UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIESSUMMARY OF COST Item No. Description Sub Total of Item - A. H.T. & L.T. OUTDOOR PAD MOUNTED EQUIPMENT. Sub Total of Item - B. H.T. & L.T. CABLE SYSTEM. Sub Total of Item - C. STREET LIGHT SYSTEM. TOTAL AMOUNT (A+B+C) Amount (Rs.) A. B. C. EE - 1 T. Each 170 EE . testing and commissioning of following HT pad mounted switches as per WAPDA Specification No. to the approval of the Consultant/ Engineer. Technical Specifications/ Standards on the already prepared foundation. a) b) c) 400 KVA 200 KVA 100 KVA Each Each Each 17 6 3 A-3 Supply at work. switches. technical specifications. for H. a) b) c) 4-Way Switch 3-Way Switch Earth Fault Indicators for above mentioned Switches Each Each Each 2 3 12 A-2 Preparation of foundation for following Pad Mounted distribution transformers conforming to requirements. Unit Rate (Rs. and to the approval of the Consultant/ Engineer. Standards. drawings. a) b) c) d) 400 KVA 200 KVA 100 KVA Earth Fault Indicators for above mentioned PMTs Each Each Each Each 17 6 3 26 A-4 Prepartion of foundation for LT Distribution Boxes (Service Box). foundation conferming to requirements. Installation. HRC fuses etc. Cable connections and MCCB of required ratings and earth fault indicators conforming to relevant WAPDA/ IEC. standards. testing and commissioning of following outdoor type Pad Mounted distribution transformers with kiosk and required number of H. and approval of the Consultant/ Engineer..2 . Drawings etc.T. as per item A-2 above.) A-1 Supply at work.UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES A . Installation. Technical Specifications.) Description Unit Quantity Amount (Rs. DD-S-46:90 amended to-date and Technical Specifications and earth faulot indicators and provision of foundation according to Drawingprovided by manufacturer and approval of the Consultant/ Engineer.HT & LT OUTDOOR PAD MOUNTED EQUIPMENT Item No. installation.00 EE . testing and commissioning of 3Phase LT Distribution Boxes (Service Box) comprising of aluminium busbar. clamp. including ground conductor (10 mm stranded GI wire).UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES A .3 . to the approval of sthe Consultant/ Engineer.5 Ohms as required for completion of the item as per requirements. A-6 Supply at work.) A-5 Supply at work. 185 mm2 LT power cable for providing of electric connections to the Commercial Consumers as indicated in the drawing. specifications. to the approval of asthe Consultant/ Engineer. 185 mm2 LT power cable for providing of electric connections to the Residential Consumers as indicated in the drawing.HT & LT OUTDOOR PAD MOUNTED EQUIPMENT Item No. testing and commissioning of 3Phase LT Distribution Boxes (Service Box) comprising of aluminium busbar. Installation. Pad Mounted Distribution Transformers and LT Distribution Boxes.S galvanized earth rod 5/8" x 10' and earth rod clamp etec. Unit Rate (Rs. A-7 Supply at works. Sub-Total : A Each 170 Each NIL Each 258 0. terminal lugs suitable for 4-Core PVC/PVC. to achieve the specified earthing results up to 2. The Distribution Boxes are to be installed on the already prepared foundations as per Item A-4 abvoe. installation. The Distribution Boxes are to the installed on the already prepared foundations as per item A-4 abvoe. drawings and approval of the Consultant/ Engineer. terminal lugs suitable for 4-Core PVC/PVC.) Description Unit Quantity Amount (Rs. M. 4-Way Switches. testing & commissioning of Earthing System for HT 3-Way. specifications.4 . and to the approval of the Consultant/ Engineer.00 B-5 Back filling of any type of trench already excavated as per item B-1 after laying various cables (HT & LT) including sand. a) b) 500 mm2 XLPE 1-Core Cable 120 mm2 XLPE 3-Core Cable Each Each 24.118. & L.00 EE .UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES B . specifications