen anchor bolts between the transformer and enclosure and let the unit rest on the vibration pads only. However. low sound level transformers can be provided for most applications. Avoid installation of units in corners. and floors with low masses. Avoid mounting the unit on walls.12. dry. SECTION 9—MAINTENANCE NOTE: Complete maintenance services are available from Square D Services. balconies. lintfree cloth. including the ground connection(s). Failure to follow this instruction will result in death or serious injury. and stairways. Contact Square D Services at 1-800-634-2003. and so forth. Inspect the substation for any signs of overheating. 4. and near heating and air conditioning ducts. Wipe all bus bars. The frequency of inspection depends on operating conditions. 2. EXPLOSION. Inspect the substation regularly. Moisture can cause insulation failures and rapid oxidation of current-carrying parts. DANGER HAZARD OF ELECTRIC SHOCK. © 2001–2004 Schneider Electric All Rights Reserved 21 ENGLISH Use acoustic absorbing materials on walls. maintenance. Refer to the torque values on page 11. an inspection once a year may be sufficient. Take the necessary steps to eliminate the moisture and seal off all leaks. DO NOT re-energize the transformer if the test results are not acceptable. Check for signs of rodent nesting in the substation. and your facility’s lock-out/tagout procedures. in “Section 2—Safety Precautions” on page 6. or missing parts. 4. # 6040-2) Metal-Enclosed Switchgear.4 kV–17. ensure all bolted connections are torqued according to the torque guidelines in Table 1 on page 11. If required. If damage has occurred. 3. 1. and your facility’s lock-out/tag-out procedures. © 2001–2004 Schneider Electric All Rights Reserved . Manually open and close switches and circuit breakers several times to verify they are working properly. Refer to the Schneider Electric instruction bulletins below for specific maintenance instructions for HVL and HVL/cc switches. 2. Failure to follow these instructions will result in death or serious injury. EXPLOSION. de-energize the transformer in accordance with the safety messages on page 21. use a good exterminating technique in the general area of the substation. 6. cracked.4kV–38 kV — 6045-1 HVL/cc Metal-Enclosed Switchgear. perform maintenance by following the procedures starting on page 21. DANGER HAZARD OF ELECTRIC SHOCK. in “Section 2— Safety Precautions” on page 6. contact the Square D Medium Voltage Transformer facility at 704-283-7411. Carefully inspect all devices for any visibly worn-out. Some of these products attract rodents. Remove the enclosure panels and inspect the transformer core and coil assembly for any physical damage. Perform the tests described in “Section 8—Startup Testing to Energize” on page 17. If no damage has occurred and all test results are acceptable. Before performing any inspections. If the transformer is energized. # 9840-3) Type HVL Load Interrupter Switch — 6040IM9202 (Alt. Using a torque wrench. 7. verify that the substation has been de-energized in accordance with the safety messages on page 21.Model III Package Substations Section 9—Maintenance 43500-054-30R1 02/2004 5. Verify that all key interlocks and door interlocking provisions are working properly. 2. 2. OR ARC FLASH Do not re-energize the transformer if the transformer has been damaged. and your facility’s lock-out/tag-out procedures. 8. ENGLISH After a Major Fault Inspection Procedure for HVL and HVL/cc Switches Transformer Inspection Procedure 22 NOTE: Do not place or use exterminating substances and chemicals inside the substation. Give the switch an overall maintenance check at least once each year.5 kV Before performing any inspections. verify that the substation has been deenergized in accordance with the safety messages on page 21. — 9840IM9301 (Alt. in “Section 2—Safety Precautions” on page 6. For general maintenance: 1. 3. Exercise circuit breakers at least once a year to ensure proper operation. OR ARC FLASH • Before performing this procedure. cables. Confirm that the coil ducts are clear. (On most molded case circuit breakers this © 2001–2004 Schneider Electric All Rights Reserved 23 ENGLISH 1. Replace corroded hardware. EXPLOSION. . Remove the rear enclosure panel to access the transformer high voltage windings. Wipe down all parts of the core. Cleaning DANGER HAZARD OF ELECTRIC SHOCK. Failure to follow this instruction can result in injury or equipment damage. Clear away any debris or other foreign objects from all ventilation openings. CAUTION HAZARD OF EQUIPMENT DAMAGE Do not push or pull the cloth through the coils. Make sure the enclosure floor is clean. stand off insulators. use a vacuum to remove any dust or debris. To clean the transformer. Remove the enclosure panel or door to access the transformer high voltage windings. If deterioration is present. and other surfaces within the enclosure. See “Section 12— Replacement Parts” on page 28.43500-054-30R1 02/2004 Model III Package Substations Section 9—Maintenance Follow steps 1–4 to inspect the transformer 2. Check the enclosure for deterioration. De-energize the transformer following the safety messages above and your facility’s lock-out/tag-out procedures. as required. bus bars. follow these steps: 1. 