(2011-01-21) Daikin BACnet Interface Programming Guide.pdf

March 26, 2018 | Author: parikhchirag88 | Category: Heat Pump, Hvac, Air Conditioning, Thermostat, Mechanical Fan


Comments



Description

Daikin BACnet Interface – DMS502B71Programming Guide Rev 2.0 1/21/2011 Daikin AC - Controls Engineering Dept © 2006 Daikin AC Contents ƒ VRV system overview for BMS integrator ƒ VRV system ƒ Configuration and Mechanism ƒ DIII-net system and Group address ƒ Changeover master ƒ Indoor unit ƒ Room temperature ƒ Skyair & Mini-split ƒ BACnet Object – format and list ƒ Basic to Optional ƒ Programming functions ƒ Setpoint Range ƒ Auto Changeover ƒ Setback ƒ Notes to program ƒ Others ƒ Q&A ƒ Links – Online documentation Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 2 © 2005 Daikin AC VRV Overview ƒ ƒ ƒ ƒ ƒ ƒ ƒ ƒ ƒ ƒ Great for comfort zoning – efficient to meet load time by time Quiet operation Multi-split with one refrigerant network Scalable Heat Pump, Heat Recovery system Air cooled, Water cooled 208/230, 460V 3phase; 208/230 1phase Simple communication network – DIII-NET Light Commercial – office, school, hotel etc. Residential VRV III VRV III-S Heat Pump Heat Pump / Heat Recovery VRV-WIII Water cooled Heat Pump / Heat Recovery VRV Condensing Units 3 and 4 Ton 208-230V/60Hz/1Ph 6 to 20 Ton 208-230V/60Hz/3Ph & 460V/60Hz/3ph Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 5 to 21 Ton 208-230V/60Hz/3Ph Slide 3 © 2005 Daikin AC How does it work ƒ Heat Pump System ƒ Heat Recovery System Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 4 © 2005 Daikin AC .VRV . VRV Control Concepts Æ VRV System ƒ Variable Refrigerant Volume Application Flexibility ƒ Variable loads meet variable capacity – Individual setpoints ƒ Staggered occupancy and space utilization ƒ Simultaneously heat and cool for ultimate efficiency ƒ The keyword “zoning” drives Daikin control philosophy ƒ PID Adaptive control technology optimizes efficiency ƒ Automatic device addressing at start-up ƒ Rethinking traditional means of air conditioning control DIII-Net (F1-F2) Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 5 © 2005 Daikin AC . Individual Zone Controls ƒ Heat pump system applications – Remote control groups Heat Pump Private Office Open / Common Areas ƒ Benefits ƒ One setpoint for multiple indoor units allows effective zoning ƒ Individual indoor units in a group control to their respective setpoints independent of the load on that unit or the system ƒ Give occupants the freedom to control their own environment ƒ Control groups reduce material and labor costs Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 6 © 2005 Daikin AC . Individual Zone Controls ƒ Heat recovery system applications – Zoning principals BS Box BS ox BS Box BS Box BS Box Heat Recovery Heat Recovery South Exposures North Exposures Office Application – Controls accommodating exposure affected loads Hotel application – Individual control is satisfied ƒ Benefits ƒ Exploits efficiency potential of the heat recovery technology ƒ Individual control is maintained where expected ƒ Control groups reduce cost and complexity ƒ Up to 16 indoor units on a single controller Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 7 © 2005 Daikin AC . mode. however once a multi zone controller such like BACnet Interface and I-Touch Controller is connected.) ƒ Information is stored within the indoor unit’s PCB ƒ Changes are initiated by the user at the controller and pushed to the indoor unit PCB ƒ Exceptions include navigation / programmable controllers where some functions – schedule. etc. temperature set-point. etc. * * They can be enabled back with a field setting Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 8 © 2005 Daikin AC . auto changeover. occur in the controller. these functions would be disabled.Indoor Unit has information and a control logic ƒ Daikin individual zone controllers serve as a sort of browser into the current settings residing in the indoor unit PCB (on/off. VRV Controls Concepts Æ Controllers ƒ Daikin Controls Matrix – What are your choices? Individual Zone Controllers Multi-zone Controllers Open Protocol Interfaces Adapter PCB’s Presentation Title : Presenter : Date Programming Guide Daikin BACnet Interface – Name DMS502B71 Slide 9 © 2005 Daikin AC . Typical BACnet project Configuration ƒ BMS controls / monitors each indoor unit in VRV systems through the BACnet and DIII-Net communications with BACnet Interface which is a gateway between BACnet and DIII-Net. DIII-Net DIII-Net BACnet BS Box DMS502B71 BACnet Interface BS Box BS Box DCS601C71 Intelligent Touch Controller REYQ VRVIII Heat Recovery FXMQ FXFQ Concealed Ceiling Ceiling Cassette BRC1E71 FXAQ Navigation Remote Controller Wall Mounted DIII-Net Building Automation System VRV III-S Heat Pump BACnet Interface and I-Touch Controller (Optional) FHQ Ceiling Suspended Unit BRC2A71 