and to the approval of the Consultant/ Engineer.H.) Description Unit Quantity Amount (Rs. testing and commissioning of following LT PVC/PVC un-armoured cable with Aluminum conductor laid directly in sand layer in already excavated trenches or through the RCC/PVC pipe (already installed at road crossings) as per requirement. Llaying. and to the approval of sthe Consultant/ Engineer. laying directly in sand layer in already excavated trenches or through the RCC and/or PVC pipe (already installed at road crossings) including cable binding ties for single core cables as per requirement. Earthing.40 B-4 Supply at works.960 KM KM 11. testing and commissioning of following HT heat shrinkable termination kits of Raychem / 3-M / Cellpack for cables laid under weork item B-2.15 B-3 Supply at work. site cleaning etc. Unit Rate (Rs. including cable glands and miscellaneous materials and installation as per requirements. and to the approval of the Consultant/ Engineer. specifications and standards provided inthe given drawings and to the approval of the Consultant/ Engineer. as per dimensioins given on the drawings.240.T.05 6. provided in the given drawings.) B-1 Excavation of every type of trench in any type of soil within the project area for laying of HT & LT cables.00 131. standards. B-2 Supply at work. CABLE SYSTEM Item No.00 62. a) 185 mm2 4-Core Cable KM 11. standards. testing and commissioning of following HT XLPE arooured cables with Aluminum conductor. protective bricks and excavated earth compacted to 95% modified AASHTO density in layhers of snot exceeding 9" thickness. installation. a) b) 500 mm2 1-Core Cable 120 mm2 3-Core Cable Cft 524. a) b) Sand (Bed and Cover) Bricks (Protection Cover) (3" thick) Cft Sft 97. as per drawings.T. Laying. 00 115.) Cft KM Each 225. standards.00 14. drawings and to the approval of the Consultant/Engineer. laying and jointing of 6" dia RCC pipe of following ducts as shown in drawings including concrete complete in all respect. B-10 with Ravi Sand including re-laying of sub-base and base course material compacted to 100% modified AASHTO density and Asphalt concrete complete to the satisfaction of Engineer. and approval of the Consultant/ Engineer.00 B-10 Cutting of Asphaltic road. B-12 Providing. B-11 Back filling of road cuts for item No. drawings.00 15.UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES B .T.Core Cable b) 120 mm² 3-Core Cable Supply at works. CABLE SYSTEM Item No.733. & L. Each Each 25.T.00 Each 409.) Description c) Excavated earth back filling and compaction d) Warning tape 30 cm width Unit Quantity Amount (Rs. base.00 Sft 250.00 B-9 R-M 120.00 75.5' for PVC/RCC pipe ducts.5 . Supply at works and installation of straight cable joints (splices) of Raychem / 3-M / Cellpack for 11-KV Cable as per specifications. installation. testing and commissioning of following L.T. sub-base and excavation in all types of soil upto 5. heat shrinkable termination kits of Raychem / 3-M / Cellpack for cables laid under work item B-3.00 B-6 Supply at work and installation of HT & LT cable markers as per specifications. B-7 B-8 a) 500 mm² 1. specifications and to the approval of the Consultant/ Engineer.00 Rft Rft 335. including cable glands and miscellaneous materials and installation as per requirements.00 Sub-Total : B 0 EE .H. a) b) Duct type (1'-6" X 2'-6") Duct type (2'-0" X 4'-0") Sft 250. Unit Rate (Rs. a) 185mm² LT 4-Core PVC/PVC Cable Provision of Horizontal thrust boring at road crossing including UPVC 6" pipe make (Beta/Dadex or approved make from Consultant/ Engineer) back filling and compaction for HT and LT Cables road crossing where road crossing sleeves are not available as per site requirement and approval of the Consultant/ Engineer. photo cell.Core 2. complete connections. nut & bolts etc. connectors. and approval of the consultant/ Engineer.UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES C . specifications. testing and commissioning of Pole Base Connection Boxes/ Plate complete comprising circuit breakers. Sigle Arm Supply at work.5 EE . Sigle Arm Supply at work . a) 25 mm² b) 16 mm² 1. 