4. Use a vacuum cleaner or simply wipe with towels. Be sure to remove all rags or other maintenance equipment from the coil ducts and check for tools when finished. review “Section 2— Safety Precautions” on page 6. 5. If possible. Repaint deteriorated areas. Clean any loose debris and dust from around the coils. Molded Case Circuit Breakers Inspection Procedure Molded case circuit breakers manufactured by Schneider Electric are designed as totally sealed units requiring minimal periodic maintenance. ensure all static charge has been discharged by grounding the coils with an appropriate grounding device. 2. Trip the circuit breaker by pushing the Push to Trip button located on the face of the circuit breaker. • Before servicing the transformer. Failure to follow these instructions will result in death or serious injury. core frames. 4. 3. being careful not to cut yourself on any sharp edges or protrusions. determine the cause and correct (if possible). with prompts to the user for initial information. NOTE: If additional lubrication is required.5 in. HNM1BL HNM4BL HLW1BL HLW4BL Blank Fillers Blank Extensions 1. overheating can occur. do not set the long time trip rating at a higher ampacity than the rating of the bus bar or load cables it supplies. © 2001–2004 Schneider Electric All Rights Reserved . It runs trip unit tests automatically. catalog number UTS3. This procedure tests alarm switches if they are built into the circuit breaker. The universal test set. all unused I-LINE circuit breaker mounting spaces must be filled with blank fillers and/or extensions as listed in Table 6 on page 24. ENGLISH 24 DANGER HAZARD OF ELECTRIC SHOCK. to the plug-on connectors’ contact surfaces. Schneider Electric manual number 0600PD9602. Refer to individual circuit breaker instruction manuals shipped with the substation for additional maintenance information. This also exercises the trip mechanism.) Contact your Schneider Electric field sales representative to obtain this manual. 2. (Refer to “Section 13—Reference Publications”. Failure to follow this instruction can result in injury or equipment damage. Manually open and close the circuit breaker two to three times. (114 mm) 1. OR ARC FLASH • If circuit breaker settings are adjusted. such as changing rating columns or adjustable settings and removing circuit breakers. Field Testing Industrial Molded Case Circuit Breakers. and contact your Schneider Electric field sales representative to obtain this manual. see “Section 13—Reference Publications” of this manual for the appropriate number. provides more in-depth information. If the instruction manual is not available. Failure to follow these instructions will result in death or serious injury. apply a coating of electrical joint compound.5 in. is available to test all circuit breakers by Schneider Electric that are equipped with MICROLOGIC® trip units.5 in. Test modules for each circuit breaker frame are used to store data necessary for automatic tests. (38 mm) 4.Model III Package Substations Section 9—Maintenance 43500-054-30R1 02/2004 button will be yellow). (114 mm) 3. CAUTION HAZARD OF EQUIPMENT DAMAGE Do not remove the protective lubricant on the plug-on connectors. (38 mm) 4. • Before energizing the substation. Table 6: Blank Fillers and Extensions Height Catalog No.5 in. catalog number PJC7201. or electrical interlocks between two circuit breakers. EXPLOSION. beginning on page 28. Failure to follow these instructions will result in death or serious injury. If a short circuit occurs. Contact your Schneider Electric field sales representative to obtain this manual. If no downstream grounds are detected and the ground fault system is not operating properly. If the ground fault protection system does not operate properly and additional equipment has been connected to the installation since the last maintenance test/check. The substation must be de-energized. de-energize the entire system and check for grounds on the