BRC2A71 REYMQ BMS FXMQ Concealed Ceiling Simplified Remote Controller RZQ SkyAir Heat Pump Simplified Remote Controller VRV System Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 10 © 2005 Daikin AC . GA ƒ Two Daikin 14-Ton VRVIII heat recovery systems for ƒ ƒ ƒ ƒ ƒ ƒ optimum efficiency One 4-Ton VRV-S and Two 3-Ton SkyAir systems 25 indoor units BACnet® integration to Automated Logic’s WebCTRL® automation system Includes Daikin’s Intelligent Touch Controller for backup operation Internet access via web portal and email notification of system alarms Daikin simplified remote controller for local control where required BS Box DMS502B71 BACnet Interface BS Box BS Box DCS601C71 Intelligent Touch Controller FXAQ REYQ VRVIII W/ Heat Recovery Automated Logic WebCTRL Third Party Automation System FXMQ Concealed Ceiling Unit (Medium Static) FXSQ Concealed Ceiling Unit FXMQ FHQ Concealed Ceiling Unit (Medium Static) Ceiling Suspended Unit VRV-S Simplified Remote Controller Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Simplified Remote Controller BRC2A71 BRC2A71 REYQ BRC2A71 Wall Mounted Unit RZQ SkyAir Simplified Remote Controller Slide 11 © 2005 Daikin AC .Case Study ƒ New ASHRAE Headquarters in Atlanta. Categorized by Object type DIII-Net Communication … BACnet Interface Application Interface … … … … … … BACnet … … Set of 26 Objects for each indoor unit TCP(UDP)/IP Ethernet Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 12 © 2005 Daikin AC .Mechanism Overview ƒ Available a set of 26 BACnet objects for each indoor unit which is connected to the DIII-Net system ƒ Daikin BACnet Interface is a gateway between BACnet and DIII-Net BMS VRV System Indoor unit … Application Graphics Schedule Trend etc. 3-00 to 3-15. up to 128 indoor units ƒ Group address ƒ Unique address in the DIII-Net system. 4-00 to 4-15 (64 addresses at maximum) DIII-Net system #1 DIII-Net system #2 Daisy Chained Daisy Chained 1-00 1-01 1-02 1-03 1-04 1-00 1-01 1-05 1-06 1-07 1-08 1-09 2-00 2-01 1-10 1-11 1-12 1-13 1-14 VRV Condensing Unit Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Remote Controller Indoor Unit 1-02 Group Address Slide 13 © 2005 Daikin AC . (2 in 4 as option) ƒ DIII-Net system ƒ Up to 10 VRV condensing units (Daisy chained) ƒ Up to 64 “Indoor unit Groups” = 64 remote controllers.DIII-Net system and Group address ƒ You can recognize the specific indoor unit with the DIII-Net system number and the indoor unit group address. configured manually in VRV commissioning ƒ 1-00 to 1-15. 2-00 to 2-15. BACnet Interface can handle up to 4 DIII-Net systems. Remote Control Group and Group Address Assign a group address to an indoor unit F1F2* F1F2* 1-00 Unit #0 P1P2** Assign a group address to a R/C group No R/C Group •Can monitor and control the indoor unit through F1F2 * F1F2 = DIII-Net ** P1P2 = R/C line Unit #0 BMS can control the indoor unit which is Unit #0 in a R/C group Unit #1 P1P2** Up to 16 indoor units Unit #16 •Can monitor one indoor unit (unit #0) through F1F2 •Can control one indoor unit (unit #0) through F1F2 and other indoor units will follow the unit #0 though P1P2 line Assign a group address to each indoor unit in a R/C group F1F2* BMS can monitor the indoor unit which the group address is assigned 1-00 1-00 Unit #0 1-15 1-01 Unit #1 P1P2** Up to 16 indoor units Unit #16 •Can monitor each indoor unit through F1F2 •Can control one indoor unit (unit #0) through F1F2 and other indoor units will follow the unit #0 though P1P2 line Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 14 © 2005 Daikin AC . Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 15 © 2005 Daikin AC . so that you can monitor and control each indoor unit.Remote Controller-less System Assign group address to each indoor unit 1-00 1-01 1-02 1-03 1-04 1-05 1-06 1-07 1-08 1-09 All indoor unit would be the Unit #0. ƒ Other units under the same condensing unit will follow the operation mode of the changeover master unit. Heat Recovery System ƒ You can change the operation mode to Cool or Heat on only a changeover master unit under a BS unit. ƒ In case of only one indoor unit connected a BS unit. you can change to Cool or Heat on individual indoor unit.Changeover master unit Heat Pump System ƒ You can change the operation mode to Cool or Heat on only a changeover master unit. ƒ Other units under the same BS unit will follow the operation mode of the changeover master unit. Changeover Master Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Changeover Master Slide 16 © 2005 Daikin AC . Heat Pump System Heat Recovery System DIII-Net DIII-Net BS Box BS Box Changeover Master There is one Changeover master unit under Heat pump condensing unit or Heat recovery BS Box even in case of remote controller-less system. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 17 © 2005 Daikin AC .02 or higher overrides Auto mode with Cool or Heat mode once Auto mode in an indoor unit is detected.Changeover Master and Followers Auto mode is not recommended to set because of a potential wide room temperature swing range. (See slide 20) I-TC V6. ƒ Since VRV is a packaged system. you don’t have to worry about the condensing unit. 0. ƒ There are no data points for the condensing unit except for the Compressor status. Alarm status and Malfunction code will show you.Indoor unit ƒ Indoor unit has a control logic to maintain a room temperature adjusting a refrigerant flow and has the following data points ƒ Unit On/Off – On/Off ƒ Operation mode – Cool/Dry/Heat/Fan (Auto would not work well) ƒ Setpoint (16C to 32C.1C basis) ƒ Room temperature (read only) ƒ Fan Speed (H/L or H/M/L depends of the indoor unit type) ƒ Air flow direction (if an indoor unit has a louver) ƒ Alarm status (read only) ƒ Malfunction code (read only) etc. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 18 © 2005 Daikin AC . ƒ BMS can change them or get the latest ones to control / monitor the indoor unit through BACnet Interface. If something wrong in the system. 57 for details. the fan should not be OFF. However when an indoor unit receives outside air.Daikin Indoor unit Sequence of Operation Cooling & Heating Unit Turned On Cooling Mode Thermo-on (Call for Cooling) Thermo-Off Fan in Cooling Thermo-Off period can be OFF with the field setting (this setting is available depends on the indoor unit type *). the fan should not be OFF. Thermo-on (Call for Heating) 74 73 Set-point 72 71 70 Fan H or L Off Similar to Fan Auto LL To sense the suction air temperature correctly * Field setting: see slide 56. However when an indoor unit receives outside air. Thermo-on (Call for Cooling) 74 73 Set-point 72 71 70 Fan Fan ON while the unit is ON H or L Off Heating Mode Thermo-on (Call for Heating) Thermo-Off Fan in Heating Thermo-Off period can be ON (H or L) or completely OFF with the field setting. (this setting is available depends on the indoor unit type *). Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 19 © 2005 Daikin AC . because the room temperature is below heating set-point minus 1F at the changeover point. it goes into the heating thermo-on mode.9F [0.5C]) basis around a cooling set-point. it goes into the heating mode with a heating set-point that is the cooling set-point minus the differential (0F). thermo on and off is working with +/. thermo on and off is working with +/.4F (= Cooling set-point – (0F / 2 +3. When a room temperature comes up 5. it goes into the cooling thermo-on mode.4F above the heating set-point. In the heating mode.1F(speaking precisely. 0.6F Heating Thermo OFF Heating Thermo ON 67 68 Heating Set-point 72F (= Cooling set-point – 0F) 69 70 71 72 73 74 75 76 77 78 79 To Cooling Changeover point 77. To Heating Changeover point 68.4F [3C]) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 20 © 2005 Daikin AC . because the room temperature is above cooling set-point plus 1F at the changeover point.Daikin Indoor unit Sequence of Operation Auto mode in H/R In the cooling mode.6F [2C])) To Cool at Setpoint + 5.6F below the cooling set-point. not thermo off mode.4F Cooling Set-point 72F Temp swing 9F Cooling Thermo ON Cooling Thermo OFF To Heat at Setpoint – 3.4F (= Heating set-point + 5. not thermo off mode. As the chart shows. When a room temperature comes down 3. it goes into the cooling mode with the cooling set-point that is the heating set-point plus the differential (0F). As the chart shows.1F basis around a heating set-point. (Set point) 74 73 72 H or L L Fan Off Do not set Dry mode from a BMS side. because an internal cooling setpoint is set based on a room temperature when Dry mode is selected. 6 min (For not returning moisture on a coil) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 21 © 2005 Daikin AC . so as to not further cool down the room temperature ƒ Set-point Å RETURN AIR (in case of RETURN AIR <= 75) ƒ Set-point Å RETURN AIR – 1F (in case of RETURN AIR > 76) ƒ The set-point is not displayed on the remote controller when Dry mode is engaged Unit Turned On Cool mode Dry mode Thermo-On (Call for Cooing) Thermo-Off Thermo-On (Call for Cooing) 76 75 Only allow an end user to select it from a remote controller in a zone.Daikin Indoor unit Sequence of Operation Dry Mode ƒ Dry mode is only selectable at the remote controller ƒ Dry mode cannot be scheduled from a multi-zone controller or through a Interface ƒ Set-point is determined based on the room temperature internally when the Dry mode is set. or ƒ Sensor in the BRC1E71 (Remote controller) ƒ It depends on the VRV indoor unit configuration (Field Setting *). ƒ Remote sensor (alternative of Return air sensor). Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 22 © 2005 Daikin AC . Return Air Sensor implemented in the unit Remote Sensor should be installed when Return Air Sensor cannot sense room temperature correctly BRC1E71 has a sensor (BRC2A71 doesn’t) (Remote sensor physically replace the Return Air Sensor ) * Field setting: see slide 58 for details. BMS can not provide the room temperature to the indoor unit.Room Temperature ƒ Room Temperature is either ƒ Indoor unit Return air sensor. ƒ An indoor unit works with one of them. Skyair and Mini-split ƒ Skyair* is connected to DIII-Net system directly ƒ Recognized as VRV III-S system which has only one indoor unit. DIII-Net (Daisy Chained) KRP928B2S DIIInet Adapter * Except for RXS30/36HVJU + FTXS30/36HVJU which requires KRP928BB2S as same as Mini-split. ƒ All objects are available. each indoor unit has to have KRP928BB2S. ƒ Mini-split is connected to the DIII-Net system with an optional adapter. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 FTXS/RX “RA” System Slide 23 © 2005 Daikin AC . ƒ Basic objects are available. KRP928BB2S ƒ KRP928BB2S is connected to the indoor unit ƒ If it is a multi system. VRV malfunction (Optional) goes to Outdoor unit Forced Off for each DIII-net line (Optional) BACnet Interface Malfunction (Optional) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 24 © 2005 Daikin AC .Status LED DIII-net #1 10 outdoor units 64 groups 128 indoor units DIII-net #2 10 outdoor units 64 groups 128 indoor units Option Board Slot (DAM411B51) for additional two DIII-net lines Ethernet LED DIII-net #1 & #2 Communication LED 24 Volt Power Supply 24v Com Gd Not Used * LED are good for troubleshooting. 55 for details. See slide 54. Battery backup Turn ON Alternative Configuration (Backup for Ethernet) Presentation Title : Presenter Name : Date Ethernet for BACnet connection and configuration Daikin BACnet Interface – DMS502B71 Programming Guide Slide 25 © 2005 Daikin AC . Daikin BACnet Object List ƒ One indoor unit has the following 26 objects #15. 18 Celsius Only Reserved #17. 21 Available for each DIII-Net system #19 Accumulated Power is not supported Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 26 © 2005 Daikin AC . 14 Instance Number 0 0 .5. 13.Object ID Format ƒ One indoor unit has the following 26 objects. 17.405. highlighted Object Type 0 .514 (0x80420A) = (2 * 2^22) + Instance Number Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 27 © 2005 Daikin AC .31 26 objects per indoor unit (See the previous page) (See the next page) Specify Indoor unit Specify Object Example Setpoint of DIII-Net system 2 and Group address 1-2 Object type AV Æ Object Number: 2 DIII-Net 2 & 1-2 Æ A/C number: 66 Setpoint Æ Member number: 10 Instance Number = 16. 20 .906 (0x420A) = (66 * 2^8) + (10) Object ID = 8.14.255 Mapped with DIII-Net system and Group Address 1 . 16. Air conditioner number ƒ Air conditioner (Indoor unit) number (0 to 255) is mapped with the DIII-Net System number (1 to 4) and Group Address (1-00 to 4-15) Group Addr. … DIIINet System … A/C Num. A/C Num. … Group Addr. 1 1-00 0 1-00 64 128 192 1-01 65 1-01 129 4 1-00 1 3 1-00 1-01 2 1-01 193 … (Port 2) (Port 3) (Port 4) 2-00 16 2-00 80 2-00 144 2-00 208 2-01 17 2-01 81 2-01 145 2-01 209 223 3-00 32 3-00 96 3-00 160 3-00 224 3-01 33 3-01 97 3-01 161 3-01 225 3-15 239 4-00 48 4-00 112 4-00 176 4-00 240 4-01 49 4-01 113 4-01 177 4-01 241 4-15 63 4-15 127 4-15 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 191 … 175 … 3-15 … 111 … 3-15 … 47 … 3-15 … … 2-15 … 159 … 2-15 … 95 … 2-15 … 31 … 2-15 … … 207 … 1-15 … 143 … 1-15 … 79 … 1-15 … 15 … 1-15 … (Port 1) … DIIINet System … A/C Num. … Group Addr. … DIIINet System 4-15 255 Slide 28 © 2005 Daikin AC . A/C Num. DIIINet System Group Addr. Auto-discovery ƒ Object list can be created with the Point List creation tool. Cimetrics BACnet Explorer Wireshark Network Analyzer Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 29 © 2005 Daikin AC . See BACnet Interface Design Guide. (See Slide 53) ƒ The BMS will get all available objects from the Daikin BACnet interface by reading the object list property in the Device object. and decrease -2C in heating in an indoor unit. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 30 © 2005 Daikin AC . Actual setpoint is not changed.BACnet Control Points (per DIII-net) (per DIII-net) * Increase internal setpoint +2C in cooling. Commands will not always match input status.BACnet Monitoring Points Note: Monitor unit status by StartStopStatus_XXX not StartStopCommand_XXX. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 31 © 2005 Daikin AC . Typical Objects for Indoor Unit ƒ Although a set of 26 objects for each indoor unit is available. mode button prohibit X X RemoteControlAirConModeSet_XXX BV 14 R/C SP adjust button prohibit X X RemoteControlTempAdjust_XXX Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 BV 16 © 2005 Daikin AC Slide 32 . you will use only some of them. Object type Member Number StartStopCommmand_XXX BO 1 StartStopStatus_XXX BI 2 AirConModeCommand_XXX MO 5 X AirConModeStatus_XXX MI 6 Room Temperature X RoomTemp_XXX AI 9 Setpoint X X TempAdjust_XXX AV 10 X AirFlowRateCommand_XXX MO 7 AirFlowRateStatus_XXX MI 8 AirDirectionCommand_XXX AV 22 Item Monitor Status (Read) Control (Write) X Unit On/Off X X Operation mode Fan Speed X X Air Flow Direction Object Name (_XXX means A/C number) (When indoor unit has a louver) X AirDirectionStatus_XXX AI 23 Alarm Status X Alarm_XXX BI 3 Malfunction Code X MalfunctionCode_XXX MI 4 R/C On/Off button prohibit X X RemoteControlStart_XXX BV 13 R/C Ope. Example: Present Value 149 = U4 error Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 33 © 2005 Daikin AC .Malfunction Code ƒ Decode Present value of Malfunction code to Daikin Error code VRV Service manual provide troubleshooting flow chart for each Error code. Optional Objects for Indoor Unit ƒ The following objects are also available Item Air Filter Sign Monitor Status (Read) Control (Write) X Air Filter Sign Reset X Object type Member Number FilterSign_XXX BV 11 FilterSignReset_XXX BV 12 Object Name (_XXX means A/C number) Communication Status X CommunicationStatus_XXX BI 20 Call for Cool/Heat Status (Thermo-on Status) X ThermoStatus_XXX BI 28 Compressor Status X CompressorStatus_XXX BI 29 Indoor Fan Status X IndoorFanStatus_XXX BI 30 Heater Status X HeaterStatus_XXX BI 31 ForcedThermoOFFCommand_XXX BO 24 ForcedThermoOFFStatus_XXX BI 25 EnergyEfficiencyCommand_XXX BO 26 EnergyEfficiencyStatus_XXX BI 27 Forced disable Call for Coo/Heat (Forced Thermo-off) X X Energy Saving X X Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 34 © 2005 Daikin AC . Monitor Status (Read) Control (Write) Central Control X X Forced System Stop X X Item Object type Member Number CL_Rejection_XXX BV 17 SystemForcedOff_XXX BV 21 Object Name (_XXX means A/C number) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 35 © 2005 Daikin AC . 64. 128 and 192. ƒ Assigned at Group address 1-00 on each DIII-Net system. Therefore air conditioner numbers are 0.Optional Objects for DIII-Net ƒ The following objects are for the DIII-net system. Limitation of KRP928BB2S for Mini-split ƒ 11 essential objects are available for mini-split Fan. 21 Available for each DIII-Net system Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 36 © 2005 Daikin AC . Auto mode are not available Not available for On/Off button prohibit When Mode or Setpoint button prohibit through KRP928. On/Off button will not be available on the remote controller #17. Available Objects Comparison Member Numer 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Point Name ON/OFF (setting) ON/OFF (status) Alarm Sign Error Code Operation Mode (setting) Operation Mode (status) Airflow Rate (setting) Airflow Rate (status) Measured Room Temperature Set Room Temperature Filer Limit Sign Filter Limit Sign Reset Remote Control Operation (ON/OFF) Remote Control Operation (Operation Mode) Blank Remote Control Operation (Set Temperature) Central Control (lower Central Contoll disable) Blank Accumulated Power Communication Status System Forced OFF Air Direction (setting) Air Direction (status) Forced Thermostat OFF (setting) Forced Thermostat OFF (status) Energy Efficiency Command (setting) Energy Efficiency Command (status) Thermostat Status Compressor Status Indoor Fan Status Heater Operation Status VRV. Skyair indoor unit Mini-Split through KRP928BBS2 StartStopCommand_xxx StartStopStatus_xxx Alarm_xxx MalfunctionCode_xxx AirConModeCommand_xxx AirConModeStatus_xxx AirFlowRateCommand_xxx AirFlowRateStatus_xxx RoomTemp_xxx TempAdjust_xxx FilterSign_xxx FilterSignReset_xxx RemoteControlStart_xxx RemoteControlAirConModeSet_xxx X X X X X X X X X X X X X X X X X X X (Cool. Heat only) RemoteControlTempAdjust_xxx CL_Rejection_xxx X X Object Name ElecTotalPower_XXX CommunicationStatus_xxx SystemForcedOff_xxx AirDirectionCommand_xxx AirDirectionStatus_xxx ForcedThermoOFFCommand_xxx ForcedThermoOFFStatus_xxx EnergyEfficiencyCommand_xxx EnergyEfficiencyStatus_xxx ThermoStatus_xxx CompressorStatus_xxx IndoorFanStatus_xxx HeaterStatus_xxx For DIII-Net X X X X X X X X X X X x x x X x X Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 37 © 2005 Daikin AC . Heat only) X (Cool. Not necessary to have additional controller. so that it is recommended not to enable any I-TC control functions. ƒ I-Touch Controller is beneficial as a centralized controller and gives some functions such like setback schedule. B ƒ Control function on I-Touch Controller might conflict the control from BMS.BMS just to Monitor or Control ƒ VRV system would work with Remote Controllers. etc. setpoint range limitation. auto changeover. ƒ You may put BMS just monitor the VRV system. I-Touch Controller might be installed as a backup controller in case that BMS and/or network is in a trouble. A ƒ You may put BMS control the VRV system to satisfy control requirements. BACnet DIII-Net DIII-Net BS Box DMS502B71 BACnet Interface BS Box DCS601C71 Intelligent Touch Controller REYQ VRVIII Heat Recovery Building Automation System BS Box Which controls the VRV system? FXMQ FXFQ Concealed Ceiling Ceiling Cassette BMS I-Touch Control A Monitor Control VRV B Control VRV Back up Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 FXAQ Wall Mounted BRC1E71 Navigation Remote Controller Slide 38 © 2005 Daikin AC . M8 error would occur on I-TC in 5 minutes. or 5 minutes after BACnet Interface is disconnected (or powered off). a lower classified multi zone controller such like I-TC on the same line is completely disabled. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 39 © 2005 Daikin AC . ƒ Manual operations are no longer available ƒ Any functions on I-TC would be disabled ƒ I-TC would be resumed once CL Rejection is disabled.CL Rejection and DIII-Net for a Backup Controller ƒ When CL Rejection is enabled for a DIII-Net line. ƒ If BMS is disconnected keeping CL Rejection enabled. and it is the time when I-TC is resumed. Cannot be adjusted through BMS. ƒ Changing of occupied setpoints is not necessary. and to heating at 3. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 40 © 2005 Daikin AC . ƒ Setback Schedule ƒ BMS should turn off the unit to enable setback. ƒ BMS should turn the unit on when setback setpoints have been reached and turn the unit off when room temperature has recovered.BMS to Satisfy Control Requirements ƒ Setpoint Range Limitation on Remote Controller ƒ Monitor and override setpoint when out of range. ƒ BMS should control changeover when tighter control is necessary. Total 9F room temperature swing would occur theoretically. ƒ Limit Setpoint Range by iTouch or Navigation Controller. ƒ Prohibit Remote Controller if necessary. ƒ Auto Changeover ƒ Indoor unit auto changes to cooling at 5.4F above the setpoint. ƒ Mode change must be sent to changeover master.6F below the setpoint. See the slide 16. BMS Setpoint Range Limit 80 79 78 77 76 75 Cool Setpoint Range Cool Setpoint 74 73 72 Heat Setpoint 71 70 Heat Setpoint Range 69 68 67 66 65 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 41 © 2005 Daikin AC . it shall override the setpoint to acceptable value. To detect setpoint change by a end user in a timely fashion. (COV is disabled at factory default) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 42 © 2005 Daikin AC .BMS Setpoint Range Limit Sequence of Operation Points Used – TempAdjust_XXX Control Logic BMS shall monitor temperature setpoint. COV would be considered. When BMS detects point out of range. BMS Autochangeover .Dual Setpoint Unit Turned On (Occ) Unit Turned Off (Unocc) 80 79 78 77 HeatÆCool 76 Changeover Point 75 Cool Setpoint 74 73 72 Heat Setpoint 71 CoolÆHeat 70 Changeover Point 69 68 67 66 65 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 43 © 2005 Daikin AC . AirConMode_XXX. * When using independent cooling and heating setpoints. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 44 © 2005 Daikin AC . When space temperature rises to 1oF (adj. BMS shall command the unit into heating and command a new setpoint. When space temperature drops to 1oF (adj. BMS shall command the unit into cooling and command a new setpoint.) below heating setpoint. the new setpoint must be communicated with every mode change as both heating and cooling setpoint memory locations are simultaneously overwritten when TempAdjust_XXX command is used. A 1 hour guard timer is recommended with this sequence to prevent excessive mode changeovers.BMS Autochangeover .) above cooling setpoint.Dual Setpoint Sequence of Operation Points Used – RoomTemp_XXX. TempAdjust_XXX Control Logic BMS shall monitor space temperature and temperature setpoint. 30 min delay (adj.Immediate 75 Changeover .BMS Autochangeover – Single Setpoint Unit Turned On (Occ) Unit Turned Off (Unocc) 80 79 78 77 76 Changeover .) Setpoint 74 73 72 71 Changeover .Immediate 69 68 67 66 65 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 45 © 2005 Daikin AC .30 min delay (adj.) 70 Changeover . BMS Autochangeover – Single Setpoint Sequence of Operation Points Used – RoomTemp_XXX. AirConMode_XXX. When space temperature rises to 2oF (adj. BMS shall command the unit into heating.) above setpoint. BMS shall command the unit into cooling.) below heating setpoint and maintains for 30 min. When space temperature drops to 3oF (adj. BMS shall command the unit into cooling. A 1 hour guard timer is recommended with this sequence to prevent excessive mode changeovers. BMS shall command the unit into heating.) above cooling setpoint and maintains for 30 min.) below setpoint. TempAdjust_XXX Control Logic – BMS shall monitor space temperature and temperature setpoint. * Commanding of new setpoints is not necessary. When space temperature rises to 3oF (adj. When space temperature drops to 2oF (adj. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 46 © 2005 Daikin AC . BMS Setback Unit Turned On (Occ) Unit Turned Off (Unocc) 80 79 78 77 Setback BMS turn on the unit when necessary HeatÆCool 76 Changeover Point 75 Cool Setpoint 74 73 72 Heat Setpoint 71 CoolÆHeat 70 Changeover Point 69 68 67 66 65 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Setback Slide 47 © 2005 Daikin AC . Unit shall try and control to occupied setpoints. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 48 © 2005 Daikin AC . StartStopCommand_XXX Control Logic – BMS shall energize the unit once setback setpoints have been reached.BMS Setback Sequence of Operation Points Used – RoomTemp_XXX. BMS shall de-energize the unit once temperature has dropped (when cooling) or risen (when heating) the set differential which is adjustable. the indoor unit will resume with the previous setting from power failure. The last change would be valid in the indoor unit either from BACnet Interface or Remote Controller. ƒ The indoor unit doesn’t have priority.Notes to program ƒ C/F conversion ƒ Since Daikin BACnet Interface supports Celsius only. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 49 © 2005 Daikin AC . ƒ EEPROM ƒ Every change you made will be transferred to an Indoor unit. With this. ƒ The Indoor unit stores the latest setting in EEPROM which has the maximum writable number of 100. so that the highest priority value would be transferred to the indoor unit. ƒ Priority Array ƒ An object in the BACnet Interface has a priority array. Releasing BMS value by sending a NULL command will revert point to default settings stored in the gateway of 25oC (77oF). ƒ Do not change anything frequently and you will be ok. Keep below 19 average per day. so that you may have to make conversion program if BMS doesn’t support it natively.000 times. a BBMD is required and should register BACnet Interface as a Foreign Device. ƒ BACnet Interface should also be configured as a Foreign Device and set BBMD IP address and port No.Foreign Device ƒ When BACnet Interface is in a different subnet from BMS. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 50 © 2005 Daikin AC . and ITC control is disabled. and auto changeover.ITC V6 ƒ When you install ITC V6 as a backup controller. ITC would change the setpoint because ITC manages individual C/H setpoints. C/H setpoint differential to 0* (single setpoint mode) ƒ Otherwise when BMS change the mode. ƒ Also configure it as a Single Setpoint Mode ƒ Set Min. ƒ Or enable CL Rejection. setpoint range limitation. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 51 © 2005 Daikin AC . disable all controls such as schedule. The BMS will get all available objects from the Daikin BACnet interface by reading the object list property in the Device object. Can the BACnet gateway be configured to report temperature values in oF? A. No limitations that I’m aware of. Q. individually applied? A. Q. Can the BACnet gateway be set up as a BACnet Broadcast Management Device (BBMD)? A. Q. What changes can be globally applied vs. however it can be setup as a foreign device to communicate directly with a BBMD on a different subnet. Unit by unit (or units in remote control group). and Instance Number for each point. Must mode changes be done unit by unit or can they be done globally? A. Allows for less potential for error as manual command which can require matching up Port Number. No. No. Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 52 © 2005 Daikin AC . does the BACnet gateway comply with? Is the gateway BTL certified? A.Q&A Q. 135-2004 and BTL certified in 2007. SystemForcedOff_XXX and CL_Rejection_XXX can be applied globally. Units must be addressed individually at the remote controller. The BACnet interface can only handle values in oC. What ASHRAE std. There is currently no auto-addressing capability. Q. Q. Most efficient way to address indoor units? A. How to execute Gateway self-discovery? Capability of this function? Limitations? A. Q. The Daikin BACnet Interface was designed per ASHRAE std. Object ID. pdf Protocol Implementation Conformance Statement (PICS) ƒ http://www.daikinac.Online Documentation ƒ Installation Manual ƒ http://www.bacnetinternational.net/btl/index.BACnet Interface DMS502B71.com/DOC/BACnet%20Gateway%20DMS502B71%20 ƒ ƒ ƒ ƒ -%20Installation%20Manual%20-%20Daikin.pdf BTL Product Listing ƒ http://www.daikinac.20%20-%20Daikin.pdf Design Guide ƒ http://www.daikinac.daikinac.com/DOC/BACnet%20Gateway%20DMS502B71%20 -%20%20Design%20Guide%20-%20ED72-749A%20-%20Daikin.php?m=29 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 53 © 2005 Daikin AC .pdf Submittal Data Sheet ƒ http://www.com/commercial/documents/sds/SDS%20DMS502B7 1.com/commercial/documents/BACnet%20gateway%2 0PICS%20statement%20Ver%206. Extracted from BACnet Interface Design