25 mm² 4-Core Cable Each Each 71 117 C-2 KM 0. testing and commissioning of LT Street Light Single Core PVC/PVC Aluminium Cable laid directly in the already excavated trenches as per item B1. Round Conical Shaped including provision of concrete foundations as per standards.05 C-4 supply at works and installation. and approval of the Consultant/Engineer. a) 12 M height.Core Cable 1-Core Cable KM KM 7. complete in all respects as per design. Duble Arm b) 8 M height. as per drawings. Hot dipped galvanized. Hot dipped galvanized. Laying. specifications and apprival of the Consulatant/ Engineer.6 . Laying. Each Each 71 117 C-5 Each 2 C-6 KM 3. Complete installation of Street Light poles.02 21. testing and commissioning of LT Street Light PVC/PVC Aluminium Cable laid directly in the already excavated trench as per item B-1 and as per drawings. as per drawings. control switches and monitoring switches etc including provision of RCC foundation. testing & commissioning of Street Light Control Panel complete in all respect with MCCB magnetic contactor relay. testing and commissioning of 2. Unit Rate (Rs.07 C-3 Supply at work. Supply at works and installation. Hot dipped galvanized.5mm² PVC/PVC Copper Conductor Cable between pole base connection box/ plate and light fixture gear compartment inside the street light pole. specification and approval of the Consultant/Engineer for: a) 12 M height. specifications.) C-1 Supply at work. specifications and approval of the Consultant/ Engineer. installation.) Description Unit Quantity Amount (Rs. Duble Arm b) 8 M height. drawings and approval of the Consultant/ Engineer. with provision of cable binding ties and as per drawings. Hot dipped galvanized.STREET LIGHT SYSTEM Item No. e. installation. clamp.7 . installation on street light poles testing and commissioning of road light fixture. having high pressure aluminium diecast LM6 (low copper content) housing suitable for lamps of following ratings with post-toop/ lateral mounting.. replaceable. Faceted..STREET LIGHT SYSTEM Item No. M. Sub-Total : C Unit Quantity Amount (Rs. Unit Rate (Rs. testing & commissioning of Earthing System for Street Light poles and Control Panels. complete with i) Ballast 100 W IMPG (Watt loss = < 20 W) ii) Ignitor SN-58 T5 (Timed Semi Parallel Impulse type) i) Capacitor 15 MFD (metallic push -in type) b) Indalux (Viento) IVH6/ Philips SPG-338.or other approved brands. complete with Lamp SON-T (PIA Plus). 250 W (32000 Lumens) with: i) Ballast 250 W IMPG (Watt loss = < 26 W) ii) Ignitor SN-58 T5 (Timed Semi Parallel Impulse type) i) Capacitor 35 MFD (metallic push -in type) Supply at works. adjustable optics with quick lateral & vertical lamp adjustments. including ground conductor (10 mm stranded GI wire).S galvanized earth rod 5/8" x 10' and earth rod clamp etc. IP 66 rating for lamp compartment.) C-7 Each 117 Each 142 C-8 Each 190 0 EE . indalux/ Philips or approved equivalent. lamp/ ballast/ ignitor/ capacitor should be og single brand and conforming to approved international standards: with power factor correction capacitor.UNDERGROUN EXTERNAL ELECTRIFICATION AND STREET LIGHT SYSTEM SEC U & T (EXTN) PHASE-VII DHA LAHORE BILL OF QUANTITIES C . ignitor etc. to achieve the specified earthing results up to 5 ohms all comlete as per specificayions. ballast. All light components i. and approval of the Cinsultant/ Engineer. as per specifications and approval of the Consultant/ Engineer of following types: a) Indalux (Viento) IVH! / Philips SPG-328. clear press glass bowl. Tempered.) Description Supply at work. 2092736905 ijaz .
Report "1- Boq of Phase-Vii Dha Lhr Exten Sec u & t"