neutral downstream from the main bonding jumper. Likewise. Before energizing the substation. SECTION 10—ADVERSE CIRCUMSTANCES This section includes. For more information © 2001–2004 Schneider Electric All Rights Reserved 25 ENGLISH . Otherwise. contact Square D Services at 1-800-634-2003 for special instructions. circuit breaker removal is not required. High mechanical and thermal stresses developed by short circuit currents may damage conductors and insulation. OR ARC FLASH • Turn off all power supplying the substation before servicing. contact Square D Services at 1-800-643-2003. all unused circuit breaker mounting spaces must be filled. If the system can be tested with or without tripping the main or branch device. such as molded case circuit breakers. testing the ground fault protection system will trip the main or branch device to which it is connected. replace it. directions for testing the system are in the device manual. Ground Fault Protection Systems Check the terminal connections on the ground fault protection system at least once a year for tightness and corrosion. If the ground fault sensor or relay is physically or electrically damaged. 1. DANGER HAZARD OF ELECTRIC SHOCK. • Use a properly rated voltage sensing device to verify that power is off. refer to “Section 13—Reference Publications”. which is included in UTS3. NOTE: Before attempting to re-energize the substation following a fault. If the manual is not available. Check the overcurrent protection device that interrupted the short circuit current for possible arcing damage. These devices should be replaced if damaged. beginning on page 28 of this manual to obtain the appropriate number. EXPLOSION. but is not limited to all electrical components of the substation. Refer to the ground fault field test instruction manual for additional testing information. make a thorough inspection of the entire system and verify that no damage to conductors or insulation has occurred. Do not open sealed devices. and the ground fault protector does not operate properly. NOTE: Tests may be conducted with a circuit breaker installed.43500-054-30R1 02/2004 Model III Package Substations Section 10—Adverse Cirmumstances Series B MICROLOGIC trip units require test module CBTMB. contact Square D Services. De-energize the substation following your company’s lock-out/tag-out procedures. all unused breaker mounting spaces must be filled. if no additions have been made to the installation. • Before energizing the substation. OR ARC FLASH • Turn off all power supplying this equipment before working on it. The substation has not been submerged or exposed to water for long periods of time. Do not re-energize the transformer if the test results are not acceptable. The insulating properties of some organic insulating materials may deteriorate during an electrical arc. • Use a properly rated voltage sensing device to verify that power is off. Perform the tests described in “Section 8—Startup Testing to Energize” on page 17. OR ARC FLASH Do not re-energize the transformer if the transformer has been damaged. 5. 3. Replace carbon-tracked insulation. Do not energize the substation. make a thorough inspection of the entire system and verify that no damage to conductors or insulation has occurred. beginning on page 28. such as molded case circuit breakers or fuses. If damage has occurred. beginning on page 28. NOTE: Contact Square D Services before cleaning a substation that has been subjected to a short circuit situation. ENGLISH Clean-up Following a Short Circuit Water-Soaked Substations Water-Sprayed or Splashed Substations (Clean Water Only) Inspection and Clean-up of Clean Water Sprayed or Splashed Substations 26 2. These devices should be replaced if damaged. EXPLOSION. refer to the appropriate instruction manual listed in “Section 13—Reference Publications”. Do not clean or repair a substation that has been exposed to large volumes of water or submerged at any time. 4. contact Schneider Electric. DANGER HAZARD OF ELECTRIC SHOCK. Follow steps 1 through 9 only if: • • No signs of physical damage to the equipment are present. ensure all bolted connections are torqued according to the torque guidelines on page 11. If the substation has been sprayed or splashed with small amounts of clean water. Using a torque wrench. If no damage has occurred and all test results are acceptable. DANGER HAZARD OF ELECTRIC SHOCK. Contact Square D Services. Perform the tests and inspection of the HVL or HVL/cc switch as described in “Section 9—Maintenance” on page 21. perform maintenance by following the procedures in “Section 9—Maintenance” on