Guide Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 54 © 2005 Daikin AC . Extracted from BACnet Interface Design Guide Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 55 © 2005 Daikin AC . For Indoor unit Fan Control Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 56 © 2005 Daikin AC . For Indoor unit Fan Control Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 57 © 2005 Daikin AC . BRC1E71 sensor Only - Field Settings ƒ To use only BRC1E71 sensor, set field settings as 10-2-03, 10-5-02 & 1C-1-02 ƒ To use Return air sensor or Remote sensor, set as 10-2-02, 10-5-01 & 1C-1-01 ƒ 10-2-03, 10-5-02 availability ƒ FXMQ_P, FXTQ_P, FTQ_P: always available ƒ All _M series (except FXFQ, FXHQ, FCQ, FHQ) ƒ Manufactured after 9/1/2009: always available ƒ Manufactured before 9/1/2009: confirm if 10-2-03, 10-5-02 are available. ƒ FXFQ, FXHQ, FCQ, FHQ: never available ƒ Set 10-2-01 and use Remote sensor (or Return air sensor) only Which single sensor is used? For indoor unit control (Cool/Dry/Heat VRV and thermo-on/off control) For BRC1E71 control (Auto changeover and setback control) (Which sensor temperature is sent to Mulizone Controller such as BACnet Interface and I-TC) BRC1E71 sensor 10-2-03 1C-1-02 (default) 10-5-02 Remote sensor (or Return air sensor) 10-2-02 (it is always available) 1C-1-01 10-5-01 (default) Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 For Multizone Control Slide 58 © 2005 Daikin AC Appendix Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 59 © 2005 Daikin AC Functionality BMS vs. iTouch / BRC1E71 ƒ Autochangeover ƒ Setback ƒ Setpoint Range Limit ƒ Scheduling ƒ Button Prohibit Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 60 © 2005 Daikin AC iTouch / BRC1E71 Autochangeover. Setback. and Setpoint Range Limit Unit Turned On (Occ) Unit Turned Off (Unocc) 80 Setback 79 78 77 HeatÆCool 76 Changeover Point 75 Cool Set-point 74 73 72 Heat Set-point 71 CoolÆHeat 70 Changeover Point 69 68 67 66 65 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Setback Slide 61 © 2005 Daikin AC . Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 62 © 2005 Daikin AC . Setpoint Range Limit – Individual cooling and heating setpoints can be bound by setpoint range limit between 60oF and 90oF. it shall energize once setback setpoints have been reached and de-energize once temperature has dropped (when cooling) or risen (when heating) the set differential which is adjustable. changeover to cooling mode shall occur at cooling setpoint + 1oF. Setback – When the unit is off during the unoccupied period. When in cooling mode. changeover to heating mode shall occur at heating setpoint – 1oF.iTouch / BRC1E71 Sequence of Operation Auto Changeover (BRC1E71) – When in heating mode. 4 Exception Schedules Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 63 © 2005 Daikin AC .iTouch / BRC1E71 Scheduling Three weekly schedule pattern options are available: 7-Day. and 5+1+1 (Weekday + Saturday + Sunday). 8 Schedules. BRC1E71: Supports up to 5 On/Off operations per day. 1 Schedule iTouch: Supports up to 8 On/Off operations per day. 5+2 (Weekday + Weekend). Open Protocol Solutions ƒ Gateways to Open Protocol Networks ƒ Vendor neutral control for Daikin air conditioning products DMS502B71 DMS504C71 BACnet® Interface LonWorks® Interface Communications BACnet IP Data Link Layer (Annex J) LonTalk® Protocol Connectivity (Network) FT-X1 (78Kbps Free Topology) VRV outdoor unit quantity 10/100 BASE-T Ethernet DIII-Net x 2 channels Another 2 channels with DAM411B51 Option 20 → 40 with DAM411B51 Option VRV indoor unit quantity 128 → 256 with DAM411B51 Option 64 Monitor & control VRV indoor units 24 VAC 50/60Hz Monitor & control VRV indoor units 24VAC 50/60Hz VRV (All Unit Types and Sizes) SkyAir Single Split Systems* Multi Split Systems* VRV (All Unit Types and Sizes) SkyAir Single Split Systems* Multi Split Systems* Connectivity (Daikin) Control points Power supply Applicable Daikin products *KRP928B2S DIII-net adapter required. DIII-Net x 1 channel 10 Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 64 © 2005 Daikin AC . Status LED Service Switch F1 F2 goes to outdoor unit 24V + ground T1 T2 Forced system shut down Presentation Title : Presenter Name : DateTwisted pair to LonGuide connection Daikin BACnet Interface – DMS502B71 Programming Slide 65 © 2005 Daikin AC . 52.5.Battery Backup Switch Cable connection for commissioning Cable provided by commissioning agent DLS-CABLE-9PIN Terminal Resistance No resistance (factory default). or 105 ohms Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 66 © 2005 Daikin AC . LonWorks SNVT List Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 67 © 2005 Daikin AC . Network Variables Presentation Title : Presenter Name : Date Programming Guide Daikin BACnet Interface – DMS502B71 Slide 68 © 2005 Daikin AC . Thank You . © 2006 Daikin AC .
Copyright © 2024 DOKUMEN.SITE Inc.