page 21. Failure to follow these instructions will result in death or serious injury. and electrical components may be damaged beyond repair. insulation systems. Do not open sealed devices. EXPLOSION. © 2001–2004 Schneider Electric All Rights Reserved . For more information about these devices. Current carrying parts. Remove the enclosure panels and inspect the transformer core and coil assembly for any physical damage. Failure to follow these instructions will result in death or serious injury. refer to the appropriate instruction manual listed in “Section 13—Reference Publications”.Model III Package Substations Section 10—Adverse Cirmumstances 43500-054-30R1 02/2004 about these devices. and insulation material with a clean. Perform the megohm tests as described in step 5 above on the HVL or HVL/cc switch. contact Square D Services at 1-800-634-2003. If the resistance measurements are less than 0. 2. Optional temperature control modules are available on ventilated dry type transformers. © 2001–2004 Schneider Electric All Rights Reserved 27 ENGLISH The water that has been in contact with the substation has not been contaminated with sewage. 7. The substation must remain completely de-energized. Turn all circuit breakers or switches to their “ON” position. SECTION 11—OPTIONAL EQUIPMENT Temperature Monitoring Systems This section provides information about optional equipment. Phase-to-phase with circuit breaker “ON”.5 megohm for the switch and circuit breakers and greater than the Table 5 values for the transformer. If ALL of the conditions listed above are true. inspect for water entering through conduits located above live parts. Perform the megger tests on the transformer as described in “Section 8—Startup Testing to Energize” on page 17. Specifically. If the resistance values are greater than 0. The monitor controls the fans and provides alarm indication. 3. The factory pre-set temperature alarm and control settings for ventilated transformers are listed in Table 7. b. the substation can be energized using the procedures listed in “Section 8—Startup Testing to Energize”. call Square D Services at 1-800-634-2003 for recommendations. insulators. lint-free cloth. dry. . proceed as follows: 1. See the manufacturer’s instruction manual included with the transformer documentation package for detailed information about the installation. Use a megohmmeter with a capacity of 500—1. or less than the values in Table 5 on page 18 for the transformer. Completely de-energize the substation. operation. Disconnect and electrically isolate the substation so no contact can be made with energized parts.43500-054-30R1 02/2004 Model III Package Substations Section 11—Optional Equipment • • The water that has been in contact with the substation has not entered any area of the enclosure that may contain wiring installed as intended and located above any live parts. Each phase-to-ground with circuit breaker “ON”. Prepare the substation for insulation resistance (megger) testing by disconnecting all line-side supply connections and all load-side cable connections to isolate the substation from the wiring system.000 Vdc and apply voltage from: a. Wipe off all moisture from the bus bars. 9. 8. beginning on page 17.5 megohm for the switch and/or circuit breakers. chemicals. 6. 5. Do not use cleansing agents or water displacement sprays. 4. or other substances that can negatively affect the integrity of the electrical equipment. and maintenance of the monitor. If any of these conditions have been met. Provide full nameplate information and a description of the part that is needed. and factory order number of the equipment in which the part is to be used. the part number of a new part can be obtained from identification of the old part. KI. SKC. such as an I-LINE panel. SECTION 12—REPLACEMENT PARTS SECTION 13—REFERENCE PUBLICATIONS The following Schneider Electric publications are available through your Schneider Electric field sales representative. When ordering parts. LC I-LINE Circuit Breakers KA. NC. or space heaters. Often. FH. vertical section. LH. Contact Schneider Electric for price and availability. FC. such as meters. KC. See the instruction manual included with the substation documentation package for detailed information about the monitor. include as much information as possible. Q4 Instructions Q2 Instruction Sheet 28 © 2001–2004 Schneider Electric All Rights Reserved . KH. Table 8: Title Installation Instructions Publication Number 48940-158-02 48040-797-04 48040-732-03 48049-031-02 48049-033-01 48049-034-02 48040-008-08 FA. is not customer serviceable. Any maintenance ® procedure or device not listed. may be supplied if specified. current or potential transformers. Specify the rating. SL 1200 I-LINE® Circuit Breakers LI. SKI Instructions FI Instructions LA. These include device replacement procedures and spare parts listings to make ordering and servicing of replacement parts quick and convenient. SLA. If specified. Sketches or photographs may be useful in describing the part.Model III Package Substations Section 12—Replacement Parts 43500-054-30R1 02/2004 Table 7: Stage Fan On Alarm On Trip Signal Factory-Set Temperature Alarm and Control Settings Temperature Rise Transformers with 80 °C/150 °C Temperature Rise Rating 110 °C 195 °C 220°C Transformers with 115 °C/150 °C Temperature Rise Rating ENGLISH Fans (Forced Air) Powerlogic® Circuit Monitor Other Optional Equipment Fan On Alarm On Trip Signal 145 °C 195 °C 220 °C Transformers with 150 °C Temperature Rise Rating Fan On Alarm On Trip Signal 180 °C 195 °C 220 °C When provided. Other optional equipment. Contact Schneider Electric for information. an optional POWERLOGIC Circuit Monitor may be supplied. SFH Circuit Breakers NA. bladed fans located above the transformer coils provide the forced air cooling. Some replacement parts for the transformer are available. 4 kV–38 kV HVL/cc Metal-Enclosed Switchgear.4 kV–17. MX Electronic Trip Circuit Breakers NE. 4000) POWERLOGIC System Display for MICROLOGIC® Circuit Breakers (SD-100.5 kV 48049-032-02 48040-189-05 48049-085-01 48049-086-01 48040-884-06 48040-495-06 48040-756-05 40268-292-01 48049-071-02 40268-525-02 9840IM9301 (Alt # 9840-3) 6040IM9202 (Alt. NX Drawout Circuit Breakers PE/PX Manual SE Electronic Trip Circuit Breaker POWERLOGIC® Circuit Monitor (CM-2050.43500-054-30R1 02/2004 Model III Package Substations Section 14—Reference Publications Table 8: Title Installation Instructions (continued) MA. 2250. PMD-32) Table 10: Title Ground Fault Field Test Instructions Publication Number 48040-757-04 63020-271-01 80043-054-01 Ground Fault Module (GFM) Field Test Procedure ME/NE/PE and MX/NX/PX Electronic Trip Circuit Breakers Type GC—Ground Fault Protection System Table 11: Title Distribution Reference Catalogs Section Number 600 4620 4620 Molded Case Circuit Breakers QMB Fusible Switches QMB Circuit Breaker Adapter Units © 2001–2004 Schneider Electric All Rights Reserved 29 ENGLISH Publication Number . # 6040-2) 6045-1 Table 9: Title LE/LX Manual Instruction and Maintenance Bulletins Publication Number 48049-027-02 48049-028-02 48049-029-01 48040-940-03 48040-495-06 3020IM9301R10/97 3050IM9103 3050IM9101 3020IM9503 ME. 2350. SMH Instructions PA. MH. SD-120) POWERLOGIC Power Interface for MICROLOGIC Circuit Breakers (PIF-3) POWERLOGIC Power Meter (PM-600. 2150. SMA. 2. PM-620. 2450. 2. PH Instruction Sheet FA-M01 and KA-M01 Motor Operator LA-M01 and MA-M01 Motor Operator PA-M02 Motor Operator SE Ground Fault Module (GFM) Ground Fault Protection System—Type GC MASTERPACT® Universal Power Circuit Breaker QMB Fusible Switches HVL Switch Metal-Enclosed Switchear. 0600PD9602 For information about obtaining NEMA documents.Model III Package Substations Section 14—Reference Publications 43500-054-30R1 02/2004 Table 12: Title Other Reference Literature Publication Number ENGLISH 30 General Instructions for Proper Installation.1 Maintenance of Switchboards Rated 600 V or Less Application Guide for Ground Fault Protective Devices for Equipment Circuit Breakers Enclosed and Miscellaneous Distribution Switches Electrical Equipment Maintenance Molded Case Circuit Breakers Field Test and Maintenance NEMA Publication PB2. write to: National Electrical Manufacturers Association (NEMA) Attention: Customer Service 1300 North 17th Street Suite 1847 Rosslyn. VA 22209 © 2001–2004 Schneider Electric All Rights Reserved . Operation.2 NEMA Publication AB-4 NEMA Publication KS-1 NFPA 70B-1999 Schneider Electric Bulletin No. and NEMA Publication PB2. 43500-054-30R1 02/2004 Model III Package Substations Section 14—Installation and Maintenance Log DATE INITIALS ACTIONS © 2001–2004 Schneider Electric All Rights Reserved 31 ENGLISH SECTION 14—INSTALLATION AND MAINTENANCE LOG . operated.com Electrical equipment should be installed. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. TN 37217 USA 1-888-SquareD (1-888-778-2733) www.SquareD.Instruction Bulletin Model III Package Substations Schneider Electric 1010 Airpark Center Drive Nashville. serviced. 43500-054-30R1 © 2001–2004 Schneider Electric All Rights Reserved Replaces 43500-054-30 dated January 2001 02/2004 . and maintained only by qualified personnel.
Copyright © 2024 DOKUMEN.SITE Inc.